CONTROL WIRING
Use 2-Core stranded shielded communication wire. Wiring length limitations must be observed to avoid any
communication interference.
Table 29 —Wiring Length Limitation
Fig. 19 —Controls Wiring
Max. length to Outdoor
L1+L2,L5
≤3937ft [1,200m]
AWG 18
Max. total length to Indoor units
L3, L3+L4
≤3937ft [1,200m]
AWG 18
Max. length from controller to indoor units
L6+L7+ L8+ L9, L10+L11
≤820ft [250m]
AWG 18