54
Table 61 —Twinned Port Indoor Unit Pipe Selection (g,h,i,j)
Table 62 —Y-Joint Selection
Fig. 51 —Piping Length and Height between Indoor Unit and MDC
Fig. 52 —Total Piping Length Restrictions
INDOOR UNIT CAPACITY
Y-JOINT MODEL
LIQUID SIDE (in.)
GAS SIDE (in.)
g
h
i
j
72
40VM900043
3/8
3/8
5/8
5/8
96
3/8
3/8
7/8
5/8
TOTAL CAPACITY
DOWNSTREAM INDOOR
UNITS (KBTU/H)
Y-JOINT
MODEL
HIGH PRESSURE SIDE (in.)
LOW PRESSURE SIDE (in.)
LOW PRESSURE SIDE (in.)
< 72
40VM900041
5/8
3/4
3/8
73~108
3/4
7/8
3/8
109~126
40VM900042
3/4
1-1/8
1/2
127~144
7/8
1-1/8
1/2
145~168
7/8
1-1/8
5/8