![Carrier 38APD115 Скачать руководство пользователя страница 61](http://html.mh-extra.com/html/carrier/38apd115/38apd115_manual_2560531061.webp)
61
temperature is satisfied, the Control Mode
9
(SPT Satisfied)
will be displayed.
OCCUPANCY SCHEDULE — With the control method set
to Occupancy,
CTRL=
2
(Occupancy), the Main Base Board
will use the operating schedules as defined under the
Time
Clock
mode in the scrolling marquee display. If
Time
Clock
o
SCH.N
(Schedule Number) is set to
0
, the unit will
remain in an occupied mode continuously.
In either case, and whether operating under a Local Sched-
ule or under a CCN Schedule, under normal operation,
Run
Status
o
VIEW
o
STAT
(Control Mode) will be
1
(Off Local)
when the Enable/Off/Remote Control switch is Off or in Re-
mote Control with the external contacts open. The control
mode will be
3
(Off Time) when the Enable/Off/Remote Con-
trol switch is in Enable or Remote Control with external con-
tacts closed and the time of day is during an unoccupied period.
Similarly, the control mode will be
7
(On Time) when the time
of day is during an occupied period. If the machine is ON, the
Control Type
Configuration
o
OPT2
o
C.TYP
=5
(SPT Multi)
is used, and the space temperature is satisfied, Control Mode
9
(SPT Satisfied) will be displayed.
Local Schedule — Local Schedules are defined by schedule
numbers from 1 to 64. All of these schedules are identical.
The schedule number (
Time Clock
o
SCH.N
) must be set to a
number greater than 0 for local schedule. For unit operation,
the Enable/Off/Remote Control switch must be in the Enable
or Remote Control position with external contacts closed.
For this option to function properly, the correct time, day
and date must be set. See the section Time, Day, and Date on
page 59. The time clock is programmed in a 24-hour format,
00.00 to 23.59. If configured, the 38AP controls can
automatically adjust the time for daylight savings time. See the
section Daylight Savings Time on page 59.
If holidays are to be used, they must be configured. Thirty
holidays are provided as part of the local schedules,
HD.01
through
HD.30
. Each holiday requires a Holiday Month,
Time
Clock
o
HOL.L
o
HD.xx
o
MON
(Holiday Start Month)
where “xx” is a number from 01 to 30; the Holiday Start Day
of Month,
Time Clock
o
HOL.L
o
HD.xx
o
DAY
(Start Day)
where “xx” is a number from 01 to 30; and the Holiday Dura-
tion,
Time Clock
o
HOL.L
o
HD.xx
o
LEN
(Duration [Days])
where “xx” is a number from 1 to 99. Holidays that do not oc-
cur on fixed dates will require annual programming.
In the example shown in Table 20, the following holidays
are to be programmed: January 1 for one day, July 4 for one
day, December 24 for two days.
Eight separate time periods, Period 1 through 8, are avail-
able as part of the local schedule. Each period has Monday
through Sunday and a Holiday day flag, and occupied and un-
occupied times. For example, an occupied time from 6:00 AM
to 8:00 PM is desired from Monday through Friday. For Satur-
day an occupied period from 6:00 AM to 12:00 Noon is de-
sired. On Sunday and holidays the unit is to remain unoccu-
pied. This schedule is shown graphically in Fig. 79.
To program this schedule,
Time Clock
o
SCH.N
(Schedule
Number) must change from 0 to a number between 1 and 64.
In this example, the Schedule Number will be 1. Two of the
eight time periods are required to create this schedule. See Ta-
ble 21.
Table 20 — Holiday Required Configurations
TIME CLOCK MODE
SUBMODE
SUB-
SUBMODE
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
HOL.L
HD.01
MON
XX
Holiday Start Month
Default: 0
Range: 0 to 12
(0=Not Used, 1=January, 2=February, etc.)
Example = 1
DAY
XX
Start Day
Default: 0
Range: 0-31
(0=Not Used)
Example = 1
LEN
XX
Duration (Days)
Default: 0
Range: 0 to 99
(0=Not Used)
Example = 1
HD.02
MON
XX
Holiday Start Month
Default: 0
Range: 0-12
(0=Not Used, 1=January, 2=February, etc.)
Example = 7
DAY
XX
Start Day
Default: 0
Range: 0 to 31
(0=Not Used)
Example = 4
LEN
XX
Duration (Days)
Default: 0
Range: 0 to 99
(0=Not Used)
Example = 1
HD.03
MON
XX
Holiday Start Month
Default: 0
Range: 0 to 12
(0=Not Used, 1=January, 2=February, etc.)
Example = 12
DAY
XX
Start Day
Default: 0
Range: 0 to 31
(0=Not Used)
Example = 24
LEN
XX
Duration (Days)
Default: 0
Range: 0 to 99
(0=Not Used)
Example = 2