APPENDIX B — CCN TABLES (cont)
Service Table
SERVICE
Setpoint Table
SETPOINT
DESCRIPTION
VALUE
UNITS
POINT NAME
NETWORK
ACCESS
COMPRESSOR ENABLE
Enable Compressor A1
Default: Depends on Unit
Model. If Compressor Size
is greater than 0, value is
Enable.
ENABLEA1
Read/Write
Enable Compressor A2
ENABLEA2
Read/Write
Enable Compressor A3
ENABLEA3
Read/Write
Enable Compressor B1
ENABLEB1
Read/Write
Enable Compressor B2
ENABLEB2
Read/Write
Enable Compressor B3
ENABLEB3
Read/Write
Reverse Rotation Enable
Disable/Enable
Default: Enable
REVR_VER
Read/Write
Two Comp Ckt Oil Mgmt
Disable/Enable
Default: Enable
TCOM_EBL
Read/Write
DESCRIPTION
VALUE
UNITS
POINT NAME
NETWORK
ACCESS
COOLING
Cooling Setpoint 1
NNN.n
Range: 40.0 to 80.0 (4.4 to 26.7)
Default: 60.0 (15.6)
°F (°C)
CSP1
Read/Write
Cooling Setpoint 2
NNN.n
Range: 40.0 to 80.0 (4.4 to 26.7)
Default: 55.0 (12.8)
°F (°C)
CSP2
Read/Write
Space T Cool Setpoint
NNN.n
Range: 65.0 to 80.0 (18.3 to 26.7)
Default: 78.0 (25.6)
°F (°C)
SPT_SP
Read/Write
Space Temperature Offset
NN.n
°F (°C)
SPTO
Read Only
Space T SP Plus Offset
NNN.n
°F (°C)
SPSP_PO
Read Only
Percent Cap. Requested
NNN
%
PERCAP
Read Only
Lo Cool On Setpoint
NN.n
Range: –1.0 to 2.0 (–0.6 to 1.1)
Default: 1.0 (0.6)
'
F (
'
C)
DMDLCON
Read/Write
HI Cool On Setpoint
NN.n
Range: 0.5 to 20.0 (0.3 to 11.1)
'
F (
'
C)
DMDHCON
Read/Write
Lo Cool Off Setpoint
NN.n
Range: 0.5 to 2.0 (0.3 to 1.1)
Default: 0.5 (0.3)
'
F (
'
C)
DMDLCOFF
Read/Write
RAMP LOADING
Cooling Ramp Loading
N.n
Range: 0.2 to 2.0
Default: 1.0
CRAMP
Read/Write
Head Setpoint ON
NNN.n
Default: 115.0 (46.1)
°F (°C)
HSP_ON
Read/Write
Head Setpoint OFF
NNN.n
Default: 72.0 (22.2)
°F (°C)
HSP_OFF
Read/Write
Fan On Set Point
NNN.n
Default: 105.0 (40.5)
°F (°C)
FANONSP
Read Only
Fan Off Set Point
NNN.n
Default: 55.0 (12.8)
°F (°C)
FANOFFSP
Read Only
Fan Stage Delta
NNN.n
Default: 15.0 (8.3)
'
F (
'
C)
FSTGDLTA
Read/Write
Fan Delta Active Time
NNN
Default: 60
sec
FANDLTTM
Read/Write
OAT Lockout Temperature
NNN.n
Range: –20.0 to 80 (–28.9 to 26.7)
Default: 30.0 (–1.1)
°F (°C)
OATLOCK
Read/Write