ENERGY MANAGEMENT MODULE (EMM) — The
EMM module (Fig. 22) is a factory-installed option or field-in-
stalled accessory that provides inputs for various energy man-
agement or unit control functions as listed below:
• 4 to 20 mA Temperature Reset Input*
• 4 to 20 mA Cooling Set point Input*
• 4 to 20 mA Requested Cooling Capacity Input*
• 4 to 20 mA Demand Limit*
• Single or Two-Step Demand Limit Inputs†
• Discrete thermostat inputs Y3 and Y4 for Dual Thermo-
stat Control†
*A field supplied 4 to 20 mA signal generator is required to
use these options with the EMM.
†Single or Two-Step Demand Limit cannot be used in con-
junction with Dual Thermostat Control,
C.TYP=
8
.
Addressing — The board address is set by the DIP switch S1
as follows:
Inputs —
Several inputs are used for status signals and safe-
ties. See Table 6.
CURRENT SENSING BOARD (CSB) — The CSB is used
to monitor the status of each compressor by measuring current
and providing an analog input to the main base board (MBB)
or compressor expansion module (CXB). Table 7 lists CSB in-
put connections.
ENABLE/OFF/REMOTE CONTACT SWITCH —
The
Enable/Off/Remote Control switch is a 3-position switch used
to control the unit. When switched to the Enable position, the
unit is under its own control. Move the switch to the Off posi-
tion to shut the unit down. Move the switch to the Remote Con-
trol position and a field-installed dry contact can be used to
start the unit. The contacts must be capable of handling a
24 vac, 50 mA load. In the Enable and Remote Control (dry
contacts closed) positions, the unit is allowed to operate and re-
spond to the scheduling configuration, CCN configuration and
set point data. See Fig. 23.
EMERGENCY ON/OFF SWITCH — The Emergency On/
Off switch should only be used when it is required to shut the
unit off immediately. Power to the MBB, CXB, AUX, EMM,
and scrolling marquee display is interrupted when this switch is
off and all outputs from these modules will be turned off. See
Fig. 23.
FAN STATUS SWITCH (FS1, FS2) — A proof-of-fan oper-
ation is recommended and needs to be field-installed in the in-
door unit. Several different types of switches can be utilized,
such as a differential pressure switch located across the indoor
fan or auxiliary contacts on an indoor fan contactor. The con-
tacts must be rated for dry circuit application capable of han-
dling a 24-vac load up to 50 mA. See Fig. 24.
CAUTION
Care should be taken when interfacing with other manufac-
turer’s control systems due to power supply differences,
full wave bridge versus half wave rectification. The two
different power supplies cannot be mixed.
Comfort
Link
controls use half wave rectification. A signal isolation
device should be utilized if a full wave bridge signal gener-
ating device is used.
SWITCH NUMBER/POSITION
1
2
3
4
ON
ON
ON
ON
CEBD430351-0396-01C
CEPL130351-01
PWR
J1
J2
J4
J3
J5
J6
J7
LEN
STATUS
RED LED - STATUS
GREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
ADDRESS
DIP SWITCH
Fig. 22 — EMM Board