APPENDIX B — CCN TABLES (cont)
Maintenance Tables (cont)
LEARNFNS
LOADFACT (Capacity Control)
PM-COIL (Condenser Coil Preventative Maintenance)
DESCRIPTION
VALUE
UNITS
POINT NAME
NETWORK
ACCESS
SCT Delta for Comp A1
NNN.N
'
F (
'
C)
A1SCTDT
Read Only
SCT Delta for Comp A2
NNN.N
'
F (
'
C)
A2SCTDT
Read Only
SCT Delta for Comp B1
NNN.N
'
F (
'
C)
B1SCTDT
Read Only
SCT Delta for Comp B2
NNN.N
'
F (
'
C)
B2SCTDT
Read Only
DESCRIPTION
VALUE
UNITS
POINT NAME
NETWORK
ACCESS
CAPACITY CONTROL
Load/Unload Factor
NNN
SMZ
Read Only
Control Point
NNN.n
°F (°C)
CTRL_PNT
Read/Write
Return Air Temperature
NNN.n
°F (°C)
RETURN_T
Read/Write
Supply Air Temperature
NNN.n
°F (°C)
SUPPLY_T
Read/Write
Ramp Load Limited
OFF/ON
MODE_5
Read Only
Slow Change Override
OFF/ON
MODE_9
Read Only
Low Temperature Cooling
OFF/ON
MODE_17
Read Only
High Temperature Cooling
OFF/ON
MODE_18
Read Only
Minimum Comp. On Time
OFF/ON
MODE_23
Read Only
DESCRIPTION
VALUE
UNITS
POINT NAME
NETWORK
ACCESS
Coil Cleaning Srvc Inter
NNNNN
Range: 0 to 65,500
Default: 8760
hours
SI_COIL
Read/Write
Coil Service Countdown
NNNNN
hours
CL_CDOWN
Read Only
Coil Cleaning Maint.Done
NO/YES
CL_MAINT
Read Write
Coil Cleaning Maint.Date
00/00/00 00:00
COIL_PM0
Read Only
Coil Cleaning Maint.Date
00/00/00 00:00
COIL_PM1
Read Only
Coil Cleaning Maint.Date
00/00/00 00:00
COIL_PM2
Read Only
Coil Cleaning Maint.Date
00/00/00 00:00
COIL_PM3
Read Only
Coil Cleaning Maint.Date
00/00/00 00:00
COIL_PM4
Read Only
o