23XL PIC II LEADLAG TABLE CONFIGURATION SHEET
DESDRIPTION
RANGE
UNITS
DEFAULT
VALUE
Lead Lag Control
LEAD/LAG Configuration
DSABLE=0, LEAD=1,
LAG=2, STANDBY=3
0 to 3
0
Load Balance Option
0/1
DSABLE/ENABLE
DSABLE
Common Sensor Option
0/1
DSABLE/ENABLE
DSABLE
LAG Percent Capacity
25 to 75
%
50
LAG Address
1 to 236
92
LAG START Timer
2 to 60
MIN
10
LAG STOP Timer
2 to 60
MIN
10
PRESTART FAULT Timer
2 to 30
MIN
5
STANDBY Chiller Option
0/1
DSABLE/ENABLE
DSABLE
STANDBY Percent Capacity
25 to 75
%
50
STANDBY Address
1 to 236
93