Table 2 — LID Screens (cont)
EXAMPLE 2 — STATUS02 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press STATUS .
3. Scroll down to highlight STATUS02.
4. Press SELECT .
DESCRIPTION
POINT TYPE
UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
INPUT
OUTPUT
Hot Gas Bypass Relay
X
OFF/ON
HGBR
*Chilled Water Pump
X
OFF/ON
CHWP
Chilled Water Flow
X
NO/YES
EVFL
*Condenser Water Pump
X
OFF/ON
CDP
Condenser Water Flow
X
NO/YES
CDFL
Compressor Start Relay
X
OFF/ON
CMPR
Compressor Start Contact
X
OPEN/CLOSED
1CR
AUX
Compressor Run Contact
X
OPEN/CLOSED
RUN
AUX
Starter Fault Contact
X
OPEN/CLOSED
STR
FLT
Pressure Trip Contact
X
OPEN/CLOSED
PRS
TRIP
Single Cycle Dropout
X
NORMAL/ALARM
V1
CYCLE
Oil Pump Relay
X
OFF/ON
OILR
Oil Heater Relay
X
OFF/ON
OILH
Motor Cooling Relay†
X
OFF/ON
MTRC
Auxiliary Oil Pump Relay**
X
OFF/ON
AUXOILR
*Tower Fan Relay
X
OFF/ON
TFR
Compr. Shunt Trip Relay
X
OFF/ON
TRIPR
Alarm Relay
X
NORMAL/ALARM
ALM
Spare Prot Limit Input
X
ALARM/NORMAL
SPR
PL
NOTE: All values are variables available for read operation to a CCN. Descriptions shown with (*) support write operations from the LID only.
†Information is applicable to hermetic machines only.
**Information is applicable to open-drive machines only.
EXAMPLE 3 — STATUS03 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press STATUS .
3. Scroll down to highlight STATUS03.
4. Press SELECT .
DESCRIPTION
RANGE
UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
OPTIONS BOARD 1
*Demand Limit 4-20 mA
4-20
mA
DEM
OPT
*Temp Reset 4-20 mA
4-20
mA
RES
OPT
*Common CHWS Sensor
–40-245 (–40-118)
DEG F (DEG C)
CHWS
*Common CHWR Sensor
–40-245 (–40-118)
DEG F (DEG C)
CHWR
*Remote Reset Sensor
–40-245 (–40-118)
DEG F (DEG C)
R
RESET
*Temp Sensor — Spare 1
–40-245 (–40-118)
DEG F (DEG C)
SPARE1
*Temp Sensor — Spare 2
–40-245 (–40-118)
DEG F (DEG C)
SPARE2
*Temp Sensor — Spare 3
–40-245 (–40-118)
DEG F (DEG C)
SPARE3
OPTIONS BOARD 2
*4-20 mA — Spare 1
4-20
mA
SPARE1
M
*4-20 mA — Spare 2
4-20
mA
SPARE2
M
*Temp Sensor — Spare 4
–40-245 (–40-118)
DEG F (DEG C)
SPARE4
*Temp Sensor — Spare 5
–40-245 (–40-118)
DEG F (DEG C)
SPARE5
*Temp Sensor — Spare 6
–40-245 (–40-118)
DEG F (DEG C)
SPARE6
*Temp Sensor — Spare 7
–40-245 (–40-118)
DEG F (DEG C)
SPARE7
*Temp Sensor — Spare 8
–40-245 (–40-118)
DEG F (DEG C)
SPARE8
*Temp Sensor — Spare 9
–40-245 (–40-118)
DEG F (DEG C)
SPARE9
NOTE: All values shall be variables available for read operation to a CCN network. Descriptions shown with (*) support write operations for BEST
programming language, data-transfer, and overriding.
28
Содержание 17
Страница 13: ...Fig 6 Open Drive 17 Series Lubrication Cycle 13 ...
Страница 15: ...Fig 7 17EX Controls and Sensor Locations 15 ...
Страница 16: ...Fig 7 17EX Controls and Sensor Locations cont 16 ...
Страница 17: ...Fig 7 17EX Controls and Sensor Locations cont 17 ...
Страница 19: ...Fig 8 19EX Controls and Sensor Locations cont 19 ...
Страница 23: ...Fig 16 17 19EX LID Menu Structure 23 ...
Страница 24: ...Fig 17 17 19EX Service Menu Structure 24 ...
Страница 50: ...Fig 28 17 19EX Leak Test Procedures 50 ...