Table 2 — LID Screens
NOTES:
1. Only 12 lines of information appear on the LID screen at any given time. Press
NEXT
or PREVIOUS to highlight a point or to view points
below or above the current screen.
2. The LID may be configured in English or SI units, as required, through the LID configuration screen.
3. Data appearing in the Reference Point Names column is used for CCN operations only.
EXAMPLE 1 — STATUS01 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press STATUS (STATUS01 will be highlighted).
3. Press SELECT .
DESCRIPTION
RANGE
UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
Control Mode
Reset.Off.Local.CCN
MODE
Run Status
Timeout.Recycle.Startup.
STATUS
Ramping.Running.Demand.
Override.Shutdown.Abnormal.
Pumpdown
Occupied ?
No/Yes
OCC
Alarm State
Normal/Alarm
ALM
*Chiller Start/Stop
Stop/Start
CHIL
S
S
Base Demand Limit
40-100
%
DLM
*Active Demand Limit
40-100
%
DEM
LIM
Compressor Motor Load
0-999
%
CA
L
Current
0-999
%
CA
P
Amps
0-9999
AMPS
CA
A
*Target Guide Vane Pos
0-100
%
GV
TRG
Actual Guide Vane Pos
0-100
%
GV
ACT
Water/Brine: Setpoint
10-120 (–12.2-48.9)
DEG F (DEG C)
SP
*
Control Point
10-120 (–12.2-48.9)
DEG F (DEG C)
LCW
STPT
Entering Chilled Water
–40-245 (–40-118)
DEG F (DEG C)
ECW
Leaving Chilled Water
–40-245 (–40-118)
DEG F (DEG C)
LCW
Entering Condenser Water
–40-245 (–40-118)
DEG F (DEG C)
ECDW
Leaving Condenser Water
–40-245 (–40-118)
DEG F (DEG C)
LCDW
Evaporator Refrig Temp
–40-245 (–40-118)
DEG F (DEG C)
ERT
Evaporator Pressure
–6.7-420 (–46-2896)
PSI (kPa)
ERP
Condenser Refrig Temp
–40-245 (–40-118)
DEG F (DEG C)
CRT
Condenser Pressure
–6.7-420 (–46-2896)
PSI (kPa)
CRP
Discharge Temperature
–40-245 (–40-118)
DEG F (DEG C)
CMPD
Bearing Temperature
–40-245 (–40-118)
DEG F (DEG C)
MTRB
Motor Winding Temp†
–40-245 (–40-118)
DEG F (DEG C)
MTRW
Motor Winding Hi
Temp Cutout**
Normal/Alarm
MTRW
Oil Sump Temperature
–40-245 (–40-118)
DEG F (DEG C)
OILT
Oil Pressure Transducer†
–6.7-420 (–46-2896)
PSI (kPa)
OILP
Oil Pressure††
–6.7-420 (–46-2896)
PSID (kPad)
OILPD
Line Voltage:
Percent
0-999
%
V
P
Actual
0-9999
VOLTS
V
A
*Remote Contacts Input
Off/On
REMCON
Total Compressor Starts
0-65535
c
starts
Starts in 12 Hours
0-8
STARTS
Compressor Ontime
0-500000.0
HOURS
c
hrs
*Service Ontime
0-32767
HOURS
S
HRS
*Compressor Motor kW
0-9999
kW
CKW
NOTE: All values are variables available for read operation to a CCN. Descriptions shown with (*) support write operations for BEST programming
language, data-transfer, and overriding.
†Information is applicable to hermetic machines only.
**Information is applicable to open-drive machines only.
††Oil pressure is read directly from a differential pressure module on 17EX machines.
27
Содержание 17
Страница 13: ...Fig 6 Open Drive 17 Series Lubrication Cycle 13 ...
Страница 15: ...Fig 7 17EX Controls and Sensor Locations 15 ...
Страница 16: ...Fig 7 17EX Controls and Sensor Locations cont 16 ...
Страница 17: ...Fig 7 17EX Controls and Sensor Locations cont 17 ...
Страница 19: ...Fig 8 19EX Controls and Sensor Locations cont 19 ...
Страница 23: ...Fig 16 17 19EX LID Menu Structure 23 ...
Страница 24: ...Fig 17 17 19EX Service Menu Structure 24 ...
Страница 50: ...Fig 28 17 19EX Leak Test Procedures 50 ...