
Demand
Limit
Control
Option
(Requires
Optional 8-Input Module) —
The demand limit may
be externally controlled with a 4 to 20 mA signal from an
energy management system (EMS). The option is set up on
the Config table. When enabled, the control is set for 100%
demand with 4 mA and an operator configured minimum de-
mand set point at 20 mA.
The Demand Reset input from an energy management sys-
tem is hardwired into the number one, 8-input module. The
signal may be internally powered by the module or exter-
nally powered. If the signal is externally powered, the signal
is wired to terminals J1-1(+) and J1-2(–). If the signal is in-
ternally powered, the signal is wired to terminals J1-3(+) and
J1-2(–). When enabled, the control is set for 100% demand
with 4 mA and an operator configured minimum demand set
point at 20 mA.
Surge Prevention Algorithm —
This is an operator
configurable feature which can determine if lift conditions
are too high for the compressor and then take corrective ac-
tion. Lift is defined as the difference between the pressure at
the impeller eye and the impeller discharge. The maximum
lift that a particular impeller wheel can perform varies with
the gas flow across the impeller, and the size of the wheel.
The algorithm first determines if corrective action is nec-
essary. This is done by checking 2 sets of operator config-
ured data points, which are the MINIMUM and the MAXI-
MUM Load Points, (T1/P1;T2/P2). These points have default
settings as defined on the Service1 table, or on Table 4. These
settings and the algorithm function are graphically dis-
played in Fig. 21 and 22. The 2 sets of load points on this
graph (default settings are shown) describe a line which the
algorithm uses to determine the maximum lift of the com-
pressor. Whenever the actual differential pressure between
the cooler and condenser, and the temperature difference be-
tween the entering and leaving chilled water are above the
line on the graph (as defined by the MINIMUM and MAXI-
MUM Load Points) the algorithm will go into a corrective
action mode. If the actual values are below the line, the al-
gorithm takes no action. Modification of the default set points
of the MINIMUM and MAXIMUM load points is described
in the Input Service configurations section on page 55.
Corrective action can be taken by making one of 2 choices.
If a hot gas bypass line is present, and the hot gas is con-
figured on the Service1 table, then the hot gas bypass valve
can be energized. If a hot gas bypass if not present, then the
action taken is to hold the guide vanes. See Table 4, Capac-
ity Overrides. Both of these corrective actions will reduce
the lift experienced by the compressor and help to prevent a
surge condition. Surge is a condition when the lift becomes
so high that the gas flow across the impeller reverses. This
condition can eventually cause machine damage. The surge
prevention algorithm is intended to notify the operator that
machine operating conditions are marginal, and to take ac-
tion, such as lowering entering condenser water tempera-
ture, to help prevent machine damage.
Surge Protection —
Surging of the compressor can be
determined by the PIC through operator configured settings.
Surge will cause amperage fluctuations of the compressor
motor. The PIC monitors these amperage swings, and if the
swing is greater than the configurable setting in one second,
then one surge count has occurred. The SURGE DELTA PER-
CENT AMPS setting is displayed and configured on the Serv-
ice1 screen. It has a default setting of 25% amps, SURGE
PROTECTION COUNTS can be monitored on the Maint03
table.
A surge protection shutdown of the machine will occur
whenever the surge protection counter reaches 12 counts within
an operator specified time, known as the SURGE TIME
PERIOD. The SURGE TIME PERIOD is displayed and
configured on the Service1 screen. It has a default of
2 minutes.
Lead/Lag Control —
Lead/lag is a control system pro-
cess that automatically starts and stops a lag or second chiller
in a 2-chiller water system. Refer to Fig. 16 and 17 for menu,
table, and screen selection information. On machines that
have PSIO software with Lead/Lag capability, it is possible
to utilize the PIC controls to perform the lead/lag function
on 2 machines. A third machine can be added to the lead/lag
system as a standby chiller to start up in case the lead or lag
chiller in the system has shut down during an alarm condi-
tion and additional cooling is required.
LEGEND
D
P = (Condenser psi) − (Cooler psi)
D
T = (ECW) − (LCW)
ECW
— Entering Chilled Water
HGBP — Hot Gas Bypass
LCW
— Leaving Chilled Water
Fig. 21 — 17/19EX Hot Gas Bypass/Surge
Prevention (English)
LEGEND
D
P = (Condenser kPa) − (Cooler kPa)
D
T = (ECW) − (LCW)
ECW
— Entering Chilled Water
HGBP — Hot Gas Bypass
LCW
— Leaving Chilled Water
Fig. 22 — 17/19EX Hot Gas Bypass/Surge
Prevention (SI)
40
1197
→
Содержание 17
Страница 13: ...Fig 6 Open Drive 17 Series Lubrication Cycle 13 ...
Страница 15: ...Fig 7 17EX Controls and Sensor Locations 15 ...
Страница 16: ...Fig 7 17EX Controls and Sensor Locations cont 16 ...
Страница 17: ...Fig 7 17EX Controls and Sensor Locations cont 17 ...
Страница 19: ...Fig 8 19EX Controls and Sensor Locations cont 19 ...
Страница 23: ...Fig 16 17 19EX LID Menu Structure 23 ...
Страница 24: ...Fig 17 17 19EX Service Menu Structure 24 ...
Страница 50: ...Fig 28 17 19EX Leak Test Procedures 50 ...