3-32
T-294-01
Table 3-10. DataCORDER Pre-Trip Data
Test
No.
TITLE
DATA
NOTE
“Auto” or “Auto1” menu includes the following: P, P1, P2, P3, P4, P5, P6 and rSLts. “Auto2’ (Optional)
menu includes the following: P, P1, P2, P3, P4, P5, P6,P7, P8, P9, P10 and rSLts. (Refer to section 3.2.1.)
1-0
Heater On
Pass/Fail/Skip Result, Change in current for Phase A, B and C
1-1
Heater Off
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
2-0
Condenser Fan On
Pass/Fail/Skip Result, Water pressure switch (WPS) -- Open/Closed,
Change in currents for Phase A, B and C
2-1
Condenser Fan Off
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
3-0
Low Speed Evaporator Fan
On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
3-1
Low Speed Evaporator Fan
On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
4-0
High Speed Evaporator Fan
On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
4-1
High Speed Evaporator Fan
On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
5-0
Supply/Return Probe Test
Pass/Fail/Skip Result, STS, RTS, SRS and RRS
5-1
Secondary Supply Probe Test Pass/Fail/Skip Result
5-2
Secondary Return Probe Test
Pass/Fail/Skip Result
6-0
Compressor On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
6-1
Not Applicable
This test is not in use starting with model number 69NT40-511-200
and UP.
6-2
Suction Modulation Valve
Open and Closed
Pass/Fail/Skip Result, Is current or pressure limit in effect? (Y,N)?
6-4
Not Applicable
This test is not in use starting with model number 69NT40-511-200
and UP.
6-5
Not Applicable
This test is not in use starting with model number 69NT40-511-200
and UP.
7-0
High Pressure Switch Closed
Pass/Fail/Skip Result, AMBS, DPT or CPT (if equipped)
Input values that component opens?
7-1
High Pressure Switch Open
Pass/Fail/Skip Result, STS, DPT or CPT (if equipped)
Input values that component closes?
8-0
Perishable Heat
Pass/Fail/Skip Result, STS, time it takes to heat to 16
_
C (60
_
F)?
8-1
Perishable Pull Down
Pass/Fail/Skip Result, STS, time it takes to pull down to 0
_
C (32
_
F)?
8-2
Perishable Maintain
Pass/Fail/Skip Result, Averaged DataCORDER supply temperature
(SRS) over last recording interval.
9-0
Defrost Test
Pass/Fail/Skip Result, DTS temperature at end of test, line voltage,
line frequency, time in defrost.
10-0
Frozen Mode Set-up
Pass/Fail/Skip Result, STS, time unit is in heat.
10-1
Frozen Mode Pull Down
Pass/Fail/Skip Result, STS, time to pull down unit to --17.8 (0
_
F).
10-2
Frozen Mode Maintain
Pass/Fail/Skip Result, Averaged DataCORDER return temperature
(RRS) over last recording interval.