G SERIES USER MANUAL
5.0 INSTALLATION OF OPTIONAL ACCESSORIES
5.11 MS Sedco Passive Detector Installation
Several MS Sedco sensors such as SmartWalk™ TX-S, SmartWalk™ XP-S or TC26-B can be connected to G
Series systems to operate the system automatically.
Refer to Carmanah Passive Detection Install and Configuration Guide for more detailed information.
For solar G Series systems, a “-S” model SmartWalk™ sensor must be used. SmartWalk™ “-S”
sensor models consume less operating power and are required for sustainable solar system
performance. AC-powered G Series systems can use either the standard or “-S” models.
Ensure Fail Safe switch #4 on the SmartWalk™ is set to the OFF position. This conserves
power by only energizing its internal relay when a pedestrian is detected.
Pushbuttons can be used in conjunction with MS Sedco sensors by wiring the pushbutton in
parallel to the INPT+ and INPT− EMS terminals.
Fail Safe Off wiring (Solar or AC G Series):
SmartWalk™
Terminal (Fail Safe
Off, SW #4 off)
Wire
Color
G Series EMS
Input/Output
Terminal
Function
Pin 1
Red
DC+
DC+ power from G Series EMS to SmartWalk™
Pin 2
Black
DC−
DC− (ground)
from G Series EMS to SmartWalk™
Pin 6
Orange
INPT+
Relay Normally Open signal from SmartWalk™ to EMS
Pin 5
Green
INPT−
Relay Common signal from SmartWalk™ to EMS
For more information on installation or configuration, refer to the MS Sedco manual or contact MS Sedco.