background image

 

 

 

 

 

  

 

 

 

 

 

 

 

 

 

 

        17 

V1.0 | NRG EtherCAT User Manual | © 2022 | CARLO GAVAZZI LTD. 

    

 

EN

 

 

5.

 

Communication 

5.1

 

Process data (PDO) 

 

Process data is the transmission of real time data between an EtherCAT slave and an EtherCAT controller. In the NRG 

system,  process  data is exchanged between the EtherCAT  Controller and the RG..N solid state relays. The data 

includes parameters and diagnostics measured by each NRG solid state relay as well as the control level from the 

PLC to control each solid state relay. Values are stored in a big endian format. 

 

TxPDO - Input Process Data 

 

Data 

Data type 

Status  

uint16 

Alarm  

uint16 

Voltage RMS Reading 

uint16 

Hold Current Reading 

uint16 

Current RMS Reading 

uint16 

Real Power Reading 

uint16 

 

The current measurements (Current RMS & Hold Current) is returned as scaled integers. Therefore, a current value of 

16.81A will be received as 1681. The PLC program has to convert the numbers into floating point values. For further 

information regarding the scaling of each measurement, refer to the Measurements section in this User Manual. 

 

 

The bits in the Alarms and Status WORDs represent alarms and status flags present on the respective solid state relay.  

 

Name 

Description 

Alarms 

Bit 0 – Mains loss alarm Flag 

Bit 1 – Load loss/SSR open circuit alarm Flag 

Bit 2 – RG..N short circuit alarm Flag 

Bit 3 – Voltage out of range alarm Flag 

Bit 4 – Current out of range alarm Flag 

Bit 5 – Frequency out of range alarm Flag 

Bit 6 – Over-temperature pre warning alarm Flag 

Bit 7 – Temperature out of range alarm Flag 

Bit 8 – Load deviation alarm Flag 

Bit 9 – Soft start current limit reached Flag  

Bit 10 – Voltage compensation not possible Flag 

Bits 11:15 - Not used. 

(shall be 0)

 

 

Status  

Bit 0 – Device reset Flag 

Bit 1 – Autoconfiguration Flag (for internal use) 

Bit 2 – Internal Error Alarm Flag 

Bit 3 – Communication Error Flag 

Bits 4:7 – Not used 

Bit 8: Alarm Status Flag 

Bit 9: TEACH busy Flag 

Bit 10: TEACH successful Flag 

Bit 11: Ramping Flag 

Bit 12: Voltage Compensation Active Flag 

Bits 13:15 - Not used. 

(shall be 0)

 

 

Note

: ‘Ref’ terminal connection is required for Voltage, Apparent Power and Real Power readings. Otherwise, the 

readings of these parameters will be 0.  

 

RxPDO – Output Process Data 

 

 

Data

 

Data type 

Control level (0 -100%)

 

uint8 

 

 

 

 

In case of 

ON/OFF

 control mode, a control level 

< 100%

 shall indicate SSR output 

OFF

 and a control level of 

100%

 shall 

indicate SSR output 

ON

 

 

For the 

Power control

 firing modes (Burst, Distributed full cycle, Advanced full cycle and Phase Angle) the 

% control 

value

 shall be translate to 

% power

 of the SSR output. Refer to Section 6.2 for more information on Switching Modes. 

 

 

 

Содержание NRG EtherCAT

Страница 1: ...NRG EtherCAT User Manual Operating instructions Manuale d istruzioni Betriebsanleitung Manuel d instructions Manual de instrucciones Brugervejledning...

Страница 2: ...ounding 10 4 EtherCAT Configuration 11 4 1 Installing the ESI file in TwinCAT 11 4 2 Integrating the NRG in TwinCAT 11 4 3 Configuration of the NRG bus chain in TwinCAT 13 4 4 Start up Parameters 14 5...

Страница 3: ...equipment Nor can Carlo Gavazzi assume liability for recommendations that appear or are implied in the following description The information in this document is not considered binding on any product w...

Страница 4: ...e related national legislation please note that WEEE cannot be disposed of as municipal waste and such waste must be collected and disposed of separately the public or private waste collection systems...

Страница 5: ...more solid state relays are needed in a system multiple BUS chains can be utilised Each BUS chain connects to another BUS chain in a line topology via the NRG controllers of the respective BUS chains...

Страница 6: ...ation on the functions of each variant refer to Section 6 Through the internal BUS the main controller can read measurement parameters and diagnostics information related to the RG N and its load The...

Страница 7: ...the main controller via the 2xRJ45 shielded communication ports The connection between the NRG controller and the solid state relays is through the internal bus cables Each RG N is equipped with 2x mi...

Страница 8: ...ny network topology If more than 32 solid state relays are required in an application multiple bus chains can be utilised These can be configured in a line or star topology as deemed fit for the appli...

Страница 9: ...tions can be looped from one RG CM N to another since all the loads have the same return path Figure 5 Loads connected between phases Reference connection Ref should always follow the return path of t...

Страница 10: ...on on the bus In case of an RG N replacement or any changes to the NRG bus chain the RG Ns have to be re addressed Follow the procedure below Figure 8 to re address the RG Ns on the NRG bus chain manu...

Страница 11: ...il must be conductive and grounded Shielded Cat 5e cables fitted with an outer metallic shell should be used The shell should be connected to the wire screen of the cable Figure 9 Metal din clip on NR...

Страница 12: ...file from https gavazziautomation com images PIM OTHERSTUFF ESI ESI_NRGC ECAT zip and relocate it in the TwinCAT default directory C TwinCAT 3 1 Config Io EtherCAT 4 2 Integrating the NRG in TwinCAT L...

Страница 13: ...LO GAVAZZI LTD V1 0 NRG EtherCAT User Manual 2022 CARLO GAVAZZI LTD EN Find the NRGC ECAT in the EtherCAT device list under Carlo Gavazzi Ltd NRG Controller with EtherCAT Figure 13 Find the NRGC ECAT...

Страница 14: ...maximum of 32 RG N solid state relays can be connected to 1 NRGC ECAT In the Slots tab populate the modules depending on which variant of the RG N solid state relays will be installed in the relevant...

Страница 15: ...meters can be assigned or re assigned via a service data object Check Communications section for further information If start up parameters are left blank the values saved internally in the RG Ns will...

Страница 16: ...mit are mutually exclusive 0 255 0 25 5s Default 0s OFF time to soft start only for RGx1P N 0x2xx2 02 Set the non firing time before soft start is reactivated 0 soft start with occur on power up only...

Страница 17: ...voltage used to compensate for deviations in voltage when Voltage Compensation is activated 0 Voltage compensation is disabled 42 600 V reference voltage for voltage compensation 0 42 600V Default 0...

Страница 18: ...t 0 Mains loss alarm Flag Bit 1 Load loss SSR open circuit alarm Flag Bit 2 RG N short circuit alarm Flag Bit 3 Voltage out of range alarm Flag Bit 4 Current out of range alarm Flag Bit 5 Frequency ou...

Страница 19: ...ble error Flag Bits 12 15 Not used shall be 0 0xF100 0xF100 xx xx RG N position on bus chain in hex Device Status 1 byte Bit 0 Substitute submodule Module type does not match installed RG N variant co...

Страница 20: ...eps of 0 01 therefore a value of 1745 17 45A Check Measurements section for more information 0 RG N model dependent UCL value Default RG N model dependent Under current limit UCL 0x2xx1 05 0 RG N mode...

Страница 21: ...6 Set the firing mode that the RG N shall use at the output 0 External only for RGx1A N 1 ON OFF 2 Burst 3 Advanced full cycle 4 Distributed full cycle 5 Phase Angle only for RGx1P N RGx1A N default O...

Страница 22: ...eading 0 default SSR ON time read only 0x2xx6 03 Holds the accumulated time in hours that the output of the RG N was switched ON 0 default Control level feedback only for RGx1P N read only 0x2xx7 01 H...

Страница 23: ...tput OFF and a control level of 100 indicates SSR output ON The advantages of this mode are It is effectively a direct replacement of the A1 A2 i e for existing systems the control algorithm within th...

Страница 24: ...ing mode 33 control level Output with Distributed firing mode 50 control level Output with Distributed firing mode 66 control level The advantage of Distributed over Burst is the reduction in thermal...

Страница 25: ...d heater applications AFC has the disadvantage of worse harmonics emissions than Burst and also slightly worse than Distributed Phase Angle Firing mode The Phase angle switching mode is available only...

Страница 26: ...e mode The soft start will apply the power smoothly to the load over a time period of maximum 25 5s This is settable via the communication system Soft start ramping time setting Soft start with curren...

Страница 27: ...ue of 50 means 0 5A and a value of 1747 means 17 47A If a fault occurs in the system such that it is not possible to measure the current this value is 0 This reading is updated every half cycle but is...

Страница 28: ...m the initial value at power up the running hours during this power up The reading is updated in steps of 1hour hence a value of 1034 would mean 1034h that the output was ON during its lifetime In the...

Страница 29: ...lickering Invalid configuration General Configuration error Possible reason State change commanded by master is impossible due to register or object settings Double Flash Application watchdog timeout...

Страница 30: ...rror Description This alarm is issued if the NRG controller detects that the BUS between the NRG controller and the RG Ns is not correctly terminated This can be due to An internal fault in the NRG co...

Страница 31: ...Iref registers will be updated by measuring the present current and voltage over a period of time The TEACH command is refuted in case of alarms present on the system If the TEACH is unsuccessful the...

Страница 32: ...sued if this condition is present for 10 seconds Though indicated as an alarm condition this alarm has no effect on the function on the RG N and it is up to the user to decide what to do when this ala...

Страница 33: ...ceived by the RG N and or replies will not be correctly received by the NRGC and or main controller Diagnose Confirm presence of 24V supply voltage on the NRG Controller US terminals Otherwise replace...

Страница 34: ...k it is important to turn it off by pressing again the blue button 2 5 secs otherwise PLC cannot communicate with the NRG bus chain 8 2 Replacing an RG N When an RG N has to be replaced 1 Connect the...

Страница 35: ...REF terminal however this will constitute some limitations as listed below 1 The following readings are not available RMS Voltage Real Power and Apparent Power 2 The TEACH operation cannot be executed...

Отзывы: