20
NRG User Manual | © 2020 | CARLO GAVAZZI LTD.
V1.0 | NRG EtherCAT User Manual | © 2022 | CARLO GAVAZZI LTD.
EN
Soft start current
limit
(only for
RGx1P..N)
0x2
xx
2:03
Set the current limit to be utilised with Soft start with
current limit mode
0 -> soft start with current limit is disabled
0.1 – RG..N model dependent -> soft start with current
limit is enabled with the set current limit.
(Recommended 1.2 – 1.5 times the nominal current)
This parameter is in steps of 0.01, therefore a value of
6600 = 66A
Note
: soft start with time and soft start with current limit
are mutually exclusive
0 – RG..N model
dependent
Default (0)
Output
substitute mode
0x2
xx
2:04
Set the output mode to be used in case of a
communication timeout
0
Clear Output
1
Hold Output
(default)
2
Set Value
Output
substitute value
0x2
xx
2:05
Set the % control level to be used in case of a
communication timeout. (Only applicable for ‘Set
Value option’ for Output substitute mode)
0 (default) – 100%
Switching mode 0x2
xx
2:06
Set the firing mode that the RG..N shall use at the
output
0
External (only for
RGx1A..N)
1
ON/OFF
2
Burst
3
Advanced full
cycle
4
Distributed full
cycle
5
Phase Angle (only
for RGx1P..N)
RGx1A..N default
(ON/OFF)
RGx1P..N default
(Phase Angle)
Time base
0x2
xx
2:07
Set the desired time base. (Only applicable for burst
firing mode)
This parameter is in steps of 0.1, therefore a value of 11
= 1.1s
0.1 (default) - 10s
Voltage
compensation
(only for
RGx1P..N)
0x2
xx
2:08
Set the reference voltage used to compensate for
deviations in voltage when Voltage Compensation is
activated
0 -> Voltage compensation is disabled
42 – 600 V – reference voltage for voltage
compensation
0, 42 – 600V
Default (0)
RG..N
commands
0x2
xx
3:01
Insert value to indicate the command that shall be
executed by the RG..N
1 -> start a TEACH
operation
4 -> store parameters
permanently in RG..N
8 -> clear Latched
Alarms in case
latching of alarms is
activated
99 -> factory reset of
RG..N
TEACH voltage
reference
0x2
xx
4:01
Holds the reference voltage to be used for the load
deviation alarm. Value is updated automatically with a
TEACH command or manually.
If TEACH is not successful value will reset to 0
0 (default) – 660VAC