4.4
Start-up Parameters
The start-up parameters are directly assigned to the respective slots (RG..Ns) and are set during device configuration.
They are transferred automatically on start-up and during re-parameterization. The service data objects with a write
access in the object dictionary can be used during the start-up sequence. This is done by adding the required objects
as start-up parameters in the “Startup” tab of the device in TwinCAT, note that start-up parameters are not added
automatically. The value of the start-up parameters should be written in a little-endian format, i.e. if for example a
value of 660 decimal (02 94 hex) is required to be written, the value written should be 94 02.
Figure 15 Click new to add parameters (and their values) to the start-up sequence
The initialisation time of the NRGC-ECAT (from Pre-OP to OP) increases with the number of objects added to the start-
up sequence. Alternatively, all parameters can be assigned or re-assigned via a service data object. Check
‘Communications’ section for further information. If start-up parameters are left blank, the values saved internally in
the RG..Ns will be loaded.
The below parameters are available for all RG..Ns on the bus chain. The
xx
in the index represents the position (in hex)
of the solid state relay (RG..N) on the bus chain:
e.g
0x2
01
1 -
1
st
RG..N on the bus chain
0x2
02
1 -
2
nd
RG..N on the bus chain
0x2
0A
1 -
10
th
RG..N on the bus chain
0x2
20
1 -
32
nd
RG..N on the bus chain
0x2
xx
1 -
xx RG..N on the bus chain
Note: ‘
TEACH Parameters’
and ‘
Load Running Hours reset’
should
not
be included as part of start-up sequence.
Index
Description
Values
Alarm recovery
mode
0x2
xx
1:01
Set the alarm recovery mode
0
Automatic (default)
1
Manual
Over voltage
limit (OVL)
0x2
xx
1:02
Set the over and under voltage limit if desired
which will trigger an alarm if the voltage reading is
beyond the range
0 – 660V & > UVL value
Default (660V)
Under voltage
limit (UVL)
0x2
xx
1:03
0 – 660V & < OVL value
Default (0V)
Over current limit
(OCL)
0x2
xx
1:04
Set the over and under current limit if desired
which will trigger an alarm if the current reading is
beyond the range
0 –RG..N model
dependent &
> UCL value
Default (RG..N model
dependent)