Carlin G3B Скачать руководство пользователя страница 5

Model G3B Gas burner — Instruction manual

MNG3B Gas 041015

 

5

1.  Prepare Site • Prepare Burner • Mount Burner 

(continued)

Inspect installation site

Combustion/ventilation air openings

  Installing the burner/appliance in a space that does not provide 

enough air for combustion and ventilation can result in severe 
personal injury, death or substantial property damage. Follow 
all applicable codes and guidelines below to ensure space has 
sufficient air openings.

Large spaces

For appliances located in basements, ventilated crawl spaces or other large 
areas, no additional air openings should be necessary.

Exception

: If the building construction is unusually tight (see National Fuel 

Gas Code or CSA B149.1 or .2 for definition), you will need to provide air 
openings into the building if appliance air comes from inside. Provide one 
opening  within 12 inches  of  the  ceiling, and  one  opening  within 12 
inches of the floor.  Size  each  opening  to provide free area (after deduction 
for louvers)  of  1  square  inch  per  1,000  Btuh  input  of  all  fuel-burning 
appliances in the building. 

Confined spaces — air from inside building

If air openings connect to areas inside the building, provide two openings, 
one within 12 inches of the ceiling, the other within 12 inches of the floor. 
Each opening must have a free area (after deduction for louvers) of 1 square 
inch per 1,000 Btuh of all appliances in the space. If the building construc-
tion is unusually tight (see National Fuel Gas Code or CSA B149.1 or .2 for 
definition), you will need to provide air openings into the building. Provide 
two openings sized and located as for the openings into the boiler space.

Confined spaces — air from outside

If  air openings connect directly to outside, provide two openings, one within 
12 inches of the ceiling, the other within 12 inches of the floor. Each opening 
must have a free area (after louver deduction) of:
•  If directly through side wall: 1 square inch for each 4,000 Btuh of all 

appliances in the space.

•  If  through vertical ducts:   1 square inch  for  each  4,000  Btuh  of all 

appliances in the space.

•  If through horizontal ducts:  1 square inch for each 2,000 Btuh of all 

appliances in the space.

Verify openings

  When sizing air openings for combustion and ventilation, include 

air required for exhaust fans and other appliances, such as 
clothes driers, that require air for operation.

Check  appliance  manual  and  applicable  codes  for  required  sizing  of 
combustion and ventilation air openings.
•  Verify that openings are unobstructed.
•  Verify that appliance space and air source spaces are free of:

–  gasoline or other flammable liquids or vapors.
–  combustible materials.
–  air contaminants, such as laundry products, paint, thinner, varnish, etc.

•  Confirm with user that the area will be kept free of these materials at 

all times.

Figure 2

  Locating & sizing air openings

Содержание G3B

Страница 1: ...servicer Except where specifi cally stated otherwise this manual must be used only by a qualified service technician In the state of MA this product must be installed by a licensed plumber or gas fit...

Страница 2: ...l property damage Before leaving the site after startup or service review the User s information manual with the user Make the user aware of all potential hazards and perform the training outlined bel...

Страница 3: ...ith integral gas pressure regulation set for 3 w c outlet pressure 10 Control panel 11 Terminal strip 12 Primary control Honeywell Model S89C primary control for use with flame rectification 13 Contro...

Страница 4: ...less steel liner to vent the flue products A defective vent system could result in severe personal injury death or substantial property damage Vent chimney sizing Follow all local codes when sizing th...

Страница 5: ...ion for louvers of 1 square inch per 1 000 Btuh of all appliances in the space If the building construc tion is unusually tight see National Fuel Gas Code or CSA B149 1 or 2 for definition you will ne...

Страница 6: ...around the burner air tube is more than wrap the burner air tube with minimum 2300 F rated ceramic fiber blanket to seal off the gap Notice that the flameholder may extend slightly into chamber as sho...

Страница 7: ...ng these items Avoid breathing dust and avoid contact with skin or eyes Wear long sleeved loose fitting clothing gloves and eye protection Use a NIOSH N95 certified respirator This respirator meets re...

Страница 8: ...eding Failure to do so could result in severe personal injury death or substantial property damage 3 Loosen Allen screws securing gas line to burner gas connection 4 Remove combination gas valve item...

Страница 9: ...connection as shown in Figure 5 4 If the burner is installed inside the appliance jacket install the main manual gas valve and sediment trap external to the jacket 5 Size piping or verify size usingT...

Страница 10: ...ersonal injuiry death or substantial property damage Figure 6 Ladder wiring diagram Electrically ground burner The burner must be grounded in accordance with local codes or in the absence of local cod...

Страница 11: ...tion of the burner controls Br brown Gr green Bk black Blue blue Or orange Pur purple Gray gray Wire color coding 120 factory wiring VAC 24 factory wiring VAC 120 field wiring VAC 24 field wiring VAC...

Страница 12: ...e plate clockwise to the closed position 3 Check the air throttle indicator The 0 position of the indicator should be even with the end of the air inlet tube If not bend the arm slightly until the ind...

Страница 13: ...n Gas valve on light remains on during normal running indicating gas valve is energized Shutdown When the call for heat ends the primary control immediately deactivates the gas valve and blower The bu...

Страница 14: ...for combination gas valve outlet pressure Adjust valve regulator if necessary so the reading is 3 5 inches w c for either natural gas or propane gas Inspect flame Look at flame through appliance obser...

Страница 15: ...from the combustion chamber If CO2 is noticeably lower overfire than in the vent the appliance has leaks that must be repaired 5 Perform Checkout Procedures Fill Out Certificate continued Check flame...

Страница 16: ...of barometric damper and spill switch If the building contains any exhaust fans or conditions that could affect vent performance check burner appliance vent operation with exhaust fans or other condit...

Страница 17: ...ur 8 32 screws securing the air tube back plate 6 Maintenance and Service Procedures 7 Swing the hold on bracket away and carefully pull out the ignition tube assembly As the white ceramic is exposed...

Страница 18: ...housing cover 6 Maintenance and Service Procedures continued Replacing blower motor or wheel Follow this procedure to replace motor or wheel 1 Remove the four 8 32 screws in the motor mounting plate...

Страница 19: ...nnect the motor leads and power the motor directly with 120 V to check motor operation Bad primary control If all above tests prove negative replace control Burner pre purges for 34 seconds but does n...

Страница 20: ...hrottle according to desired input Wrong orifice size Check orifice drill size Manifold pressure Adjust regulator to 3 5 W C for natural gas or propane Inadequate gas supply Line pressure requirements...

Страница 21: ...ative overfire pressure The G3B burner must not be installed on a product that operates with a pressurized combustion chamber Failure to comply could result in severe personal injury death or substant...

Страница 22: ...in 54858 13 Insulator Tube 2 required 74617 14 Hot Surface Ignitor NORTON 120 volt 5 3 8 OAL 87197S 15 Gasket ignitor assembly 40360 16 Rear Ignitor Assembly 6 overall length 7 1 2 9 overall length 10...

Страница 23: ...Model G3B Gas burner Instruction manual MNG3B Gas 041015 23 9 Replacement parts continued...

Страница 24: ...Model G3B Gas burner Instruction manual MNG3B Gas 041015 24...

Отзывы: