POSITIONING OF THE THERMO FIREPLACE INSIDE THE ROOM
It is absolutely necessary to do the displacement and unpacking of the Thermo Fireplace with adequate tools and to
verify the compatibility of the internal room where you require to install.
2.1 DISPLACEMENT OF THE THERMO FIREPLACE
When moving and unpacking the Thermo Fireplace you must absolutely:
a) Keep it upright at all times;
b) Never turn it in a horizontal position;
c) If necessary, move it with an inclination towards the rear or side view up to a maximum of 45° in order to avoid that
the chain (positioned inside the door) detaches from the pinion on which rotates, causing the block of the door itself.
d) Do not ever tilt it on the front to avoid breakage of the glass.
2.2 CHECKING THE BEARING PLATE
a) Inspect the capacity of the floor;
b) In the case of the floor not being suitable to support the weight of the thermo fireplace, it is possible to install steel
plates or a concrete base in order to distribute the weight. (see figure)
Note: for the plates and the concrete base size, make sure to consult a qualified technician.
c) It is recommended to install the thermo fireplace from floor to fire level of about 40/50 cm height to simplify the
use.
d) Form a straight line surface by using the appropriate adjustment screws under the feet of the thermo fireplace.
2.3 INSPECTION OF THE WALLS ADJACENT TO THE
FIREPLACE
a) It is advisable to never install the thermo fireplace along
the walls, leave at least 2 cm space;
b) Never install the thermo fireplace against flammable walls;
c) In case of unavoidable installation near flammable walls, it
is absolutely necessary to insulate the walls using insulat-
ing plates made of Calcium Silicate “PROMASIL 1000” of 40
mm thickness.
d) While installing the covering, it is recommended to leave
a small space of about 0.5 cm for any possible thermal ex-
pansion.
e) Minimum distance from the front of the thermo fireplace
to flammable materials. (see figure)
Distance from flammable materials
C
A
B
R
E
D
Straight-line distance from flammable side door
A
100 mm
Straight-line distance from flammable read door
B
100 mm
Insulating material thickness for the side/rear door
C
80 mm
Straight-line distance from flammable floor
D
150 mm
Insulating material thickness for the floor
E
80 mm
Straight-line minimum distance from
flammable material
R
200 cm