6.8 Condensate in duct
1.
Verify humidifi er capacity versus air volume.
2.
See section 6.1 in trouble-shooting section of this manual.
3.
Verify that hi-limit controller is working. Correct if necessary.
4.
Verify evaporation distance to obstructions or elbows. Correct if
necessary.
5.
Verify steam valve is not leaking. Correct if necessary.
6.
Uninsulated duct may be running through an area where ambient
temperature is below internal duct dew point. Insulate duct
externally.
6.9 Steam leaks from P-traps.
1.
Check that height of trap exceeds the static pressure of the duct/
AHU, especially if under negative pressure. Correct if necessary.
2.
Check valve sizing to maximum distributor capacity. Resize valve
within distributor capacity.
3.
Check that inlet steam pressure does not exceed the limits of the
valve.
7. MAINTENANCE
8. SPARE
PARTS
The ultimateSAM distributor itself requires no regular maintenance since
its design has no moving parts. It is recommended that the external
surfaces of the distributor should be inspected once a year. If there is
evidence of a steam leak at one of the static seals, contact CAREL.
For optional equipment, such as valves, actuators, traps, and strainers,
follow the maintenance instructions in the user manuals that are provided
with each of these devices. These accessories should be inspected at
least once a year. For systems in which the inlet pressure to the control
valve is greater than 0.7 bar (10 psig), more frequent inspections of the
valve may be required. In addition, steam hoses should be inspected
yearly for evidence of cracking or hardening.
8.1 Adjustable feet Kit for SAB* / SAT*
Feet kit to increase the distance between the base of the ultimateSam
and the duct. Fig. 8.a shows the pedestal SAKS010000 in two diff erent
positions.
a
236.6 mm
(9.31 in)
386.5 mm
(15.22 in)
Optional pedestal
in minimized position
Optional pedestal
in standard position
Fig. 8.a
kIT CODE
Description
Duct height
mm ( in)
Weight
kg (lbs)
SAKS010000
High adjustable feet kit
386.5 mm (15.2in)
0.9 (2.0 lbs)
SAKS020000
Standard adjustable feet kit 236.6 mm (9.3in)
1 (2.0 lbs)
SAKS030000
Short adjustable feet kit
(version without frame)
37.5mm (1.48in)
0.8 (1.8 lbs)
Tab. 8.a
Each kit contains 2 adjustable feet and 16 screws
8.2 Horizontal manifold Kit (steam feed –
condensate drain) for SAB* / SAT*
5
6
7
8
9
1
0
F
a
mi
l
y
p
r
e
fix
SAKM
x x x x 0 0
Pos. Meaning
Option
Description
Type
S
S = Steam feed (100x100 mm)
D
D = Condensate drain (70x70 mm)
Unit width mm
(in)
A
A = 447 (18)
B
B = 599 (23.75)
C
C = 751 (29.75)
D
D = 903 (35.75)
E
E = 1055 (41.75)
F
F = 1207 (47.75)
G
G = 1359 (53.75)
H
H = 1511 (59.50)
I
I = 1663 (65.50)
J
J = 1815 (71.50)
K
K = 1967 (77.50)
L
L = 2119 (83.50)
M
M = 2271 (89.50)
N
N = 2423 (95.50)
O
O = 2575 (101.50)
P
P = 2727 (107.50)
Q
Q = 2879 (113.50)
R
R = 3031 (119.50)
Upright Size &
Center distance
mm (in)
S
S = 35 (1.50) - OD; 152 (6.00)
L
L = 45 (1.75) - OD; 152 (6.00)
H
H = 35 (1.50) - OD; 76 (3.00)
Insulation
I
I = insulated
N
N = uninsulated no insert
Tab. 8.b