50
EN
“UEX-PLUS” +030220621 - rel. 1.4 - 04.08.2009
installer
user
ser
vice
“D”
read (R)/
write (W)
digital variables (Modbus®: COILS)
CAREL - Modbus®
1
R/W
system timer – hour: 1 = variable i24 (hour) can be modifi ed; 0 = i24 cannot be modifi ed
2
R/W
system timer – minute: 1 = variable i25 (minute) can be modifi ed; 0 = i25 cannot be modifi ed
3
R/W
system timer – day: 1 = variable i26 (day) can be modifi ed; 0 = i26 cannot be modifi ed
4
R/W
system timer – month: 1 = variable i27 (month) can be modifi ed; 0 = i27 cannot be modifi ed
5
R/W
system timer - year: 1 = variable i28 (year) can be modifi ed; 0 = i28 cannot be modifi ed
6
R/W
system timer - weekday: 1 = variable i29 (weekday) can be modifi ed; 0 = i29 cannot be modifi ed
7
R/W
measure system:
0 = international system
1 = british system
8
R/W
remote on/off from network: 0 = ue disabled, 1 = ue enabled
9
R
at least 1 alarm is active
10
R
humidistat status: 0 = open, 1 = closed
11
R
remote on/off status:
0 = open = ue disabled
1 = closed = ue enabled
12
R
high conductivity alarm
13
R
high conductivity warning
14
R
cylinder 1: high current alarm
15
R
cylinder 1: low current alarm
16
R
cylinder 1: lack of water alarm
17
R
cylinder 1: low production alarm
18
R
cylinder 1: drain alarm
19
R
cylinder 1: full without demand alarm
20
R
cylinder 1: maintenance-due alarm (timed)
21
R
cylinder 1: pre-exhaustion warning
22
R
cylinder 1: foam warning
23
R
cylinder 1: totally exhausted warning
24
R
cylinder 1: maintenance-due warning (timed)
25
R
cylinder 2: high current alarm
26
R
cylinder 2: low current alarm
27
R
cylinder 2: lack of water alarm
28
R
cylinder 2: low production alarm
29
R
cylinder 2: drain alarm
30
R
cylinder 2: full without demand alarm
31
R
cylinder 2: maintenance-due alarm
32
R
cylinder 2: pre-exhaustion warning
33
R
cylinder 2: foam warning
34
R
cylinder 2: totally exhausted warning
35
R
cylinder 2: maintenance-due warning
36
R
warning: room probe/external regulator not properly connected (only when their signal is 2-10 v or 4-20 ma)
37
R
warning: limit probe not properly connected (only when their signal is 2-10 v or 4-20 ma)
38
R
room high humidity warning
39
R
room low humidity warning
40
R
limit probe high humidity warning
41
R
hour counter alarm
42
R/W
drain for strong demand reduction:
1 = enabled, 0 = disabled
43
R/W
long-inactivity drain: 1 = enabled, 0 = disabled
44
R/W
total periodical fl ush: 1 = enabled, 0 = disabled
45
R/W
dehumidifi cation: 1 = enabled, 0 = disabled
46
R/W
dilution drain with contactor opened: 1 = enabled, 0 = disabled
Содержание humiSteam x-plus