51
EN
“UEX-PLUS” +030220621 - rel. 1.4 - 04.08.2009
installer
user
ser
vice
47
R/W
warnings for pre-exhaustion and complete exhaustion: 1 = enabled, 0 = disabled
48
R/W
cylinders in parallel or series: 0 = parallel, 1 = series
49
R/W
cylinder 1: reset of the hour counter
50
R/W
cylinder 2: reset of the hour counter
51
R/W
alarms reset
52
R/W
cylinder 1: manual drain: 1 = on, 0 = off
53
R/W
cylinder 2: manual drain: 1 = on, 0 = off
54
R/W
cylinder 1: cleaning cycle: 1 = on, 0 = off
55
R/W
cylinder 2: cleaning cycle: 1 = on, 0 = off
“I”
read (R)/
write (W)
integer variables (Modbus®: REGISTERS)
CAREL
Modbus®
1
129
R
high part sw version
2
130
R
low part sw version
3
131
R
day sw version
4
132
R
month sw version
5
133
R
year sw version
6
134
R
sw release type
7
135
R
sw release number
8
136
R
humidifi er status
0 = on duty; 1 = alarm(s) present; 2 = disabled via network; 3 = disabled by timer; 4 = disabled by remote on/off ; 5
= disabled by keyboard; 6 = manual control; 7 = no demand
9
137
R
conductivity reading
10
138
R/W
manual force conductivity value
11
139
R
cylinder 1: working phase
0 = not active; 1 = softstart; 2 = start; 3 = production at steady state; 4 = reduced production
5 = production delayed stop; 6 = full fl ush
12
140
R
cylinder 1: status
0 = no production; 1 = start of evaporation cycle; 2 = water fi ll; 3 = steam production in progress;
4 = water drain (decision to open the contactor; drain pump still stopped); 5 = water drain (drain pump running); 6 =
water drain (drain pump stopped; contactor closing, if open); 7 = humidifi er blocked
8 = long-term-inactivity full drain; 9 = fl ushing of the hydraulic circuit; 10 = full drain by manual or network request;
11 = automatic management of lack of supply water; 12 = total periodic drain
13
141
R
cylinder 2: working phase
0 = not active; 1 = softstart; 2 = start; 3 = production at steady state; 4 = reduced production; 5 = production delayed
stop; 6 = full fl ush
14
142
R
cilindro 2: status
0 = no production; 1 = start of evaporation cycle; 2 = water fi ll; 3 = steam production in progress;
4 = water drain (decision to open the contactor; drain pump still stopped); 5 = water drain (drain pump running); 6 =
water drain (drain pump stopped; contactor closing, if open); 7 = humidifi er blocked
8 = long-term-inactivity full drain; 9 = fl ushing of the hydraulic circuit; 10 = full drain by manual or network request;
11 = automatic management of lack of supply water; 12 = total periodic drain
15
143
R/W
regulation type:
0 = on/off ; 1 = slave 0-100%; 2 = slave 0-100% + limit probe; 3 = %rh control with external probe without limit probe
4 = %rh control with external probe + limit probe; 5 = temperature control
16
144
R/W
room probe/ext. regulator: type of signal
0 = 0-1 v; 1 = 0-10 v; 2 = 2-10 v; 3 = 0-20 ma; 4 = 4-20 ma; 5 = ntc carel standard
17
145
R/W
limit probe: type of signal
0 = 0-1 V; 1 = 0-10 V: 2 = 2-10 V; 3 = 0-20 mA; 4 = 4-20 mA; 5 = NTC CAREL standard
18
146
R/W
maintenance time-out
19
147
R/W
periodical fl ush: period
20
148
R/W
inactivity drain: time-out
21
149
R/W
conductivity warning: threshold
22
150
R/W
conductivity alarm: threshold
23
151
R/W
tuning of dilution frequency: parameter b8
24
152
R/W
tuning of dilution duration: parameter b9
25
153
R
system timer: hour
26
154
R
system timer: minute
Содержание humiSteam x-plus
Страница 1: ...humiSteam x plus User manual humidifiers ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 56: ...Note ...
Страница 57: ...Note ...
Страница 58: ...Note ...
Страница 59: ......