90
ENG
“heaterSteam” +0300087EN - rel. 1.4 - 22.01.2021
16.6 Linear nozzle models and typical installations
humidifi er model: UR002 UR004 UR006 UR010 UR013 UR020 UR027 UR040
UR053
UR060
UR080
ø of steam outlet mm (in):
30 (1.2”)
40 (1.6”)
2x40 (1.6”)
maximum capacity kg/h (lb/h):
2 (4.4)
4 (8.8) 6 (13.2) 10 (22) 13(28.6) 20 (44) 27(59.5) 40 (88) 53(116.8)
60(132.2)
80(176.36)
nozzle steam
inlet ø mm (in)
max. nozzle capac-
ity kg/h (lb/h)
length of nozzle
mm (in)
code
30 (1.2”)
5 (11)
350 (13.7)
DP035D30R0
1
1
30 (1.2”)
8 (17.6)
450 (17.7)
DP045D30R0
1
1
1
30 (1.2”)
12 (26.4)
600 (23.6)
DP060D30R0
1
1
1
(2)*
30 (1.2”)
18 (39.6)
850 (33.5)
DP085D30R0
1
1
1
1
(2)*
(2)*
30 (1.2”)
18 (39.6)
1050 (41.3)
DP105D30R0
1
1
1
1
(2)*
(2)*
30 (1.2”)
18 (39.6)
1250 (49.2)
DP125D30R0
1
1
1
1
(2)*
(2)*
30 (1.2”)
18 (39.6)
1650 (65)
DP165D30R0
1
1
(2)*
(2)*
30 (1.2”)
15 (33)
300 (11.8)
DP030D30RU
1
1
1
1
1
30 (1.2”)
15 (33)
450 (17.7)
DP045D30RU
1
1
1
1
1
(2)*
(2)*
30 (1.2”)
15 (33)
600 (23.6)
DP060D30RU
1
1
1
1
(2)*
(2)*
40 (1.6”)
25 (55)
850 (33.5)
DP085D40R0
1
1
(2)**
(4)**
(4)**
(4)**
40 (1.6”)
35 (77)
1050 (41.3)
DP105D40R0
1
1
(2)**
2
2
(4)**
40 (1.6”)
45 (99)
1250 (49.2)
DP125D40R0
1
1
1
2
2
2
40 (1.6”)
45 (99)
1650 (65)
DP165D40R0
1
1
2
2
2
40 (1.6”)
45 (99)
2050 (80.7)
DP205D40R0
1
2
2
2
40 (1.6”)
45 (99)
600 (23.6)
DP060D40RU
1
1
1
2
2
2
30 (1.2”)
5 (11)
350 (13.7”)
DP035D30RH
1
1
30 (1.2”)
8 (17.6)
450 (17.7”)
DP045D30RH
1
1
1
30 (1.2”)
12 (26.4)
600 (23.6”)
DP060D30RH
1
1
1
(2)*
30 (1.2”)
18 (39.6)
850 (33.5”)
DP085D30RH
1
1
1
1
(2)*
(2)*
30 (1.2”)
18 (39.6)
1050 (41.3”)
DP105D30RH
1
1
1
1
(2)*
(2)*
30 (1.2”)
18 (39.6)
1250 (49.2”)
DP125D30RH
1
1
1
1
(2)*
(2)*
30 (1.2”)
18 (39.6)
1650 (65”)
DP165D30RH
1
1
(2)*
(2)*
40 (1.6”)
25 (55)
850 (33.5”)
DP085D40RH
1
1
(2)**
(4)**
(4)**
(4)**
40 (1.6”)
35 (77)
1050 (41.3”)
DP105D40RH
1
1
(2)**
2
2
(4)**
40 (1.6”)
45 (99)
1250 (49.2”)
DP125D40RH
1
1
1
2
2
2
40 (1.6”)
45 (99)
1650 (65”)
DP165D40RH
1
1
2
2
2
40 (1.6”)
45 (99)
2050 (80.7”)
DP205D40RH
1
2
2
2
Tab. 16.e
(*) use CAREL “Y” kit P/N UEKY000000, 40 mm (1.6”) inlet and 2 x 30 mm (1.2”) outlets
(**) use CAREL “Y” kit P/N UEKY40X400, 40 mm (1.6”) inlet and 2 x 40 mm (1.6”) outlets
For typical installations of linear distibutors see Fig. 8.a.
≥ 70 mm
min. 200 mm
1
(8”)
(2.7”)
1/3 H
H > 250 mm
2
(9.8”)
1/3 H
≥ 200 mm
H > 250 mm
3
(9.8”)
(8”)
1/5 H
2/5 H
≥ 200 mm
H > 350 mm
4
(8”)
(13.7”)
1/5 H
2/5 H
H > 400 mm
5
(15.7”)
1/7 H
2/7 H
2/7 H
H > 500 mm
6
(19.7”)
1/7 H
2/7 H
2/7 H
H > 600 mm
7
(23.6”)
min 200 mm
=
=
8
(8”)
H > 200 mm
=
=
1/2 H
9
(8”)
H > 300 mm
=
=
=
=
10
(11.8”)
H > 500 mm
=
1/3 H
1/3 H
=
11
(19.7”)
Fig. 16.x