Address
Variable name
Occup.
Description
Default
Min
Max
UoM Access
70
Alrm_HiBoilerTemp.Active
1
Alarm ALC05: High boiler temperature (>110°)
Read
72
Warn_AutotestCancel.Active
1
Warning ALW07: Autotest cancelled, saved and displayed
Read
73
Warn_NoDrainYet.Active
1
Warning ALW08: No drain to dilute (if micro-fi lling active)
Read
78
DisableVarUnitPause
1
Disable paused by monitoring service
(0: not disabled 1: disabled)
Read
Tab. 11.f
COIL STATUS
Address
Variable name
Occup. Description
Default
Min
Max UoM Access
1
OnBySV
1
On/off control from supervisor (SV)
ReadWrite
6
WHardnessTyp
1
Set water hardness management mode (0 = AUTO; 1 = MANUAL)
ReadWrite
7
SchedDayCfg[0].EnTB
1
Scheduler: Enable time band 1
ReadWrite
8
SchedDayCfg[1].EnTB
1
Scheduler: Enable time band 2
ReadWrite
9
SchedDayCfg[2].EnTB
1
Scheduler: Enable time band 3
ReadWrite
10
SchedDayCfg[3].EnTB
1
Scheduler: Enable time band 4
ReadWrite
11
SchedDayCfg[4].EnTB
1
Scheduler: Enable time band 5
ReadWrite
12
SchedDayCfg[5].EnTB
1
Scheduler: Enable time band 6
ReadWrite
13
ManExtFan
1
Blower command in manual mode
ReadWrite
17
EnSched
1
Enable scheduler
FALSE
ReadWrite
18
EnHiConductAlrm
1
Enable high conductivity alarm
TRUE
ReadWrite
19
ManDrain
1
Manual total drain command (value changes from 1 to 0 when drain is
complete)
ReadWrite
20
EnPreheatOff
1
Enable preheating function
FALSE
ReadWrite
21
EnPartFills
1
Enable micro-fi lling function to restore water level
ReadWrite
22
DilDrainCfg.DailySched[1].Enable
1
Drain to dilute - Daily scheduler (Monday) - enable
TRUE
ReadWrite
23
DilDrainCfg.DailySched[2].Enable
1
Drain to dilute - Daily scheduler (Tuesday) - enable
TRUE
ReadWrite
24
DilDrainCfg.DailySched[3].Enable
1
Drain to dilute - Daily scheduler (Wednesday) - enable
TRUE
ReadWrite
25
DilDrainCfg.DailySched[4].Enable
1
Drain to dilute - Daily scheduler (Thursday) - enable
TRUE
ReadWrite
26
DilDrainCfg.DailySched[5].Enable
1
Drain to dilute - Daily scheduler (Friday) - enable
TRUE
ReadWrite
27
DilDrainCfg.DailySched[6].Enable
1
Drain to dilute - Daily scheduler (Saturday) - enable
FALSE
ReadWrite
28
DilDrainCfg.DailySched[7].Enable
1
Drain to dilute - Daily scheduler (Sunday) - enable
FALSE
ReadWrite
29
EnPeriodicDrain
1
Enable periodic total drain
FALSE
ReadWrite
30
UnitPause
1
Set unit paused (0: not paused 1: paused)
ReadWrite
71
Alrm_SVOffl
ine.Active
1
Alarm ALA07: Supervisor offl
ine
Read
Tab. 11.g
Содержание HeaterSteam 4 UR002
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 91: ...91 ENG heaterSteam 0300087EN rel rel 1 4 22 01 2021...