Carel HeaterSteam 4 UR002 Скачать руководство пользователя страница 3

3

ENG

“heaterSteam” +0300087EN - rel. rel. 1.4 - 22.01.2021

IMP

O

RTA

N

T WAR

N

I

NGS

:

This product is compliant with the European directives and other standards 
specifi ed on the EC declaration of conformity. The customer is responsible 
for suitably verifying any use of the product that implies application of 
standards relating to any special environments and/or processes (e.g. 
heavy industry, medical environments, maritime environments, railway 
environments, etc.) other than those specifi ed by Carel.

The humidifi ers manufactured by CAREL are advanced products, whose 
operation is specifi ed in the technical documentation supplied with the product 
that can be downloaded, even prior to purchase, from the website www.carel.
com. Every product made by CAREL Industried, in relation to its advanced level of 
technology, requires a qualifi cation/ confi guration / setup phse in order to best 
fulfi l your specifi c application. The lack of such phase of study, as indicated in the 
manual, can cause the fi nal product to malfunction, of which CAREL cannot be 
held responsible. The client (builder, developer or installer of the fi nal equipment) 
assumes all responsibility and risk relating to the confi guration of the product in 
order to achieve the expected results in relation to the specifi c fi nal installation 
and/or equipping. In this case, subject to specifi c agreements, CAREL acts as a 
consultant for the success of the installation / start-up / use of the machine, but 
in no case does it accept liability for proper operation of the humidifi er and of 
the fi nal plant, should  the warnings and recommendations in this manual or in 
any other technical documentation of the product not be followed. In particular, 
in addition to the obligation to observe the above mentioned warnings and 
recommendations for proper use of the product, we recommend paying 
attention to the following warnings: 

DA

NG

ER ELE

C

TRI

C

 

S

H

OC

K: 

The humidifi er includes live electrical parts. 

Disconnect the power supply before accessing internal parts, in case of 
maintenance and during installation.

DA

NG

ER WATER LEAK

S

:

 The humidifi er automatically and constantly sucks 

in/drains quantities of water. Malfunctions in the connections or humidifi er 
may cause leaks.

DA

NG

ER 

O

B

UR

NS

:

 The humidifi er contains hot parts and delivers steam 

at 100 °C / 212 °F.

• 

The product is designed exclusively to humidify rooms either directly or 
through distribution systems (ducts). 

• 

Installation, operation and maintenance must be performed by qualifi ed 
personnel, aware of the necessary precautions and able to perform the 
required operations correctly. 

• 

All operations on the product must be carried out according to the 
instructions given in this manual and on the labels applied to the 
product. Any uses or modifi cations unauthorized by the manufacturer are 
considered improper. CAREL denies all responsibility for such unauthorized 
uses. 

• 

Do not attempt to open the humidifi er in any way other than the ones 
described in the manual.

• 

Follow the regulations in force in the place where the humidifi er is installed.  

• 

Keep the humidifi er out of the reach of children and pets. 

• 

Do not install and use the product near objects that can be damaged by 
contact with water (or condensate). CAREL denies all responsibility for direct 
or indirect damage as a result of loss of water from the humidifi er. 

• 

Do not use corrosive chemicals, aggressive solvents or detergents to clean 
the internal or external parts of the humidifi er, unless specifi cally indicated 
in the user’s manual.

CAREL adopts a continuous development policy. Therefore, CAREL reserves the 
right to carry out modifi cations and improvements to any product described 
in this document without prior notice. The technical data in the manual 
can undergo modifi cations without forewarning. The liability of CAREL in 
relation to its own product is governed by CAREL general contract conditions 
published on the website www.carel.com and/or by specifi c agreements with 
clients; in particular, within the limits set by the applicable law, in no way will 
CAREL, its employees or its branch offi

  ces/affi

  liates be responsible for any lack 

of earnings or sales, loss of data and information, cost of replacement goods 
or services, damage to objects or persons, work interruptions, or any direct, 
indirect, accidental, patrimonial, coverage, punitive, special or consequential 
damage in any way caused, be they contractual, out-of-contract, or due to 
negligence or other responsibility originating from the installation, use or 
inability of use of the product, even if CAREL or its branch offi

  ces/affi

  liates 

have been warned of the possible damage.

ATTENTION

NO POWER 

& SIGNAL 

CABLES 

TOGETHER

READ CAREFULLY IN THE TEXT!

Separate the probe cables and the digital input cables as much as possible 
from the inductive load and power cables to prevent possible electro-
magnetic interference. 
Never introduce power cables and signal cables (including those of electric 
control board) into the same cable troughs.

The installation of the product must absolutely include the grounding 
connection, using the special yellow-green terminal on the terminal block.  
Do not use the neutral as grounding connection.

DI

S

P

OS

AL

Fig. 1        Fig.2

Please read and keep.

With reference to European Union directive 2012/19/EU issued on 4 July 2012 
and related national legislation, please note that:

1. 

Waste Electrical and Electronic Equipment (WEEE) cannot be disposed 
of as municipal waste but must be collected separately so as to allow 
subsequent recycling, treatment or disposal, as required by law;

2. 

users are required to take Electrical and Electronic Equipment (EEE) at end-
of-life, complete with all essential components, to the WEEE collection 
centres identifi ed by local authorities. The directive also provides for the 
possibility to return the equipment to the distributor or retailer at end-of-
life if purchasing equivalent new equipment, on a one-to-one basis, or 
one-to-zero for equipment less than 25 cm on their longest side;

3. 

this equipment may contain hazardous substances: improper use or 
incorrect disposal of such may have negative eff ects on human health 
and on the environment;

4. 

the symbol (crossed-out wheeled bin – Fig.1) even if, shown on the 
product or on the packaging, indicates that the equipment must be 
disposed of separately at end-of-life;

5. 

if at end-of-life the EEE contains a battery (Fig. 2), this must be removed 
following the instructions provided in the user manual before disposing 
of the equipment. Used batteries must be taken to appropriate waste 
collection centres as required by local regulations;

6. 

in the event of illegal disposal of electrical and electronic waste, the 
penalties are specifi ed by local waste disposal legislation.

Warranty for materials: 

2 years (from the manufacture date, excluding 

consumables).

Certifi cation: 

the quality and safety of CAREL products are guaranteed by 

CAREL’s ISO 9001 certifi ed design and production system, as well as 

and 

.marking.

Содержание HeaterSteam 4 UR002

Страница 1: ...H i g h E f f i c i e n c y S o l u t i o n s heaterSteam 4 UR NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT Electric resistance humidifier User manual...

Страница 2: ......

Страница 3: ...detergents to clean the internal or external parts of the humidi er unless speci cally indicated in the user s manual CARELadoptsacontinuousdevelopmentpolicy Therefore CARELreservesthe right to carry...

Страница 4: ......

Страница 5: ...connection 44 8 3 Type of Master Slave system installation 44 8 4 Master Slave system con guration 45 9 WEB SERVER 47 9 1 Integrated web server 47 9 2 Connecting to the integrated web server 47 9 3 De...

Страница 6: ......

Страница 7: ...ng conditions see par Wall mounting The models UR020 UR080 can be oor installed to ensure proper distribution of steam place the humidi er next to the steam distribution point position the humidi er v...

Страница 8: ...y pulling it forward 4 remove the protective lm on all external surfaces of the humidi er 1 7 Mounting the front panel Models UR002 UR013 2 1 3 4 Fig 1 g 1 turn the red oval plate with the CAREL logo...

Страница 9: ...ote tampering removal lack of the identi cation plate or other does not allow the safe identi cation of the product and will make any installation or maintenance operation to be performed di cult 1 10...

Страница 10: ...nic controller 21 Fastening strap 7 Power cable terminal block 22 Heater 8 Pump fuse F3 23 Drain pump 9 RF interference suppressor where envisaged 24 Fill valve 10 Power cable gland 25 Drain tempering...

Страница 11: ...23 Boiler 5 Heater fuses where envisaged 24 Drain pipe 6 Contactor 25 Heater 7 Motor protector THP 26 Boiler thermal protector Klixon 8 NTC probe socket 27 Foam detection sensor 9 Transformer 28 Wate...

Страница 12: ...4 connect a section of pipe for draining resistant to temperatures of 100 C 212 F and with a minimum internal diameter of 40 mm 1 6 in for models UR002 UR013 and 50 mm 2 in for models UR020 UR080 for...

Страница 13: ...ll Water ll Water drain Water drain Steam exhaust and condensate drain Models UR002 UR013 top view A1 A2 A3 Fig 2 f size mm in Models UR002 UR013 F 126 7 5 F 224 8 8 G 137 9 5 4 G 21 7 0 85 A1 Steam o...

Страница 14: ...12 mm 0 5 in model SDPOEM0022 hole diameter 22 mm 0 9 in D drilling jig Note if using steam hoses with an inside diameter of 30 mm 1 2 in remove the 22 mm 0 9 in inlet section from the steam nozzle 3...

Страница 15: ...D40RH A 30 1 2 40 1 6 B 10 0 4 10 0 4 Y 68 2 7 89 3 5 45 1 8 60 2 4 1 60 2 4 80 3 1 X 77 3 0 99 3 9 3 4 CAREL blowers for room installation VSDU0A VRDXL Steam distributors for installation in rooms Th...

Страница 16: ...of the steam transport and condensate drain pipes All the UR models 5 D 200mm 8 5 R 300mm 12 H 2 m 7 8 Fig 3 e Models UR002 UR013 1 condensate drain connection with return to fill tank 20 5 1 D 200mm...

Страница 17: ...if necessary cut the top part of the conical cable gland B and insert the power cable 3 connect the electrical wires to the terminal block reposition the cover and fasten it using the screws To attac...

Страница 18: ...an be delivered 50 mA Protec tion against short circuits G Probe power supply G CAREL 0 10 V M2 4 Digital input for backup rotation function Maximum current output 5 mA Maximum voltage with contact op...

Страница 19: ...al signal Y Pmax Steam_Pr Pmin OFF ON 0 hy 2xhy 100 Y Y 0 1Vdc 0 10Vdc 2 10Vdc 0 20mA 4 20mA Fig 4 k Key Steam_pr Steam production Y External signal P0 Max production hy Activation hysteresis Pm Min p...

Страница 20: ...ulating operation short circuit terminals M2 7 M2 8 jumper to enable production connect terminals M2 1 and M2 2 production request to an external controller to enable control set Screen ind Screen des...

Страница 21: ...ype Select from 0 1V 0 10V 2 10V 0 20mA 4 20mA M2 M9 M8 1 1 2 3 4 5 6 7 8 2 1 2 OUT H T M G Main probe Fig 4 t _________________________________________________________ CONTROL WITH ONE HUMIDITY PROBE...

Страница 22: ...100 C 32 212 F di erential 2 20 C 3 6 36 F Minimum production 0 100 Maximum production 0 100 Ec01 Main probe type Select from 0 1V 0 10V 2 10V 0 20mA 4 20mA M2 M9 M8 1 1 2 3 4 5 6 7 8 2 1 2 OUT H T M...

Страница 23: ...probe to terminals M2 5 M2 6 to enable control set Screen Screen description parameter Ea01 Control type Modulation with two temperature probes Ea02 Control with 2 probes Set the weight of the two pro...

Страница 24: ...ure involves a water ll cycle to above the high level green LED followed by a drain cycle until below the minimum level red LED The procedure then re lls the unit with water in order to restart produc...

Страница 25: ...e probes including the set point or external request signal Fig 6 e Pos Function Pos Function 1 System menu 6 Alarm list 2 home 7 ON OFF 3 Scheduler settings 8 Set point setting 4 System date and time...

Страница 26: ...request graphic area displays the production request and the values read by the probes For each control type there is a speci c display as described below control proportional to an external signal an...

Страница 27: ...ing O from BMS steam production disabled by the supervisor O by time band steam production disabled due to set time band O from Din production of steam stopped due to opening of the remote ON OFF cont...

Страница 28: ...ails need to be entered Use the password 0044 to enter the Maintenance settings Use the password 0077 to enter the Installer settings Settings menu icons Index Icon Menu Menu type Control type A Contr...

Страница 29: ...Set the integral time and neutral zone for PI control limit probe Installer heaterSteam process heaterSteam titanium Ea07 Display cylinder operating hours and set maintenance pre alert threshold Serv...

Страница 30: ...onal or Imperial Select the language when starting Installer heaterSteam process heaterSteam titanium Change password Eg04 Change the password Service Installer Service Installer heaterSteam process h...

Страница 31: ...the special periods B04 Scheduler Set the special days Fig 7 b Fig 7 c Note if control is by external signal the humidi er can only be switched ON or OFF 7 1 3 Alarm thresholds Main menu To check that...

Страница 32: ...0 Possible settings 0 100 Step 1 The weight of each probe should be expressed with a value from 0 to 100 The weighted average is calculated as follows Weighted average S1 p1 S2 p2 p1 p2 where Sx is th...

Страница 33: ...er 1260 hours The humidi er will signal an alarm and STOP the unit for maintenance once the pre set hours have been reached plus an additional 120 hours in the above example 1500 120 1620 hours It mus...

Страница 34: ...vity time is three days 72 hours the cylinder will be automatically emptied when heaterSteam remains on for at least three days without humidi cation request 7 3 4 Periodical drain Installer menu If t...

Страница 35: ...s Save the log of main variables to USB pen drive Export to USB Yes to save the log Fig 7 f 7 3 9 Save alarm log The alarm log can be saved to USB pen drive To export the file plug the USB pen drive i...

Страница 36: ...after the evaporation cycle in this case using the variation in ll time parameter new ll time default ll time variation in ll time 100 Remarks on the duration of the drain to dilute cycle if the drain...

Страница 37: ...Master Slave Initial Master Slave system con guration Press PRG to con gure the Master Slave network Index Description Parameter Ed02 Unit 1 Unit 2 Unit 20 Add unit to the Master Slave system To add...

Страница 38: ...s auto or user de ned 9 9 manual drain to dilute cycle setting Index Description Parameter Eg01 Wizard Start the wizard for initial unit con guration Set whether to display the wizard when next restar...

Страница 39: ...xternal gateway supernode for humidi cation 7 9 2 BMS port settings Installer menu Screen Eh02 is used to set supervisor communication on the BMS port Index Description Parameter Eh02 BMS port supervi...

Страница 40: ...ng service settings Display unit paused by monitoring service status Set unit paused by monitoring service bypass Unit paused bypass automatic reset delay 7 9 8 Restart controller following change in...

Страница 41: ...st In this speci c case the Master will always be the unit with the lowest IP address of those connected to the signal probes If necessary an additional humidi er backup can be installed to cover requ...

Страница 42: ...Ed04 is only shown if rotation is enabled on screen Ed03 Grouped rotation logic the units are activated in series one after the other according to steam request Example M S system comprising two 80 kg...

Страница 43: ...malfunctions Note if a unit goes o ine due to a malfunction or shutdown it will temporarily be excluded from the system and when next restarted it may take 15 seconds or more to automatically come onl...

Страница 44: ...r is not accessible directly on the internet as a rewall guarantees remote access only via a secure connection Carel tERA cloud or encrypted VPN connection 9 3 Description of the web server function T...

Страница 45: ...visor to the Ethernet port 2 set the network parameters DHCP IP address subnet mask gateway DNS on screen Eh04 For other supervisor protocols select the Carel protocol on the BMS serial port and use t...

Страница 46: ...tting for SSR heater power control cycle in manual mode 0 10000 ms ReadWrite 19 RegulationCfg RegTyp Control mode 0 External proportional signal 1 External proportio nal signal limit 2 ON OFF signal 3...

Страница 47: ...ite 102 HiConductWarnHyst High conductivity warning threshold hysteresis setting 25 0 100 ReadWrite 103 FoamLevSetPScale Foam sensor sensitivity 0 200 def 100 100 0 200 ReadWrite 104 PartFillsT Micro...

Страница 48: ...etP_Temp Set temperature value temperature set point 42 0 0 100 0 C F ReadWrite 17 RegulationCfg Hyst Set control hysteresis 2 0 0 5 100 0 ReadWrite 18 RegulationCfg Di Set control di erential 5 0 2 0...

Страница 49: ...ALN7 Network unit 7 alarm Read 50 Alrm_NetUnit_8 Active Alarm ALN8 Network unit 8 alarm Read 51 Alrm_NetUnit_9 Active Alarm ALN9 Network unit 9 alarm Read 52 Alrm_NetUnit_10 Active Alarm ALN10 Networ...

Страница 50: ...y poor 8 14 Poor 15 30 Good 31 100 Excellent Read 29 WirelessPrbVal_4 Hum 1 Wireless probe 4 reading Humidity 0 1 rh Read 31 WirelessPrbVal_4 Temp 1 Wireless probe 4 reading Temperature 0 1 C F Read 3...

Страница 51: ...1 Set main probe type 0 0 1V 1 0 10V 2 2 10V 5 NTC 3 0 20mA 4 4 20mA 1 0 4 ReadWrite 39 MainPrbCfg Mi_Hum 2 Set main probe minimum humidity value 0 0 100 rh ReadWrite 41 MainPrbCfg Ma_Hum 2 Set main...

Страница 52: ...2 Set water preheating temperature 70 0 50 0 80 0 C F ReadWrite 113 PreheatO set_Temp 2 Set temperature di erence with reference to tempera ture set point for activation of preheating preheating o set...

Страница 53: ...HiHum Active 1 Alarm ALH01 High humidity temperature Read 21 Alrm_LoHum Active 1 Alarm ALH02 Low humidity temperature Read 22 Alrm_HiHum_Lim Active 1 Alarm ALH03 High humidity temperature limit probe...

Страница 54: ...command in manual mode ReadWrite 17 EnSched 1 Enable scheduler FALSE ReadWrite 18 EnHiConductAlrm 1 Enable high conductivity alarm TRUE ReadWrite 19 ManDrain 1 Manual total drain command value change...

Страница 55: ...0 s ReadWrite 20 MainPrbCfg UITyp Set main probe type 0 0 1V 1 0 10V 2 2 10V 5 NTC 3 0 20mA 4 4 20mA 1 0 4 ReadWrite 21 LimitPrbCfg UITyp Set limit probe type 0 0 1V 1 0 10V 2 2 10V 3 0 20mA 4 4 20mA...

Страница 56: ...ll function active 0 Disabled 1 Daily scheduler 2 Periodic 0 0 2 ReadWrite 89 DilDrainCfg Perio dicDilDrainThrsh Set number of hours between two periodic drain to dilute cycles if micro lling mode ac...

Страница 57: ...5 GlbSetP_Temp Set temperature value temperature set point 42 0 0 100 0 C F ReadWrite 16 RegulationCfg Hyst Set control hysteresis 2 0 0 5 100 0 ReadWrite 17 RegulationCfg Di Set control di erential 5...

Страница 58: ...m_NetUnit_7 Active Alarm ALN7 Network unit 7 alarm Read 49 Alrm_NetUnit_8 Active Alarm ALN8 Network unit 8 alarm Read 50 Alrm_NetUnit_9 Active Alarm ALN9 Network unit 9 alarm Read 51 Alrm_NetUnit_10 A...

Страница 59: ...DisableVarUnitPause Disable paused by monitoring service 0 not disabled 1 disabled Read Tab 11 j 11 3 heaterSteam tERA service registration The humidi er can be connected to the Carel tERA service Th...

Страница 60: ...probes for measuring temperature and humidity WS01G01M00 or WS01F01M00 Fig 12 b HeaterSteam Access point connection To connect the humidi er to the access point use the Fieldbus connection on termina...

Страница 61: ...hat the supply pipe to the humidi er and the internal tubing are not blocked or choked and that there is enough pressure 0 1 0 8 MPa 1 8 bars Check operation of the ll solenoid valve Check that there...

Страница 62: ...only ALN08 Network alarm on unit 8 Network unit alarm see the speci ed unit for details Carry out the checks based on the alarm displayed on the unit in question Automatic Open Signal only ALN09 Netwo...

Страница 63: ...i c machine code N description no of kit for single UR UR 6 1 UR 6 3 UR 10 3 UR 13 3 UR6 1 UR6 3 UR10 3 UR13 3 URKCR00020 1 power connection protective cover single package 3 URKCOPC02M 16 boiler cove...

Страница 64: ...cover 1 URKFLAN020 11 kit of utilities ange with gasket 1 URKFS00000 3 ani foam sensor kit 1 Tab 14 c where not indicated single package the kits comprise the quantity of parts needed for the speci c...

Страница 65: ...n pipe 7 over ow pipe 8 feed pipe 10 compensation pipes URKTDT002M only for drain temperng URKTDT002M only for drain temperng 12 drain tempering pipe for the models equipped with it Tab 14 e where not...

Страница 66: ...R30000 URKTR00000 6 Transformer heaterSteam process URH00000P4 heaterSteam titanium URH00000T4 7 Electronic controller URKREL2400 8 Pump relay URKFANS000 URKFANL200 9 Fan HCTXRCFP00 HCTXRCR000 10 TOUC...

Страница 67: ...r to the following gures Fig 14 f a loosen the fastening strap and remove the steam pipe 1 b from the boiler cover remove the pressure compensation pipe 2 connected to the level control c loosen the f...

Страница 68: ...tions please refer to the wiring diagrams of the heaters next to the heads Scale collection bag optional only unit 2 13 kg On the inner wall of the boiler is present depending on model a lm made in an...

Страница 69: ...ed not used not used 40 A GG KTK Tab 14 j Fuse Fuse code 40 A GG KTK URKFUSE700 50 A GG KTK URKFUSE800 Heaters To replace the heaters unmount them removing the fastening nut D on the cover in this cas...

Страница 70: ...ay rise excessively until it reaches 65 C Power to the solid state relays is cut o by a special Klixon heat sensor with manual reset see the wiring diagram without signalling the intervention In this...

Страница 71: ...MAIN PROBE G ENG heaterSteam 0300087EN rel rel 1 4 22 01 2021 15 WIRING DIAGRAMS To be carried out by the installer TB Terminal Board THP Motor Protector QC1 Fast coupling K Contactor LLC Level gauge...

Страница 72: ...RED PURPLE C G MAIN PROBE G ENG heaterSteam 0300087EN rel 1 4 22 01 2021 To be carried out by the installer TB Terminal Board THP Motor Protector QC1 Fast coupling K Contactor LLC Level gauge ST Senso...

Страница 73: ...RDA1 KA2 KA1 EVF EVF G MAIN PROBE G ENG heaterSteam 0300087EN rel rel 1 4 22 01 2021 To be carried out by the installer TB Terminal Board THP Motor Protector QC1 Fast coupling K Contactor LLC Level ga...

Страница 74: ...DA1 KA2 KA1 EVF EVF RD X3 X4 C G MAIN PROBE G ENG heaterSteam 0300087EN rel 1 4 22 01 2021 To be carried out by the installer TB Terminal Board THP Motor Protector QC1 Fast coupling K Contactor LLC Le...

Страница 75: ...1 X1 CS CS LS LS NTC NTC BLUE YELLOW RED PURPLE G MAIN PROBE G ENG heaterSteam 0300087EN rel rel 1 4 22 01 2021 To be carried out by the installer TB Terminal Board THP Motor Protector QC1 Fast coupli...

Страница 76: ...LS NTC NTC BLUE YELLOW RED PURPLE X3 X4 C SSR1 SSR2 G MAIN PROBE G ENG heaterSteam 0300087EN rel 1 4 22 01 2021 To be carried out by the installer TB Terminal Board THP Motor Protector QC1 Fast coupl...

Страница 77: ...1 3 TR Transformer DP Drain pump LS High level electrodes CS Conductivity meter electrodes MS Manual switch R1 3 Electric heater 1 3 SSR1 3 Solid state relay 1 3 FSB Fan control board FAN Fan RDT Dra...

Страница 78: ...R SUPPLY PE 1 BRIDGING CONNECTION 2 3 C SSR1 SSR2 TO DP G MAIN PROBE G ENG heaterSteam 0300087EN rel 1 4 22 01 2021 To be carried out by the installer THP Motor Protector QC1 Fast coupling K CONTACTOR...

Страница 79: ...3 1 2 2 1 2 1 2 ALARM RELAY C NC NO GO G EXTERNAL SIGNALS BRIDGING CONNECTION G MAIN PROBE G ENG heaterSteam 0300087EN rel rel 1 4 22 01 2021 To be carried out by the installer THP Motor Protector QC1...

Страница 80: ...C NC NO GO G LS R4 R5 R6 R1 R2 R3 PTC1 PTC3 PTC2 PTC4 PTC5 PTC6 G MAIN PROBE G ENG heaterSteam 0300087EN rel 1 4 22 01 2021 To be carried out by the installer THP Motor Protector QC1 Fast coupling K...

Страница 81: ...1 R2 R3 4 5 6 G I M H L N R1 R2 R3 1 2 3 A C E B D F UR053 400 460 690V 3F R1 R2 R3 4 5 6 O Q S P R T G MAIN PROBE G ENG heaterSteam 0300087EN rel rel 1 4 22 01 2021 To be carried out by the installer...

Страница 82: ...FAN NTC NTC BLUE YELLOW RED PURPLE EXTERNAL SIGNALS ALARM RELAY C NC NO GO G POWER SUPPLY G MAIN PROBE G ENG heaterSteam 0300087EN rel 1 4 22 01 2021 To be carried out by the installer QC1 Fast coupl...

Страница 83: ...ED PURPLE CS CS LS LS NTC NTC RS RS K M2 M1 EVF EVF KA1 KA2 RDA1 RDA2 FAN FAN ALARM RELAY C NC NO EXTERNAL SIGNALS G MAIN PROBE G ENG heaterSteam 0300087EN rel rel 1 4 22 01 2021 To be carried out by...

Страница 84: ...M RELAY C NC NO GO G F1 F2 F3 F4 TR L1 L2 L3 PE K MS TO DP N A RD S1 SSR2 SSR3 SSR1 F5 F6 F7 F8 F9 F10 1 BRIDGING CONNECTION 2 3 4 5 6 POWER SUPPLY G MAIN PROBE G ENG heaterSteam 0300087EN rel 1 4 22...

Страница 85: ...4 R5 R6 I M L N G H R7 R8 R9 4 5 6 O Q S P R T R1 R2 R3 1 2 3 A C E B D F R4 R5 R6 I M L N G H O P R Q S T R9 R8 R7 UR60 400 460 690V 3F UR80 690V 3F G MAIN PROBE G ENG heaterSteam 0300087EN rel rel 1...

Страница 86: ...VF EVF KA1 KA2 RDA1 RDA2 FAN FAN NTC NTC BLUE YELLOW RED PURPLE EXTERNAL SIGNALS ALARM RELAY C NC NO GO G F5 F6 F7 F8 F9 F10 F11 F12 F13 1 2 3 4 5 6 7 8 9 G MAIN PROBE G ENG heaterSteam 0300087EN rel...

Страница 87: ...16e Fig 15 g 20 0 44 15 0 P 690 3 x 5000 Y 3 x 12 5 6 16 rapid Fig 16e Fig 15h UR027 27 0 59 5 19 8 K 230 3 x 6612 3 x 49 8 16 60 rapid Fig 16h Fig 16e_1 Fig 15 h Fig 15 i 27 0 59 5 20 0 L 400 3 x 666...

Страница 88: ...6 p Three phase STAR 53 kg h 575 V U Three phase TRIANGLE 20 kg h 208 U 230 V 0 U 27 kg h 208 U 230 V U Three phase STAR 60 kg h 400 460 V U 80 kg h 400 460 V 0 1 2 3 A B C D E F O P Q R S T 1 2 3 A B...

Страница 89: ...ls 0 1 Vdc 0 10 Vdc 2 10 Vdc 50 with signals 0 20 mA 4 20 mA power supply for active probes general features 24 Vdc 24 Vac recti ed Imax 250 mA 12 Vdc 5 Imax 50 mA alarm relay outputs general features...

Страница 90: ...R0 1 1 1 2 2 2 40 1 6 45 99 1650 65 DP165D40R0 1 1 2 2 2 40 1 6 45 99 2050 80 7 DP205D40R0 1 2 2 2 40 1 6 45 99 600 23 6 DP060D40RU 1 1 1 2 2 2 30 1 2 5 11 350 13 7 DP035D30RH 1 1 30 1 2 8 17 6 450 17...

Страница 91: ...91 ENG heaterSteam 0300087EN rel rel 1 4 22 01 2021...

Страница 92: ...CAREL INDUSTRIES HQs Via dell Industria 11 35020 Brugine Padova Italy Tel 39 0499 716611 Fax 39 0499 716600 carel carel com www carel com Agenzia heaterSteam 0300087EN rel 1 4 22 01 2021...

Отзывы: