30
ENG
“heaterSteam” +0300087EN - rel. 1.4 - 22.01.2021
Menu
Screen
Menu description
Menu type Controller type
E. Settings
(password)
c. Confi guration
High conductivity
Ec16
Set conductivity thresholds: warning, alarm and hysteresis
Installer
heaterSteam process
heaterSteam titanium
Remote ON input logic
Ec22
Remote ON/OFF operating logic
Installer
heaterSteam process
heaterSteam titanium
SSR PWM period
Ec23
Duration of SSR modulation period
Installer
heaterSteam process
heaterSteam titanium
Ec25
Set foam level
Installer
heaterSteam process
heaterSteam titanium
d. Master/Slave
Master/Slave
Ed01
Initial Master/Slave system confi guration
Press “PRG” to confi gure the Master/Slave network
Installer
heaterSteam titanium
Unit 1
Unit 2 . . . Unit 20
Ed02
Add unit to the Master/Slave system
Installer
heaterSteam titanium
Maximum production of
Master/Slave system.
Unit rotation.
Ed03
Set maximum production of the Master/Slave system
Set the unit rotation logic
Installer
heaterSteam titanium
Advanced preheating
Rotation time.
Ed04
Enable the advanced preheating function for Master/Slave systems
Set the rotation time between one unit and the next
Installer
heaterSteam titanium
Offl
ine timeout.
Ed05
Set the unit offl
ine time in the Master/Slave system
Installer
heaterSteam titanium
Disconnect unit from
Master/Slave system
Ed06
Disable/disconnect the current unit from the Master/Slave system
Installer
heaterSteam titanium
Master/Slave production
Ed07
Display the request (%) and the production (kg/h / lbs/h) of the
Master/Slave system
Press “PRG” to confi gure the Master/Slave network
Installer
heaterSteam titanium
Display Master/Slave
system
Ed08
Unit status with corresponding % of production
Press “PRG” to confi gure the Master/Slave network
Installer
heaterSteam titanium
Display info on individual
unit. Unit 1 Unit 2 . ..
Unit 20
Ed09
Display unit operating hours, current production and any alarms
To move between the various units use the UP and DOWN arrows
Installer
heaterSteam titanium
Unit switched off for
maintenance.
Ed10
Unit switched off for maintenance
Installer
heaterSteam titanium
e. Backup
Enable backup
Ee01
Enable automatic unit backup in the event of shutdown, using a
second independent unit
Installer
heaterSteam titanium
Priority when starting
Ee02
Defi ne the priority of the units when in backup mode
Installer
heaterSteam titanium
f. Manual mode
Type of manual mode
Ef01
Enable manual mode: Disabled, manual management of outputs
and manual request
Service
Installer
heaterSteam process
heaterSteam titanium
Manual management of
outputs
Ef02
Test the outputs: fi ll valve, drain pump, contactor, SSR status, SSR ON
time, SSR OFF time
Service
Installer
heaterSteam process
heaterSteam titanium
Manual management of
request
Ef03
Manually set the production request
Service
Installer
heaterSteam process
heaterSteam titanium
g. Initialisation
Wizard
Eg01
Start the wizard for initial unit confi guration
Set whether to display the wizard when next restarting
Service
Installer
heaterSteam process
heaterSteam titanium
Language
Eg02
Set the language
Service
Installer
heaterSteam process
heaterSteam titanium
Unit of measure and lan-
guage when starting
Eg03
Set unit of measure (International or Imperial).
Select the language when starting
Installer
heaterSteam process
heaterSteam titanium
Change password
Eg04
Change the password (Service, Installer).
Service
Installer
heaterSteam process
heaterSteam titanium
Inst. default
Eg06
Unit factory reset. Important: resetting the model will cancel all of
the control settings and load the default values
Service
Installer
heaterSteam process
heaterSteam titanium
Software update
Eg07
Update the unit software from USB pen drive
Service
Installer
heaterSteam process
heaterSteam titanium
Export parameters
Eg08
Export the confi guration parameters from the unit to USB pen drive Service
Installer
heaterSteam process
heaterSteam titanium
Import parameters
Eg09
Import the confi guration parameters from USB pen drive to the unit
Delete alarm log
Service
Installer
heaterSteam process
heaterSteam titanium
h. Supervision
Unit supervision address
on BMS port
Eh01
Set the unit address for supervision. Enable the supervisor type and
protocol
Installer
heaterSteam process
heaterSteam titanium
BMS port communication
settings
Eh02
Set the communication parameters for supervision via BMS: Baud
rate, stop bits and parity
Installer
heaterSteam process
heaterSteam titanium
BACnet MS/TP
confi guration
Eh03
Set the address, maximum number of masters and maximum
number of frames
Installer
heaterSteam process
heaterSteam titanium
BACnet address
Eh04
Device instance address
-
-
Ethernet network settings Eh05
Set DHCP, IP address, mask, gateway, DNS for the Ethernet network.
Important: these values must be provided by the local network
administrator
Installer
heaterSteam process
heaterSteam titanium
Supervision settings on
Ethernet port
Eh06
Select the protocol on the Ethernet port: ModBus or BACnet
Installer
heaterSteam process
heaterSteam titanium
Supervision settings
Eh07
Select the type of port for control by supervisor (BMS or Ethernet)
-
-
Eh08
Set supervisor offl
ine alarm enabling and activation delay (for control
by supervisor)
Installer
heaterSteam process
heaterSteam titanium
Eh09
Enable automatic disabling of paused by monitoring service bypass,
display paused by monitoring service status
Installer
heaterSteam process
heaterSteam titanium
i. Logout
Logout
Ei01
Information on the type of login performed. Possibility to logout
Service
Installer
heaterSteam process
heaterSteam titanium
Tab. 6.e
6.9 Alarms
Any active alarms will be shown on the corresponding screen with direct
access from the display.
When an alarm occurs, the corresponding alarm button
starts fl ashing.
In these conditions, pressing the alarm button
once displays the type
of alarm. In the event of potentially dangerous alarms, the humidifi er
automatically stops steam production. For certain alarm events, as well as
the alarm signal, the alarm relay is activated (see Chap. 13 “Alarm table”).
When the cause of the alarm is no longer present:
•
the humidifi er and the alarm relay are reset automatically or manually;
•
the message shown on the display can only be cleared manually (see
Chap. 13 “Alarm table”);
Even if no longer active, the alarm status continues to be indicated until
“clear display” button is pressed.
Alarms that are still active cannot be reset. If there is more than one alarm,
the display shows all the alarms in sequence.
From the alarm screen, the alarm log can be displayed by pressing “Enter”
. For the complete table of alarms, see chapter 13. Alarm table.