Carel EVD evolution Скачать руководство пользователя страница 25

24

ENG

“EVD evolution” +030222041 - rel. 1.0 - 01.06.2008

FUNCTIONS

6. 

Inputs and outputs

6.1 

Analogue inputs

The parameters in question concern the choice of the type of pressure 
sensor  S1  and  S3  and  the  choice  of  the  temperature  sensor  S2  and 
S4,  as  well  as  the  possibility  to  calibrate  the  pressure  and  temperature 
signals. As regards the choice of pressure sensor S1, see the chapter on 
“Commissioning”.

Inputs S2, S4

The options are standard NTC sensors, high temperature NTC, combined 
temperature  and  pressure  sensors  and  0  to  10 Vdc  input.  For  S4  the  0 
to  10  Vdc  input  is  not  available.  When  choosing  the  type  of  sensor, 
the  minimum  and  maximum  alarm  values  are  automatically  set.  See 
the  chapter  on “Alarms”.  The  auxiliary  sensor  S4  is  associated  with  the 
Modulating thermostat function or can be used as a backup sensor for 
the main sensor S2.

Type

CAREL code

Range

CAREL NTC (10KΩ at 25°C)

NTC0**HP00

NTC0**WF00
NTC0**HF00

-50T105°C

CAREL NTC-HT HT (50KΩ at 25°C) NTC0**HT00

0T120°C  
(150 °C per 3000 h)

Combined NTC 

SPKP**T0

-40T120°C

 

Attention:  in  case  of  combined 

NTC  sensor,  select  also  the 

parameter relevant to the corresponding ratiometric pressure sensor.

Parameter/description

Def.

CONFIGURATION
Sensor S2:
CAREL NTC;  CAREL NTC-HT high T;  Combined NTC SPKP**T0;  
0-10 V external signal

CAREL NTC

Sensor S4:
CAREL NTC;  CAREL NTC-HT high T;  Combined NTC SPKP**T0 

CAREL NTC

Tab. 6.a

Input S3

The  auxiliary  sensor  S3  is  associated  with  the  high  condensing 
temperature protection or can be used as a backup sensor for the main 
sensor S1. If the sensor being used is not included in the list, select any 
0 to 5 V ratiometric or electronic 4 to 20 mA sensor and then manually 
modify the minimum and maximum measurement in the manufacturer 
parameters corresponding to the sensors.

 

Important:  

sensors S3 and S4 appear as NOT USED if the “auxiliary 

control” parameter is set as “ disabled”.
If “auxiliary control” has any other setting, the manufacturer setting for the 
sensor used will be shown, which can be selected according to the type.

Auxiliary control

Variable displayed

High condensing temperature protection  

S3

Modulating thermostat

S4

Backup sensors

S3,S4

Tab. 6.b

Parameter/description

Def.

Configuration
Sensor S3:

Ratiom.:  -1 to 
9.3 barg

Ratiometric (OUT=0 to 5 V) Electronic (OUT=4 to 20 mA)
-1 to 4.2 barg
-0.4 to 9.2 barg
-1 to 9.3 barg
0 to 17.3 barg
-0.4 to 34.2 barg
0 to 34.5 barg
0 to 45 barg

-0.5 to 7 barg
0 to 10 barg
0 to 18.2 bar
0 to 25 barg
0 to 30 barg
0 to 44.8 barg
remote, -0.5 to 7 barg
remote, 0 to 10 barg
remote, 0 to 18.2 barg
remote, 0 to 25 barg
remote, 0 to 30 barg
remote, 0 to 44.8 barg

Tab. 6.c

Calibrating pressure sensors S1, S3 and temperature 
sensors S2 and S4 (offset and gain parameters)

In case it is necessary to make a calibration:

of  the  pressure  sensor,  S1  and/or  S3  it  is  possible  to  use  the  offeset 

• 

parameter,  which  represents  a  constant  that  is  added  to  the  signal 
across  the  entire  range  of  measurement,  and  can  be  expressed  in 
barg/psig. If the 4 to 20 mA signal coming from an external controller 
on  input  S1  needs  to  be  calibrated,  both  the  offset  and  the  gain 
parameters can be used, the latter which modifies the gradient of the 
line in the field from 4 to 20 mA.
of the temperature sensor, S2 and/or S4 it is possible to use the offset 

• 

parameter,  which  represents  a  constant  that  is  added  to  the  signal 
across the entire range of measurement, and can be expressed in °C/°F. 
If the 0 to 10 Vdc signal coming from an external controller on input 
S2 needs to be calibrated, both the offset and the gain parameters can 
be used, the latter which modifies the gradient of the line in the field 
from 0 to 10 Vdc.

4

20

A

B

mA

0

10

A

B

Vdc

Fig. 6.a

Key:

 

A= offset, 
B= gain

Parameter/description

Def.

Min.

Max.

UOM

Sonde
S1: calibration offset

0

-60 (-870), 
-60

60 (870), 
60 

barg (psig), 
mA

S1: calibration gain, 4 to 20 mA

1

-20

20

-

S2: calibration offset

0

-20 (-290), 
20

20 (290), 
20

°C (°F), volt

S2: calibration gain, 0 to 10 V

1

-20

20

-

S3: calibration offset

0

-60 (-870)

60 (870) barg (psig)

S4: calibration offset

0

-20 (-36)

20 (36)

°C (°F)

Tab. 6.d

Digital inputs 

Digital input DI1 is used to activate the control:

digital input 1 closed: control activated;

• 

digital input 1 open: driver in standby (see paragraph “Control status”).

• 

As regards digital input 2, if configured, this is used to tell the driver the 
active defrost status:
Defrost active= contact DI2 closed.
When entering Manufacturer programming mode, the start delay after 
defrost can be set (see the following paragraphs).  

Parameter/description

Def.

Min.

Max. UOM

Configuration
Configuration of DI2 
Disabled;  Optimise valve control after 
defrost.

Disabled

-

-

-

Control
Start delay after defrost

10

0

60

min

Tab. 6.e

Содержание EVD evolution

Страница 1: ......

Страница 2: ...I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s EVD evolution User manual electronic expansion valve driver...

Страница 3: ......

Страница 4: ...to open the device in any way other than described in the manual do not drop hit or shake the device as the internal circuits and mechanisms may be irreparably damaged do not use corrosive chemicals s...

Страница 5: ......

Страница 6: ...oning 17 4 4 Other functions 17 5 CONTROL 18 5 1 Main and auxiliary control 18 5 2 Superheat control 18 5 3 Special control 19 5 4 Auxiliary control 22 6 FUNCTIONS 24 6 1 Inputs and outputs 24 6 2 Con...

Страница 7: ......

Страница 8: ...play for EVD evolution English EVDIS00ES0 Display for EVD evolution Spanish EVDIS00FR0 Display for EVD evolution French EVDIS00IT0 Display for EVD evolution Italian EVDIS00PT0 Display for EVD evolutio...

Страница 9: ...e time required to completely close the electronic valve being controlled while during normal operation the battery is recharged The complete module with batteries code EVBAT00300 and the box for batt...

Страница 10: ...seriale di servizio rimuovere il coperchio per potervi accedere Tab 2 a Connection diagram superheat control 2 3 G G0 G G0 VBAT COM1 NO1 1 3 2 4 NET OPEN CLOSE Tx Rx GND DI1 S4 S3 S2 S1 GND DI2 VREF 2...

Страница 11: ...idity greater than the 90 or condensing strong vibrations or knocks exposure to continuous water sprays exposure to aggressive and polluting atmospheres e g sulphur and ammonia fumes saline mist smoke...

Страница 12: ...he 5 operation was successful UPLOAD the display saves all the values of the parameters on the source driver DOWNLOAD the display copies all the values of the parameters to the target driver RESET all...

Страница 13: ...GND DI1 S4 S3 S2 S1 GND DI2 VREF Tx Rx GND DI1 S4 S3 S2 S1 GND DI2 VREF 1 15 3 EVD evolution Fig 2 j Key 1 white A Connection to EVBAT200 300 2 yellow B Connection to electronic pressure sensor SPK 00...

Страница 14: ...status of the driver the activation of the protectors any alarms and the status of the relay output Hjgg hXVaYVb 6eZgijgV kVakdaV DC BDE 6A6GB GZaZ 1 2 3 4 5 6 Fig 3 c Key 1 1st variable displayed 2...

Страница 15: ...ng the Service 10 parameters E6HHLDG9 Fig 3 e Note if no button is pressed after 5 min the display automatically returns to the standard mode Modifying the Manufacturer parameters The Manufacturer lev...

Страница 16: ...on will commence between the two instruments and the driver automatically be enabled for control The main screen will shown on the display which can then be removed and control will be commence when r...

Страница 17: ...sure sensor 0 5 to 7 bars for 3 drivers For the first driver select 0 5 to 7 barg For the second and third driver select remote 0 5 to 7 barg Note the range of measurement by default is always in bar...

Страница 18: ...an be selected transcritical CO2 hot gas bypass etc as well as so called special control functions which do not involve the superheat activating auxiliary controls that use sensors S3 and or S4 and se...

Страница 19: ...superheat temperature in fact corresponds to a situation of probable instability due to the turbulent evaporation process approaching the measurement point of the sensors The expansion valve must the...

Страница 20: ...See the EEV system guide 030220810 for further information on calibrating PID control Note when selecting the type of main control both superheat control and special modes the PID control values sugg...

Страница 21: ...ressure set point 3 20 290 200 2900 barg psig PID proportional gain 15 0 800 PID integration time 150 0 1000 s PID derivative time 5 0 800 s Tab 5 f Hot gas bypass by temperature This control function...

Страница 22: ...le in display mode Control is direct as the pressure increases the valve opens Parameter description Def Min Max UOM SPECIAL Transcritical CO2 coefficient A 3 3 100 800 Transcritical CO2 coefficient B...

Страница 23: ...t S4 to modulate the opening of the electronic valve so as to limit the lowering of the temperature read and consequently reach the control set point This is useful in applications such as the multipl...

Страница 24: ...Backup sensors on S3 S4 In this case pressure sensor S3 and temperature sensor S4 will be used to replace sensors S1 and S2 respectively in the event of faults on one or both so as to guarantee a high...

Страница 25: ...9 3 barg Ratiometric OUT 0 to 5 V Electronic OUT 4 to 20 mA 1 to 4 2 barg 0 4 to 9 2 barg 1 to 9 3 barg 0 to 17 3 barg 0 4 to 34 2 barg 0 to 34 5 barg 0 to 45 barg 0 5 to 7 barg 0 to 10 barg 0 to 18 2...

Страница 26: ...at start evaporator valve capacity ratio 50 0 100 Tab 6 i This parameter should be set based on the ratio between the rated cooling capacity of the evaporator and the valve e g rated evaporator cooli...

Страница 27: ...reaching 0 steps plus a further number of steps so as to guarantee complete closing Following the stop phase the valve returns to standby t t t t OFF ON R OFF ON ST OFF ON S OFF ON A T4 Fig 6 d Key A...

Страница 28: ...s only valid when the driver is performing superheat control Unblock valve is an automatic safety procedure that attempts to unblock a valve that is supposedly blocked based on the control variables s...

Страница 29: ...tection threshold 5 40 72 set point superheat K R LowSH protection integration time 15 0 800 s ALARM CONFIGURATION Low superheat alarm delay LowSH 0 alarm disabled 300 0 18000 s Tab 7 b When the super...

Страница 30: ...ure alarm delay MOP 0 alarm disabled 600 0 18000 s Tab 7 d The integration time is set automatically based on the type of main control When the evaporation temperature rises above the MOP threshold th...

Страница 31: ...will not resume based on the activation of the protector but rather on the reduction in the outside temperature The system will therefore remain in the best operating conditions a little below the thr...

Страница 32: ...emote 0 to 10 barg remote 0 to 18 2 barg remote 0 to 25 barg remote 0 to 30 barg remote 0 to 44 8 barg External signal 4 to 20 mA Ratiometric 1 to 9 3 barg I 16 143 A Main control Multiplexed cabinet...

Страница 33: ...n Current cooling capacity Control set point Superheat Suction temperature Evaporation temperature Evaporation pressure Condensing temperature Condensing pressure Modulating thermostat temperature EPR...

Страница 34: ...50 60 76 Temperature S4 MAXIMUM alarm value C F A 47 46 C Temperature S4 MAXIMUM alarm value 105 Temperature S4 MINIMUM alarm value 200 392 C F A 45 44 CONTROL A Superheat set point 11 LowSH thre shol...

Страница 35: ...e of variable A analogue D digital I integer Unit of measure 8 1 In the configuration parameters menu with access by manufacturer password the user can choose the unit of measure for the driver intern...

Страница 36: ...irmware version Tab 8 b Digital input status 0 open 1 closed Note the readings of sensors S1 S2 S3 S4 are always displayed regardless of whether or not the sensor is connected Variables only accessibl...

Страница 37: ...R Relay status 0 0 1 D 9 8 R ALARMS LOP low evaporation temperature 0 0 1 D 10 9 R MOP high evaporation temperature 0 0 1 D 11 10 R LowSH low superheat 0 0 1 D 12 11 R HiTcond high condensing tempera...

Страница 38: ...nfiguration parameter automatic Depends on parameter Sensor S1 alarm manage ment Check the sensor connections Check the Sensor S1 alarm management and Pressure S1 MINIMUM MAXI MUM alarm value paramete...

Страница 39: ...g normal operation the relay contact is closed and is open only in standby There is no change in the event of alarms solenoid valve relay alarm during normal operation the relay contact is closed and...

Страница 40: ...ealarmisnotlinkedtoanyprotectionfunction It features a threshold and a delay and is useful in the event of sensor or valve malfunctions to protect the compressor using the relay to control the solenoi...

Страница 41: ...driver will remain in standby however control will be able to start if the digital input is closed In this case it will start with current cooling capacity 100 case 4 unit in control digital input DI1...

Страница 42: ...reaching operating conditions is very low for a few minutes Check that the LowSH threshold is greater than the superheat value measured and that the corresponding protection is activated integration...

Страница 43: ...he LOP protection threshold is at the required saturated evaporation temperature between the rated evaporation temperature of the unit and the corre sponding temperature at the calibration of the low...

Страница 44: ...iometric pressure sensor 0 to 5 V resolution 0 1 FS measurement error 2 FS maximum 1 typical electronic pressure sensor 4 to 20 mA resolution 0 5 FS measurement error 8 FS maximum 7 typical electronic...

Страница 45: ...2 a Then the user can choose to directly access to the list of parameters for the EVD evolution 1 saved to EEPROM select tLAN This is done in real time ONLINE mode at the top right set the network add...

Страница 46: ...e code Different firmware versions may cause compatibility problems Setting the default parameters 12 4 When the program opens select the model from the range and load the associated list of parameter...

Страница 47: ...46 ENG EVD evolution 030222041 rel 1 0 01 06 2008...

Страница 48: ......

Страница 49: ...CAREL S p A Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency 030222041 rel 1 0 01 06 2008...

Отзывы: