“EVD evolution” +030222041 - rel. 1.0 - 01.06.2008
INSTALLATION
2.
DIN rail assembly and dimensions
2.1
EVD evolution is supplied with screen-printed connectors to simplify
wiring. The shield is connected with a spade terminal.
VBA
T
G0
G
E
X
V connection
Power Supply
Relay
NO 1
COM 1
4
2
3
1
GND
V REF
S1
S2
S3
S4
DI1
DI2
Analog – Digital Input
Network
GND
Tx/Rx
EVD
evolution
70
60
110
45
Fig. 2.a
Description of the terminals
2.2
VBA
T
G0
G
E
X
V connection
Power Supply
Relay
NO 1
COM 1
4
2
3
1
GND
V REF
S1
S2
S3
S4
DI1
DI2
Analog – Digital Input
Network
GND
Tx/Rx
EVD
evolution
aa
Fig. 2.b
Terminal
Description
G, G0
Power supply
VBAT
Emergency power supply
Functional earth
1,3,2,4
Stepper motor power supply
COM1, NO1
Alarm relay
GND
Earth for the signals
VREF
Power to active sensors
S1
Sensor 1 (pressure) or 4 to 20 mA external signal
S2
Sensor 2 (temperature) or 0 to 10 V external signal
S3
Sensor 3 (pressure)
S4
Sensor 4 (temperature)
DI1
Digital input 1
DI2
Digital input 2
Terminal for tLAN, pLAN, RS485, Modbus® connection
Terminal for tLAN, pLAN, RS485, Modbus® connection
Terminal for pLAN, RS485, Modbus® connection
aa
porta seriale di servizio (rimuovere il coperchio per potervi
accedere)
Tab. 2.a
Connection diagram - superheat control
2.3
G
G0
G
G0
VBA
T
C
OM1
NO1
1
3
2
4
NET
OPEN
CLOSE
Tx/Rx
GND
DI1
S4
S3
S2
S1
GND
DI2
VREF
2 AT
24 Vac
230 Vac
30VA
shield
E
VD4
PC
EVD4 ser
vice
USB adapter
4
S
4
2
3
CAREL E
X
V
1
6
7
8 9
10
11
12
13
5
Fig. 2.c
Key:
1
green
2
yellow
3
brown
4
white
5
personal computer for confi guration
6
USB/tLAN converter
7
adapter
8
ratiometric pressure transducer - evaporation pressure
9
NTC suction temperature
10
digital input 1 to enable control
11
free contact (up to 230 Vac)
12
solenoid valve
13
alarm signal
Note:
the use of the driver for the superheat control requires the use of the
•
evaporation pressure sensor S1 and the suction temperature sensor S2,
which will be fi tted after the evaporator, and digital input 1 to enable
control. As an alternative to digital input 1, control can be enabled via
remote signal (tLAN, pLAN, RS485). For the positioning of the sensors
relating to other applications, see the chapter on “Control”;
inputs S1, S2 are programmable and the connection to the terminals
•
depends on the setting of the parameters. See the chapters on
“Commissioning” and “Functions”;
pressure sensor S1 in the diagram is ratiometric. See the general
•
connection diagram for the other electronic sensors, 4 to 20 mA or
combined.