8200-M503-01 Rev-B
•
2XX-IP
4
INSTALLATION, Cont.
Ethernet Cable Installation
NOTE:
The Ethernet cable must be routed through the provided special
metallic gland connector (CPN 6610-1506) and the shield wire must be
connected to this gland connector for grounding and to eliminate RFI.
1. Remove the acorn nuts securing the back panel to
main housing.
2. Locate and remove an unused cable gland
connector for the cable.
3. Install the provided special metallic gland connector.
4. Loosen and remove the metal gland connector nut
and remove the plastic insert.
5. Route the Ethernet cable (CAT 5 or equivalent)
through the nut and plastic insert and into the
enclosure.
6. With the Ethernet cable routed into the enclosure,
refer to the figure below and remove the cable outer
insulating jacket exposing the internal wires. Allow an adequate length of exposed wires to
reach the 2XX-IP Ethernet port (without being tight) after it has been terminated.
7. Next, cut the shield wire so that it extends past the outer jacket approximately 3/4 inch.
8. Referring to the figure below, fold the shield wire back over the plastic insert and then insert
the plastic insert (with the shield wire) into the gland connector.
3/4 inch
Remove outer jacket
Shield
Wire