Remote Panel Option
The remote panel is a device used to control the operation of the heater from a remote location. This unit is
available in both a “2 Position” and “3 Position” configuration, and with or without a cooling output. It also
will accommodate both discharge and space heating configurations. It is important to understand the
following remote panel controls and uses:
Figure 24 - Remote Heater Controls
1.
Manual/Off/Auto Switch
- Used to control blower operation and tempering mode of unit. The
AUTO
position allows the unit to “decide”, through the use of the intake air thermostat, whether or not heating
is needed. The
MANUAL
position allows the user to control whether or not heat is needed. The
OFF
position will turn the blower off when a “3 Position” remote panel is ordered. The
OFF
position will
disable all temperature controls when a “2 Position” remote panel is ordered and fan power is then
controlled by the pre-wire package only.
2.
Lights
-
Displays the current status of unit features. The light definitions are as follows:
POWER
- Illuminated when there is power to the remote panel.
BLOWER ON
- Illuminated when the blower motor is powered.
BURNER ON
- Illuminates after pilot flame has established and main valve is powered.
FLAME FAILURE
- Illuminated when the Flame Safety Control is in alarm mode.
CLOGGED FILTER
– (Optional) Illuminated when the intake filters are dirty.
3.
Temperature Control
-
Controls the discharge temperature of a standard unit. The temperature dial is
replaced with a Maxitrol Selectrastat in space heating applications and is used to control the space
temperature.
4.
Heat/Vent Switch
- This switch is powered when the Manual/Off/Auto switch is in the
MANUAL
position.
It is used to control the tempering mode of the unit. The
VENT
position will prevent the burner
from operating and the heater will deliver untempered air. The
HEAT
position will force the burner on
and the unit will heat the incoming air. This switch becomes a Heat/Vent/Cool switch when the cooling
interlock is ordered. This option provides a 120V cooling output from the remote panel.
MANUAL
AUTO
VENT
HEAT
REMOTE HEATER CONTROLS
BLOWER
ON
BURNER
ON
POWER
FLAME
FAILURE
CLOGGED
FILTER
1
2
3
4
55
60
65
70
75
80
85
90
OFF