29
Pulley Adjustment
The adjustable motor pulley is factory set for the RPM specified (
). Speed can be increased by
closing or decreased by opening the adjustable motor sheave. Two groove variable pitch pulleys must be
adjusted to an equal number of turns open or closed. Any increase in speed represents a substantial
increase in horsepower required by the unit. Motor amperage should always be checked to avoid serious
damage to the motor when the speed is varied. Always torque set screws according to the
torque
.
Figure 17 - Adjustable Pulley
Table 7 - Maximum RPM and HP Chart
Blower Size
Maximum RPM
Maximum HP
7”
2400
2
Decrease Amperage
and
Blower RPM
Setscrew Thread Size
Torque (in-lbs)
No. 10 (bushing)
32
1/4” (bushing)
72
5/16”
130
Содержание D76
Страница 2: ...2...