17
•
Modbus
#
- Adjustable Modbus ID. Exhaust Fan range 11-18, Supply Fan range 21 or 22.
A VFD and
MSC cannot use the same Modbus #
.
•
Options
•
Feedback
Fault
- If set to ENABLED, the MSC will monitor RPM feedback. If the MSC does not
receive data for 30 seconds or 70% of the expected RPM, this fault will be displayed.
Ziehl motors
do not provide feedback.
•
2
Speed
- The 0-10V output cannot be used when the 2 Speed or Manual Speed options are On,
or if the “Control Type” is set to Modbus. When the 0-10V OUT and 0-10V IN terminals are
not
jumped together, the fan will operate at low speed. When 0-10V OUT and 0-10V IN terminals are
jumped together, the fan will operate at high speed.
•
Analog Speed
- The user may enable/disable the option, and calibrate a potentiometer for proper
operation that is connected between the 0-10V OUT and 0-10V IN terminals. When enabled, you
must calibrate the potentiometer. Follow the MSC’s on-screen instructions. The speed will be
adjustable between 0V (low speed) to 10V (high speed).
•
Input Threshold
- When control type is set to Remote 0-10V, an input threshold will be created for
motor control. Refer to
for threshold examples.
•
Zero Operation
- The user may select how the motor will operate when the
0-10V input is at 0V. The options will be Off or Low Speed (default).
•
Threshold
- Increasing the threshold value will allow for the device to hold its voltage/RPM
output while the input is between the 0 - threshold value.
•
Restore
Settings
- Provides access to restore factory settings, and test & balance settings.
•
Factory
Settings
- This will reset all values back to factory settings.
• T & B Settings
- This will reset all values back to last saved test & balance settings.
•
Change
Password
- Users may update the password setting to their own. Password 0225 will also be
stored for backup. Both passwords will allow users to enter “Board Config” settings.
Software Version
- Displays the current software version installed on the board.
Faults
- This provides access to “Fault History,” “Fault Totals,” and “Clear Faults.”
•
Fault
History
- Displays fault history and board reboots in chronological order. Possible displayed
faults are:
•
No
Faults
- There are no active faults with the system.
•
Feedback
Fault
- Only displayed for motors with feedback capabilities.
•
Reboot
- Any time the fan goes from OFF to ON, this “fault” will be logged. This fault will only
display in “Fault History.”
•
Modbus
- Issue with Modbus communication between the MSC and master board.
•
Variable
Device
Fault
- When “Analog Speed” is selected and a potentiometer is connected, if the
voltage drops below 1V, this fault will be displayed.
•
Fault Totals
- Displays amount of faults for Modbus, Feedback, Var Device, Reboot, and Total Faults.
•
Clear
Faults
- Users may clear all faults from the board.
Service
- This provides access to service settings. Password: 1234
•
Save T & B
- After the test & balance process has been completed, save adjustments under this
menu.
•
IO Status
- Provides access to information about the inputs and outputs of the MSC board.
•
V In
- Displays the incoming voltage (0-10V) to the MSC.
•
V Out
- Displays the output voltage (0-10V) to the motor.
•
RPM
- Displays motor RPM feedback.
Ziehl motors do not provide feedback.
•
PWM V
- Displays equivalent voltage reading of the PWM output to the motor.
•
Speed%
- Displays PWM percentage output value to the motor.