C&M 24 Скачать руководство пользователя страница 8

8

5

Please check that you are familiar with the installation requirements before commencing work.(section 6)
The installation accessories described in the following list are included in the boiler packaging.
- Hanging bracket
- A paper template (showing the dimensions of the boiler with 5 mm side clearances, fitting instructions and commissioning
instructions)
- Connection tails
- Screws and wall plugs 
- Connection washers and filters
- Installation manual

Method of positioning the boiler on the wall.

The paper template can be used to ensure the correct positioning of kitchen cabinets etc. It also details the commissioning
instructions.

The paper template has to be fixed to the wall and used to locate the position of the hanging bracket and the centre for the flue
hole.

Drill and plug the wall and secure the hanging bracket using the screws provided. Remove the boiler from its packaging as
shown in fig. 8 and unscrew the 4 screws and remove the casing (Fig. 9).
Place the boiler on the wall on the hanging bracket (Fig. 10).
If required, there is space for all piping to pass behind the boiler. Using Fig. 10 for reference, connect the gas and water pipes
and the valves to the base of the appliance using the tails provided. There is a 190 mm space between the valves and the wall
to make these connections. 

Connecting the boiler to the system

- Push in the tabs “P” (fig. 12) on either side of the boiler and pivot the electrical box forward to gain access to the valve
connections
- Remove the yellow caps and connect the boiler to the taps using washers provided in the plastic bag.
2 x fibre washers for the C/H flow and return.
1 x rubber washer for gas connection.
Provision must be made to fill and recharge the system pressure. This can be achieved using a filling loop or other methods
approved by the local water authority.

Safety valve and condensate drains

The pressure relief valve tube is clear silicone. It should terminate below the boiler over a tundish or 22 mm pipe (see fig 4)
which should in turn discharge safely outside the premises. Care should be taken that it does not terminate over an entrance
or window or where a discharge of heated water could endanger occupants or passers by.

The system should be carefully checked for leaks, as frequent refilling could cause premature system corrosion or
unnecessary scaling of the heat exchanger. The pipe from the siphon 12 (fig. 1) should be connected to a drain is the
conditions described in the relevant Brittish regulations.

External termination via condensate siphon
The condensate drainage pipe should have a minimum diameter of 22 mm, it should be inserted into a suitable acid resitant
pipe - e.g. plastic waste or overflow pipe (refer to BS 6798 : 2000) by at least 50mm, must have a continuous fall and
preferably be installed and terminated within the building.

Pay special attention to not bend the condensates silicone drain pipe such as the flow will be interrupted. 

The discharge pipe must terminate in a suitable position:

i)

Connecting to an internal soil stack (at least 450mm above the invert of the stack).  A trap giving a water seal of at least 
75mm must be incorporated into the pipe run, there must also be an air break upstream of the trap.

ii)

Connecting into the waste system of the building, such as a washing machine or sink. The connection should be upstream

of the washing machine / sink (if the connection is down stream of the waste trap then an additional trap giving a minimum
water seal of 75mm and an air break must be incorporated in the pipe run as above.

iii) Terminating into a gully below the grid level but above the water level.

iv) Into a soakaway.

N

OTE

:

IF ANY CONDENSATE PIPEWORK IS TO BE INSTALLTED EXTERNALLY

THEN IT SHOULD BE KEPT TO A MINIMUM AND BE INSULATED WITH

A WATERPROOF INSULATION AND HAVE A CONTINUOUS FALL

The condensate flow can reach 2 litres/hour; because of the acidity of the condensate products (Ph close to 2), take care
before operation.

Fitting the Horizontal Flue

Attention ! Before starting the boiler, the siphon 12 fig. 1 must be filled with water. Before fitting the flue terminal onto
the boiler, please poor 1/4 litre of water in the exhaust pipe as shown in Fig. 11.

The instructions for the vertical and biflux (twin pipe) flue options are included with the relevant adapter kits.

The standard flue supplied with the appliance is suitable for lengths from 300 mm minimum to 720 mm maximum.

Installing the Boiler

Содержание 24

Страница 1: ...system 30 c Manufactures N Model Type Gas Council N 200905821037 31 Centora Green System 24 Nat 41 980 12 200906822037 31 Centora Green System 30 Nat 41 980 31 GB IE U n i t 3 A T h o r n t o n R o a...

Страница 2: ...ors and windows to ventilate the room Shut the gas mains tap on the gas meter or the valve of the gas cylinder and call your Gas Supplier immediately If you are going away for a long period of time re...

Страница 3: ...S 7671 and document IGE UP 7 In the Republic the Republic of Ireland the installation should be carried out in accordance with the following codes of practice I S 813 Domestic Gas Installation the fol...

Страница 4: ...T FUNCTION 21 19 TECHNICAL DATA 22 This instruction booklet is especially designed for appliances installed in the The United Kingdom and The Republic of Ireland INTRODUCTION The CENTORA GREEN SYSTEM...

Страница 5: ...at sensor 42 Silencer 1 2 3 4 5 6 8 11 12 13 14 35 30 24 34 1 INSTALLER S INSTRUCTIONS 7 Fig 1 Fig 3 15 21 10 9 Fig 2 33 36 31 32 19 18 23 16 29 24 Display 27 Setting key 28 Setting key 29 Central Hea...

Страница 6: ...m The expansion vessel is pre charged to 0 7 bar 10 lb in 2 The vessel is suitable for systems up to 145 litres capacity For systems of greater capacity an additional expansion vessel will be required...

Страница 7: ...ulphur level contained in the gas should comply with the europ an Standards which are maximum 150 mg m3 for a short period in a year average level of 30 mg m3 during one year Electrical Supply The app...

Страница 8: ...e system should be carefully checked for leaks as frequent refilling could cause premature system corrosion or unnecessary scaling of the heat exchanger The pipe from the siphon 12 fig 1 should be con...

Страница 9: ...of 5 mm If the flue is a side exit installation then calculate the position of the hole with a slope of 5 mm metre towards the boiler from the terminal The flue should rise up slightly to the terminal...

Страница 10: ...rthing continuity DHW Open the main cold feed valve 40 Open all hot taps to purge DHW system Check for water soundness Check flow rate at the bath tap is set correctly see technical data Central Heati...

Страница 11: ...available in C H mode Post Commissioning Ensure system pressure has been set correctly Set all parameters of the boilers as shown in chapter 9 ADJUSTMENTS AND SETTINGS Set boiler thermostat and contro...

Страница 12: ...eter in a section Press on setting key key on the Left side to enter in modification mode The 2nd and 3rd digits are flashing Press on or on the Right side to select the correct value then press on Se...

Страница 13: ...ersion of display PCB 0 10 to 99 Flue type 2 1 FF variable speed Room thermostat is calling for heat 3 0 no 3 1 yes Theoretical position of the 3 way valve 4 0 DHW 4 1 CH DHW flow temperature in Celsi...

Страница 14: ...min 2 1 0 min 2 5 0 min Maximum Central Heating flow temperature 4 50 C 4 80 C CH anti cycling delay 8 0 0 min From 0 to 7 minutes by step of 0 5 min 8 0 5 min 8 2 5 min 8 5 0 min CH maximum output li...

Страница 15: ...erature is displayed in celsius degrees The 3 dots indicate that the combustion rate control is ON at maximum output X X Switching off the combustion rate control mode press once press once press once...

Страница 16: ...side times The display shows 906 which corresponds to the 18 kW which is the factory setting 9 section 9 06 18 kW press on setting key on the Left side one time the 2nd and 3rd digits flash together T...

Страница 17: ...l Heating thermistor faulty open circuit 12 Central Heating thermistor faulty open circuit 18 Attempt to re light 20 Wiring problem 23 Fan speed too low 24 Fan control system defective 31 Communicatio...

Страница 18: ...nge indicator Burner ON 35 Red indicator Lock out flame failure 36 Reset button 12 Connecting bracket Taps shown in Open position fig 21 37 Central heating flow isolating valve 39 Gas service tap 41 C...

Страница 19: ...ing Press on key 29 the green indicator 30 will light and the display will show the Heating flow temperature Keys 31 and 32 allow to adjust the temperature required in the Central Heating system regar...

Страница 20: ...and the burner will start 13 15 The manufacturer s guarantee is for 12 months from the date of purchase The guarantee is voidable if the appliance is not installed in accordance with the recommendati...

Страница 21: ...system and rise up the system pressure chapter 8 Close the heating flow isolating valve Don t forget to open it again when you will start heating Gas Conversion Incorrect Operation Helpful suggestions...

Страница 22: ...0 87 m3 h 31 ft3 h 1 m3 h 35 ft3 h Gas valve restrictor diameter without without Propane L P G G31 Gas rate C H max 1 94 kg h 36 ft3 h 2 21 kg h 41 ft3 h Gas rate C H mini 0 64 kg h 12 ft3 h 0 73 kg h...

Страница 23: ...23 U n i t 3 A T h o r n t o n R o a d I n d E s t a t e O f f H o c k n e y R o a d B r a d f o r d B D 8 9 H Q 0 1 2 7 4 4 8 8 3 8 8 w w w h e a t i n g s p a r e s 2 4 7 c o m...

Страница 24: ...ited MTS Building Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone 01494 755600 Fax 01494 459775 Internet www chaffoteaux co uk E mail info uk mtsgroup com Technical Support Help Line 0870 241 8...

Отзывы: