SOUNDER DURATION (sounder ring time)

3-2 (Range  3-20 minutes)

Enter 3-2. This has been  preset to a factory default of 15 minutes.  A new time
may be programmed by entering one key from the following table. Press * to
confirm the selection. The accept tone will sound.

Enter 1

 3  minutes. Led 1 on.

Enter 2

 4  minutes. Led 2 on.

Enter 3

 5  minutes. Led 3 on.

Enter 4

10 minutes. Led 4 on.

Enter 5

15 minutes. Led 5 on. (default)

Enter 6

20 minutes. Led 6 on.

NIGHT SET  / HOME SET EXIT TIME

3-3 (Range 0-90 seconds)

Enter 3-3. This has been  preset to a factory default of 15 seconds.  A new time
may be programmed by entering one key from the following table. Press * to
confirm the selection. The accept tone will sound.

Enter 0

  0 Seconds. All LED's off ( Instant ).

Enter 1

10 Seconds. Led 1 on.

Enter 2

15 Seconds. Led 2 on. (default)

Enter 3

30 Seconds. Led 3 on.

Enter 4

45 Seconds. Led 4 on.

Enter 5

60 Seconds. Led 5 on.

Enter 6

90 Seconds. Led 6 on.

NOTE: The exit sounder volume can be altered by the control on the PCB marked

VOLUME or RV1

. Please note, this will not apply to keypad bleepers.

Option

Option

Results from choosing option no.

Code

Description

0

1

2

3

4

5

6

3-0

Exit Time (secs)

10

15

30

45

60

90

3-1

Entry Time (secs)

10

15

30

45

60

90

3-2

Sounder Duration (mins)

3

4

5

10

15

20

3-3

Night  / Home Exit (secs)

0

10

15

30

45

60

90

Examples

Change the FULL set exit time to 60 seconds

ENTER THIS

3-0

5

*

Description

Choose full set

Select 60 seconds

Confirm selection

Change the Sounder duration to 3 minutes

ENTER THIS

3-2

1

*

Description

Choose
sounder

Select 3 minutes

Confirm selection

Change the ENTRY time to 45 seconds

ENTER THIS

3-1

4

*

Description

Choose entry

Select 45 seconds

Confirm selection

SOUNDER
DURATION

NIGHT / HOME
SET EXIT TIMER

SUMMARY

Содержание S802

Страница 1: ...INSTALLATION MANUAL SECURIT 802 CONTROL PANEL S802 ...

Страница 2: ...nal Devices 5 Strobe 5 Keyswitch Connections 5 Aux DC power 5 Mounting Keypads 6 Wiring Keypads 6 Powering Up 6 7 Programming 7 Exit Time 7 Entry Time 7 Bell Duration 8 Night Set Exit Time 8 Home Set Exit Time 8 Circuit Programming 9 Zone Selections 9 Extended Programming 9 Home Set Zone Selection 9 10 Engineer Access Code 10 Engineer Log Review 10 Engineer Test Options 10 Restoring Default Codes ...

Страница 3: ...ill incur otherwise the unit will be repaired and returned free of charge PRODUCT DESCRIPTION The Securit 800L hereafter known as the Control Panel is an 8 zone programmable microprocessor control panel using state of the art technology and manufacturing techniques The panel has many advanced features that can only be found in more expensive control panels such as two user codes Chime Fire and Key...

Страница 4: ... C to 40 C Humidity 10 to 90 R H non condensing Dimensions 263 mm W 223 mm H 82 mm D Control Panel Weight 2 7 kg Excluding Battery Stand by Battery 1 2 Ah 12 V Rechargeable Lead Acid 2 1 Ah max Maximum Cable Run 100 Metres per run Use For internal use only Factory Defaults User customer Code 1 1234 User customer Code 2 Disabled 0000 Engineer Code 7890 Circuit 1 Entry Circuit Fixed Circuit 2 Alarm ...

Страница 5: ...ensure continued safe operation CAUTION Under certain circumstances the transformer metalwork can reach 70 C this is normal and well within prescribed limits Battery connection Maximum battery size 12V 2 1Ah max This panel requires a standby battery to be fitted to provide power in the event of mains failure A valve regulated lead acid battery must be used Detector circuits Connections are provide...

Страница 6: ...al sounder and strobe are shown in diagram A Please note sounder trigger is applied negative Negative ring ST Strobe switched negative trigger S Sounder switched negative trigger Sounder hold off strobe positive supply Sounder hold off supply sounder tamper feed negative R Sounder tamper return negative AUX DC Detector power The auxiliary power is provided from connections marked AUX This is to pr...

Страница 7: ... for series and parallel examples DIAGRAM C POWERING UP INITIAL POWER UP NOTE The lid should remain off the main control panel so that engineer mode may be used Alternatively entering 7890 can also be used to enter engineer mode If the engineers code is entered and the panel is then left it will set 1 Switch the mains supply on the internal sounder will start This denotes a tamper alarm 2 Enter 1 ...

Страница 8: ...d PROGRAMMING Once in engineering mode the day LED will flash You now have the following options available EXIT TIME 3 0 Range 10 90 Seconds Enter 3 0 This has been preset to a factory default of 30 seconds A new time may be programmed by entering one key from the following table Once the desired option is chosen press to confirm The accept tone will sound Enter 1 10 Seconds Led 1 on Enter 2 15 Se...

Страница 9: ...n Enter 2 15 Seconds Led 2 on default Enter 3 30 Seconds Led 3 on Enter 4 45 Seconds Led 4 on Enter 5 60 Seconds Led 5 on Enter 6 90 Seconds Led 6 on NOTE The exit sounder volume can be altered by the control on the PCB marked VOLUME or RV1 Please note this will not apply to keypad bleepers Option Option Results from choosing option no Code Description 0 1 2 3 4 5 6 3 0 Exit Time secs 10 15 30 45 ...

Страница 10: ... OPTIONS 7 Range 1 8 Further options are available to increase the versatility of the control panel Enter 7 1 Disables sounder strobe in night set Enter 7 2 Chime Enable See user manual for zone allocation Enter 7 3 Full set door sense setting Enter 7 4 Convert L to ID output Enter 7 5 Allow Manual Isolation of Zone 1 Entry Exit In night set Enter 7 6 Remote Keypad PA Enable Operated by Enter 7 7 ...

Страница 11: ...ar a continual tone which denotes you are viewing the last set condition There may be no lights illuminated as there may not have been an alarm during that time Pressing the key will turn off the sounder and show the last unset period By pressing 0 you will show the last ALARM condition that was caused in an UNSET period no matter how long ago that alarm was Pressing will bring the sounder back on...

Страница 12: ...and is labelled Memory Default at which point zone 1 light will illuminate 2 Wait a few seconds then re connect the battery and then the mains and then refer to page 6 regarding initial power up The speaker will omit the accept tone and the factory user code defaults will be restored 3 Remove the link at which point zone 1 light will go out GLOSSARY OF TERMS FULL SET This is a setting method norma...

Страница 13: ...NG This allows you to have a variable FULL SET EXIT TIME You can program the EXIT time to maximum and when you full set the system the exit time will drop to 8 seconds as soon as the EXIT door has closed thus avoiding the preset exit time FULL SET KEYSWITCH This allows the panel to be set unset and reset via zone 8 This is performed by using a 2 position keyswitch make break across the zone To set...

Страница 14: ...NTROL PANEL OR WITH THE INSTALLER IT CAN BE USED TO REFER TO PROGRAMMING DETAILS WHEN NEEDED CONTROL PANEL ST S AUX R SONADE 2000 STROBE B D A T FLASHGUARD XL STROBE SIREN SUPPLY SUPPLY TAMPER OUT STARLIGHT 2000 ST R H H RTN ACTIVEGUARD STB S 12V 12V RIGHT HAND TAMPER ACTIVE GUARD 3 ST SW V V RET SECURIGUARD STROBE S SUPPLY SUPPLY LEFT HAND TAMPER NOVA GUARD 2 T STROBE S 12V 12V R SPIRIT AU1000 ST...

Страница 15: ...iring Make sure the devices are wired in series NOT parallel Zone activates during entry Seeing an alarm zone on entry or deviating from entry route Make sure all zones on entry route are programmed with walkthrough Don t deviate Zone activates even in day mode Programmed to PA or FIRE Reprogram the zone to be an alarm zone or similar If you are still experiencing problems then contact our technic...

Страница 16: ...oat Industrial Estate Redditch Worcs B98 9HE Tel 01527 68111 Fax 01527 68222 Tech Support 0345 660533 9am 5pm Weekdays UK ONLY email to info cksys co uk website http users powernet co uk cksys 5 051 519 01 Approved BS EN ISO No 9002 1994 Certificate No 0944 ...

Отзывы: