9
CIRCUIT PROGRAMMING
4 (Range 2-7)
Circuits 2 - 7 can be reprogrammed to suit your requirements. Circuit 1 is fixed as
a Final exit circuit. Circuit 8 has limited options.
ENTER
PROGRAM ZONE
ENTER
PROGRAM ZONE
4 - 2
2
4 - 6
6
4 - 3
3
4 - 7
7
4 - 4
4
4 - 8
8
4 - 5
5
Select the circuit you wish to alter. That circuit may then be programmed by
entering one key from the following table. Once the option is selected press * to
confirm. The accept tone will sound.
N/S = Night Set
Option no.
Zones 2-7
Zone 8
1
Alarm
Alarm
2
Alarm with walk through
Fire
3
Alarm & Isolate in Night Set
PA
4
Alarm, Walk through & Isolate in N/S
Full set keyswitch
5
Alarm, Walk through & N/S Entry
6
Fire
7
Entry Route
8
P.A
SEE GLOSSARY OF TERMS (p.11) FOR DESCRIPTIONS OF ZONE TYPES etc.
To program zone 3 as an “Entry Route” enter - 4 3 7 *
To program zone 8 as a “Keyswitch” enter - 4 8 4 *
EXTENDED PROGRAMMING OPTIONS
7 (Range 1-8)
Further options are available to increase the versatility of the control panel.
Enter 7 - 1
Disables sounder & strobe in night set.
Enter 7 - 2
Chime Enable ( See user manual for zone allocation).
Enter 7 - 3
Full set door sense setting.
Enter 7 - 4
Convert L+ to ID- output.
Enter 7 - 5
Allow Manual Isolation of Zone 1 (Entry/Exit) In night set.
Enter 7 - 6
Remote Keypad PA Enable ( Operated by * & # ).
Enter 7 - 7
L+ will latch only the first detector to alarm.
Enter 7 - 8
Inhibit strobe testing. ( For speech dialler connection)
Press * to confirm. The accept tone will sound
HOME SET ZONE SELECTION
8 (Range 1-8 N/A if Fire or PA)
This Control Panel can enable parts of the premises to be alarm protected while
other parts are occupied and in use .. This can be achieved by using the
Home
Set
feature. This is similar to
Night Set
except that an Exit/Entry route is not
required as part of the Setting or Unsetting procedure.
In programming mode press 8 to select
Home Set
zone selection mode.
CIRCUIT
PROGRAMMING
ZONE
SELECTIONS
EXTENDED
PROGRAMMING
HOME SET
ZONE
SELECTION