24VDC connection of individual front access batteries 

 

Step 1

.  

If installing in a multiple tier rack or cabinet arrangement, always begin with the lowest shelf,  

string A & B, place each the individual front access batteries on the shelf (typically 4 per level) with 
approximately 1/2 inch spacing between the individual units. All the batteries should be placed with terminals 
 to the front of the rack / shelf. Remove and save terminal protectors.

  

 

Step 2.

  

If supplied by the rack/cabinet manufacturer, place a safety shield in the center of the tray between 

adjacent 24 volt battery strings. 
 
Step 3.  C&D recommends, prior to connection of inter-unit bus bars and lugged cables, the battery terminals and 
all contact surfaces should be neutralized, cleaned, lightly brushed with a brass bristle brush or scotch brite type 
pad and lightly coated with protective No-Ox-Id terminal grease. 
 
Step 4a.  Starting at the battery on the far right of the tray/shelf, which is to be the positive (+) output, label it as 
number 1 and then label the adjacent battery to the left as battery number two, string A.  Repeat the numbering 
procedure for the adjacent string (next two batteries to the left), string B. 
 
Step 4b.  If more than two 24 VDC strings is within the enclosure, number these batteries the same way.  
Identify the bottom tray as string A and B with the strings above as string C and D and so on  
 
Step 5.  Using the provided inter-unit bus bar and hardware (bolt and washer), connect between String A,  
battery 1’s negative (-) terminal to String A, battery 2’s positive (+) terminal as shown in Figure 5.  Tighten bolt 
washer assembly hand tight. 
 
Step 6.  Torque each of the above bolt washer assemblies as per the inch-pound specifications in Table 3 for the 
appropriate product.    
 
Step 7.   Following the rack or cabinet manufacturers cabling guidelines to attach the lugged power lead 
connections  to positive (+) of String A, battery 1 and negative (-) of String A, battery 2 terminals verifying 
proper polarities are observed. 
 
Step 8.   Torque each of the above bolt washer assemblies as per the inch-pound specifications in Table 3 for the 
appropriate product.    
 
Step 9.   Repeat above steps for String B and each of any remaining battery strings. 
 
Step 11.  Install all protective terminal covers and use a utility knife or diagonal cutter to trim the cover as 
needed allowing for proper cable routing.  
 
Step 12.  Verify charging equipment is set for proper float voltage of 2.25 to 2.30 volt per cell at 77°F at the 
battery terminals (27 to 27.6 VDC for a nominal 24 volt battery). 

 

 

Parallel Connection of individual strings of batteries 

 

C&D recommends each individual battery string be cabled separately to a common junction point or box. Each 
string may also contain a separate fuse or disconnect switch to facilitate maintenance. The parallel 
connections should be completed only when the charger and load are not connected to the battery output 
circuit or battery string voltage should be matched to within 0.5 volts before the connection is made and 
should be performed only by qualified technicians familiar with live battery connections. The battery 
strings must not be ''daisy chained'' in parallel. 

 
 
 
 

 

RS02046/0514/CD 

 

 

 

 

 

 

 

www.cdtechno.com 

Содержание TEL12-105FNSG

Страница 1: ...rmation www cdtechno com Technical Warranty Assistance contact C D Technologies Inc 1400 Union Meeting Road PO Box 3053 Blue Bell PA 19422 0858 800 543 8630 or 215 619 2700 Fax 215 619 7899 Before han...

Страница 2: ...TEL12 170F FG 1 15028593 8mm x 16 1 15028594 2 15028591 15028595 15028596 1 15028538 TEL12 180F 1 30046800 20 x 3 4 1 15029218 2 15029217 N A N A 1 15028506 TEL12 190F FG 1 15028593 8mm x 16 1 1 15028...

Страница 3: ...trolyte which contains dilute sulfuric acid this is harmful to the skin and eyes is electrically conductive and is corrosive If electrolyte contacts the skin wash immediately and thoroughly If electro...

Страница 4: ...ohm meter ohmic test set 100 amp momentary load test set or system load bank Typically for Telecom applications four individual batteries are connected in series to form a higher voltage string of ba...

Страница 5: ...e terminal to battery 2 s positive terminal as shown in Figure 4 Tighten bolt washer assembly hand tight Step 5 Repeat using the provided inter unit bus bar and hardware bolt and washer connect betwee...

Страница 6: ...gative terminal to String A battery 2 s positive terminal as shown in Figure 5 Tighten bolt washer assembly hand tight Step 6 Torque each of the above bolt washer assemblies as per the inch pound spec...

Страница 7: ...unsafe condition VI Freshening Charge When the batteries have been in storage or transit for an extended period over 6 months or if OCV s are below 12 48 volts or when the number of cells in series i...

Страница 8: ...vent the free flow of gases thru the exit point Semiannual Inspection Repeat the quarterly checks Record the on charge voltage of each unit Optionally perform and record Ohmic checks for trending purp...

Отзывы: