Table 3 - Post hardware torque values
Battery Models
Terminal
Hardware Size
Typical
Socket
Required
Initial Torque
Maintenance Torque
TEL12-105FNS/FNSG, TEL12-155F/FG,
TEL12-170F/FG, TEL12-190F/FG,
TEL12-210F/FG
M8
13mm
160 in-lbs (18 N-m)
160 in-lbs (18 N-m)
TEL12-115FN/FNG, TEL12-145FW
M6
10mm
110 in-lbs (12.4N-m)
110 in-lbs (12.4N-m)
TEL12-160F, TEL12-160FW,
TEL12-180F, TEL12-210Fa
1-4/20
7/16"
110 in-lbs (12.4N-m)
110 in-lbs (12.4N-m)
I. Safety
Installation and servicing of batteries should be performed or supervised by personnel knowledgeable of
lead acid batteries standard safety practices i.e., personal and equipment safety precautions.
Safety Concerns (Please reference C&D Material Safety Data Sheet document L-84 for additional
information which is available directly from www.cdtechno.com)
•
Electrical Hazards
Battery systems present a risk of electrical shock and high short circuit current. Remove any metal
objects (e.g. watches and rings), use properly insulated tools, and wear eye protection and rubber gloves.
Observe circuit polarities, use a voltmeter to check potentials before making connections and do not
make or break live circuits without following all proper safety precautions
.
•
Disposal
Lead Acid Batteries are to be recycled. VRLA batteries contain lead and immobilized dilute sulfuric
acid. Dispose of in accordance with Federal, State and local regulations. Do not dispose of in a
landfill, lake or other unauthorized location. For assistance contact C&D at
•
Chemical Hazards
Any liquid emission from a battery may be electrolyte which contains dilute sulfuric acid this is
harmful to the skin and eyes, is electrically conductive and is corrosive. If electrolyte contacts the
skin, wash immediately and thoroughly. If electrolyte enters the eyes, promptly flush eyes with water
and seek medical attention. Neutralize spilled electrolyte with a solution of 1 lb. bicarbonate of soda
(baking soda) to 1 gallon of water.
•
Fire, Explosion and Heat Hazards
Batteries can contain an explosive mixture of hydrogen gas which can vent under overcharging
conditions. Do not smoke or cause sparks in the vicinity of the battery. Do not install and charge
batteries in a sealed container. Mount the individual batteries with a minimum of 0.5'' between units.
If contained, assure the container or cabinet and room have adequate ventilation to prevent
accumulation of potentially explosive vented gas. Refer to the current issue of the National Electric
Code (NEC) and other applicable building codes.
Please note that for sealed cabinets with VRLA gas
removal provisions, the C&D TEL Series batteries with gas collection (G suffix) and the optional
tubing kit can be utilized (see Diagram in Section V of this document)
•
Caution
Do not attempt to remove battery vents or add water as this presents a safety hazard and voids the
warranty. Wash hands after any contact with the battery lead terminals.
II. Receiving Instructions
Upon receipt, inspect the batteries for physical damage to the containers and terminals. If found, a claim must
be filed with the carrier within 10 days. Also check the packing slip to make sure all material has arrived.
The batteries are shipped fully charged. Their Open Circuit Voltage (OCV) should not be below 12.48 volts
per 12 volt unit.
RS02046/0514/CD
3
www.cdtechno.com