General: 

The purpose of this manual is to inform installers how to receive, install and maintain C&D Technologies front 
access batteries.  

Battery Description: 

The Valve Regulated Lead Acid (VRLA) battery is a minimal maintenance system utilizing an oxygen 
recombination cycle to minimize gassing and eliminate electrolyte maintenance. The dilute sulfuric acid 
electrolyte is immobilized by absorbent glass mat (AGM) separators. Each of the 2 VDC cells (6 cells per 
unit) in each unit has a unique self-resealing one way valve to relieve any excess pressure generated 
during overcharging conditions. Four six cell units in series make up a 24 cell 48VDC battery, two six cell 
units in series for a 12 cell 24VDC applications. 
 

 

 

See Section IV.

 

Installation Instructions

-

for further descriptions.   

 

 
 

 

Model 

Bus Bar 

Connector 

Hardware 

Package (two 

SS Bolts & 

two SS 

washers)  

Protective 

Terminal 

Cover 

Lifting 

Handle 

Gas Collection 

Plug Kit 

Gas Collection 

Tubing Kit 

TEL12-
105FNSG/FNS 

(1) 15028536 

8mm x 16 

(1) 15028540 

(2) 15028591 

15028595* 

15028596* 

(1) 15028538 

TEL12-
115FN/FNG 

(1) 15028537 

6mm x 16 

(1) 15028540 

(2) 15028591 

15028595* 

15028596* 

(1) 15028539 

TEL12-145FW 

(1) 30046795 

6mm x 16 

(1) 15028594 

(2) 15029231 

N/A 

N/A 

(1) 15028539 

TEL12-
155F/FG 

(1) 15028593 

8mm x 16 (1) 

(1) 15028594 

(2) 15028591 

15028595* 

15028596* 

15028538 

TEL12-160F 

(1) 30046800 

1/4-20 x 3/4 

(1) 15029218 

(2) 15029217 

N/A 

N/A 

(1) 15028506 

TEL12-160FW 

(1) 30046795 

¼-20 x 3/4 

(1) 15029218 

(2) 15029217 

N/A 

N/A 

(1) 15028506 

TEL12-
170F/FG 

(1) 15028593 

8mm x 16 

(1) 15028594 

(2) 15028591 

15028595* 

15028596* 

(1) 15028538 

TEL12-180F 

(1)30046800 

¼-20 x 3/4 

(1) 15029218 

(2) 15029217 

N/A 

N/A 

(1) 15028506 

TEL12-
190F/FG 

(1) 15028593 

8mm x 16 (1) 

(1) 15028594 

(2) 15028591 

15028595* 

15028596* 

15028539 

TEL12-
210F/FG 

(1) 15028593 

8mm x 16 

(1) 15028594 

(2) 15028591 

15028595* 

15028596* 

(1) 15028538 

TEL12-210Fa 

(1)30046800 

¼-20 x ¾ 

(1) 15028506 

(1) 15029218 

(2) 15029217 

N/A 

N/A 

*Models with “G” suffix only 

Hardware, terminal protector, and bus bar indicated above is individually packaged within the insert on the top of the 
battery, inside the shipping carton of each 12 volt battery unit

Batteries ordered without cartons (bulk) do not include 

connector or hardware. 

 

 

Safety Glasses for each installer   
Insulated gloves (1 pair for each installer)                  
Digital Voltmeter           
Terminal Prep Supplies (water, baking soda, cloth rag, brass bristle brush or scotch brite type pad, NO-OX-ID terminal 
grease)                   
Insulated Inch Pound Torque Wrench (up to 160 in lb) 
Insulated 7/16” socket wrench for TEL12-105FS, TEL12-160F, TEL12-160FW, TEL12-180F &  
TEL12-210Fa models 
Insulated 10mm socket wrench for TEL12-115FN/FNG & TEL12-145FW models      
Insulated 13mm socket wrench for TEL12-105FNSG/FNS,TEL12-155F/FG, TEL12-170F/FG, 
TEL12-190F/FG, TEL12-210F/FG models 
Utility knife or diagonal cutter  (for trimming protective covers and gas collection tubing if used)     
Battery Numbers and String Letters/Numbers 
Optional plastic apron, portable eyewash, spill kit and fire extinguisher (Class C) 

Table 1 - Installation Tools (minimum) required to be supplied by Installer

 

Table 2 - Installation Hardware Included with each 12 Volt Battery 

RS02046/0514/CD 

 

 

 

 

 

 

 

www.cdtechno.com 

Содержание TEL12-105FNSG

Страница 1: ...rmation www cdtechno com Technical Warranty Assistance contact C D Technologies Inc 1400 Union Meeting Road PO Box 3053 Blue Bell PA 19422 0858 800 543 8630 or 215 619 2700 Fax 215 619 7899 Before han...

Страница 2: ...TEL12 170F FG 1 15028593 8mm x 16 1 15028594 2 15028591 15028595 15028596 1 15028538 TEL12 180F 1 30046800 20 x 3 4 1 15029218 2 15029217 N A N A 1 15028506 TEL12 190F FG 1 15028593 8mm x 16 1 1 15028...

Страница 3: ...trolyte which contains dilute sulfuric acid this is harmful to the skin and eyes is electrically conductive and is corrosive If electrolyte contacts the skin wash immediately and thoroughly If electro...

Страница 4: ...ohm meter ohmic test set 100 amp momentary load test set or system load bank Typically for Telecom applications four individual batteries are connected in series to form a higher voltage string of ba...

Страница 5: ...e terminal to battery 2 s positive terminal as shown in Figure 4 Tighten bolt washer assembly hand tight Step 5 Repeat using the provided inter unit bus bar and hardware bolt and washer connect betwee...

Страница 6: ...gative terminal to String A battery 2 s positive terminal as shown in Figure 5 Tighten bolt washer assembly hand tight Step 6 Torque each of the above bolt washer assemblies as per the inch pound spec...

Страница 7: ...unsafe condition VI Freshening Charge When the batteries have been in storage or transit for an extended period over 6 months or if OCV s are below 12 48 volts or when the number of cells in series i...

Страница 8: ...vent the free flow of gases thru the exit point Semiannual Inspection Repeat the quarterly checks Record the on charge voltage of each unit Optionally perform and record Ohmic checks for trending purp...

Отзывы: