![CanadianSolar CSI SERIES Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/canadiansolar/csi-series/csi-series_installation-and-operation-manual_4081198036.webp)
9. Specifications
Compliance
MPPT operation range
Number of MPPT/strings per MPPT
Rated output power
Max. output power
Rated grid voltage
Operation phase
Rated grid output current
Output power factor range
Grid current THD
Rated grid frequency
Max. Efficiency
Protection
Size(inch)
Weight
Topology
Internal consumption
Running temperature
Ingress protection
Interface
Design lifetime
Operating Range Utility Frequency
Operation Surroundings Humidity
Connections
200~850Vdc
50kW
480Vac
422. 4
~
528Vac
Three phase
0.8leading ... 0.8lagging
<50mA
60Hz
-
25
~
60
℃
RS485 WIFI GPRS(Optional)
>20years
59.5-60.5Hz
4/3
50kW
60.2Aac
<1W(Night)
0~100% Condensing
<3%
1000Vdc
24.8W*40.7H*13.9D
CSI-50KTL-GS-B
Transformerless
>98.8%
DC class II and AC class III(optional)
NEMA 4X
114A (28.5A per MPPT)
172lb
9. Specifications
Compliance
MPPT operation range
Number of MPPT/strings per MPPT
Rated output power
Max. output power
Rated grid voltage
Operation phase
Rated grid output current
Output power factor range
Grid current THD
Rated grid frequency
Max. Efficiency
Protection
Size(inch)
Weight
Topology
Internal consumption
Running temperature
Ingress protection
Interface
Design lifetime
Operating Range Utility Frequency
Operation Surroundings Humidity
200~850Vdc
60kW
480Vac
422. 4
~
528Vac
Three phase
0.8leading ... 0.8lagging
<50mA
60Hz
-
25
~
60
℃
RS485 WIFI GPRS(Optional)
>20years
59.5-60.5Hz
4/4
60kW
72.2Aac
<1W(Night)
0~100% Condensing
<3%
1000Vdc
24.8W*40.7H*13.9D
CSI-60KTL-GS-B
Transformerless
>98.8%
DC class II and AC class III(optional)
NEMA 4X
114A (28.5A per MPPT)
172lb
CSI-66KTL-GS-B
66kW
66kW
79.4Aac
Connections
4 knockout for 2" conduit at bottom and side.
DC Input - Copper only 12-6AWG
AC Input - Copper or aluminum 8-2AWG
Aluminum requires bi-metallic compatible terminal
4 knockout for 2" conduit at bottom and side.
DC Input - Copper only 12-6AWG
AC Input - Copper or aluminum 8-2AWG
Aluminum requires bi-metallic compatible terminal
.69.
.68.
Grid voltage range
DC injection current
Max DC input voltage
Max DC input current
Grid voltage range
DC injection current
Max DC input voltage
Max DC input current
CAN/CSAC22.2 N107.1, UL1741 SA, IEEE1547
UL1998, UL1699B, FCC part 15, Class B, ISO-NE
CAN/CSAC22.2 N107.1, UL1741 SA, IEEE1547
UL1998, UL1699B, FCC part 15, Class B, ISO-NE