6.7.8 STD
Mode Settings
1.
Working Mode Set
2.
Power Rate Limit
3.
Freq Derate Set
4.
10mins Voltage Set
5.
Initial Settings
Selecting “STD Mode. Settings” displays the sub-menu shown below:
This section is applicable to maintenance personnel only.
Table
6.4
Voltage ride through
Wear
pressure
Region
1
2
3
4
5
Hv2
voltage
(
% nominal voltage
)
480Va.c.
V≥576
240≤V
<
336
/ /
12S
/ /
20S
Operating mode
Momentary
Cessation
Continuous
Operation
Mandatory
Operation
Maximum
time limit
0.16S
11S
13S
21S
/ /
6
V
<
240
1
.
5S
Hv1
NN
Lv1
Lv2
Lv3
528
<
V
<
576
422.4≤V≤528
336≤V
<
422.4
Ride-through
until
10S
1S
Not
Applicable
Mandatory
Operation
Momentary
Cessation
The voltage and frequency ride through limit is fixed, can't change.
6.7.7.9 IgZero_COMP.Set
6.7.7.10 PI Set
This function is applicable by maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
This function is applicable by maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
Figure 6.23 V/FRT Set
VRT
_
US
:
STOP
FRT
_
US
:
STOP
6.7.7.11 IgADCheckPRO Set
This function is applicable by maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
6.7.7.12
NoSmallPulse
Set
This function is applicable by maintenance personnel only.
Canadian
Solar Three Phase Inverters support 6 working mode in this menu:
1. Null
2. Volt-watt
3. Volt-Var
4. Fixed-PF
5. Reac-Power
6. P-Factor
7. VgWatt-UL
Based on UL1741SA , work mode 1, 3, 4, 7 could be used for grid operator.
6.7.8.1 Working Mode Set
1. Null (Default setting)
Inverter not under any of below working mode.
The default setting of working mode is Null.
This function is applicable by maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
2. Volt-Watt
Inverter will limit output power when voltage changes. This mode is not required by UL1741SA .
6. Normal operation
6. Normal operation