192 

Invalid igniter on during setting 

Lockout 

193 

Invalid ignite failure delay setting 

Lockout 

194 

Invalid ignite failure response setting 

Lockout 

195 

Invalid ignite failure retries setting 

Lockout 

196 

Invalid ignition source setting 

Lockout 

197 

Invalid interlock open response setting 

Lockout 

198 

Invalid Interlock start check setting 

Lockout 

199 

Invalid LCI enable setting 

Lockout 

200 

Invalid lightoff rate setting 

Lockout 

201 

Invalid lightoff rate proving setting 

Lockout 

202 

Invalid Main Flame Establishing Period setting 

Lockout 

203 

Invalid MFEP flame failure response setting 

Lockout 

204 

Invalid NTC sensor type setting 

Lockout 

205 

Invalid Outlet high limit response setting 

Lockout 

206 

Invalid Pilot Flame Establishing Period setting 

Lockout 

207 

Invalid PII enable setting 

Lockout 

208 

Invalid pilot test hold setting 

Lockout 

209 

Invalid pilot type setting 

Lockout 

210 

Invalid postpurge time setting 

Lockout 

211 

Invalid power up with lockout setting 

Lockout 

212 

Invalid preignition time setting 

Lockout 

213 

Invalid prepurge rate setting 

Lockout 

214 

Invalid prepurge time setting 

Lockout 

215 

Invalid purge rate proving setting 

Lockout 

216 

Invalid run flame failure response setting 

Lockout 

217 

Invalid run stabilization time setting 

Lockout 

218 

Invalid stack limit enable setting 

Lockout 

219 

Invalid stack limit enable setting 

Lockout 

224 

Invalid DHW demand source setting 

Lockout 

225 

Invalid flame threshold setting 

Lockout 

226 

Invalid outlet high limit setpoint setting 

Lockout 

228 

Invalid Stack limit setpoint setting 

Lockout 

229 

Invalid modulation output setting 

Lockout 

230 

Invalid CH demand source setting 

Lockout 

231 

Invalid Delta T limit delay setting 

Lockout 

234 

Invalid outlet high limit enable setting 

Lockout 

235 

Invalid outlet connector type setting 

Lockout 

236 

Invalid inlet connector type setting 

Lockout 

237 

Invalid DHW connector type setting 

Lockout 

238 

Invalid Stack connector type setting 

Lockout 

239 

Invalid S2 (J8-6) connector type setting 

Lockout 

240 

Invalid S5 (J8-11) connector type setting 

Lockout 

244 

Internal fault: Safety relay test invalid state 

Lockout 

246 

4-20mA cannot be used for both modulation and setpoint control 

Lockout 

250 

Invalid fan speed error message 

Lockout 

252-255 

RESERVED 

 

Содержание ProtoNode FPC-N34

Страница 1: ...up Guide For Interfacing Camus Products Sola DynaFLO Valiant To Building Automation Systems BACnet MS TP BACnet IP Metasys N2 Modbus TCP IP LonWorks and SMC Cloud APPLICABILITY EFFECTIVITY Explains P...

Страница 2: ...echnical support of the ProtoNode product MSA Safety does not provide direct support If Camus needs to escalate the concern they will contact MSA Safety for assistance Support Contact Information Camu...

Страница 3: ...de FPC N34 3 pin RS 485 port to the field protocol cabling Section 4 3 or connect the ProtoNode FPC N35 2 pin LonWorks port to the field protocol cabling Section 4 4 8 Connect power to the ProtoNode 6...

Страница 4: ...85 Device Network 25 4 6 2 End of Line Termination Switch for the RS 485 Device Network 26 4 7 Serial Network FPC N34 Wiring Field Port to RS 485 Network 27 4 8 LonWorks FPC N35 Wiring LonWorks Device...

Страница 5: ...7 Sola Modbus RTU Mappings to BACnet Metasys N2 Modbus TCP IP LonWorks 57 DynaFLO Modbus RTU Mappings to BACnet Metasys N2 Modbus TCP IP LonWorks 61 Valiant Modbus RTU Mappings to BACnet Metasys N2 Mo...

Страница 6: ...Figure 20 Web Configurator Showing Available Profile Selection 33 Figure 21 Web Configurator Showing Active Profile Additions 33 Figure 22 Web Configurator Screen with Active Profiles 34 Figure 23 Ch...

Страница 7: ...for more information about the BACnet Testing Laboratory Click here for the BACnet PIC Statement LonMark International is the recognized authority for certification education and promotion of interop...

Страница 8: ...JCI Modbus TCP IP or LonWorks 3 It is not necessary to download any configuration files to support the required applications The ProtoNode is pre loaded with tested profiles configurations for the sup...

Страница 9: ...d provides the following capabilities for any registered devices in the field Remotely monitor and control devices Collect device data and view it on the SMC Cloud Dashboard and the SMC Smart Phone Ap...

Страница 10: ...N34 FPC N34 0565 ProtoNode FPC N35 FPC N35 0566 Figure 1 ProtoNode Part Numbers FPC N34 units have the following 3 ports RS 485 Ethernet RS 485 FPC N35 units have the following 3 ports LonWorks Ether...

Страница 11: ...odbus RTU Modbus RTU Modbus RTU Baud Rate 38400 9600 19200 Parity None None None Data Bits 8 8 8 Stop Bits 1 2 1 Figure 4 COM Settings 3 3 2 Set Node ID for Any Device Attached to the ProtoNode Set No...

Страница 12: ...do not use the S bank DIP switches S0 S3 to select a field protocol o On ProtoNode FPC N35 units these switches are disabled the field protocol is always LonWorks ProtoNode FPC N34 S Bank DIP Switche...

Страница 13: ...BMS front end can find ProtoNode via BACnet Auto Discovery NOTE Never set a BACnet MS TP MAC Address of the ProtoNode to a value from 128 to 255 Addresses from 128 to 255 are Slave Addresses and canno...

Страница 14: ...lt refer to Section 5 6 3 5 3 FPC N34 Setting the Baud Rate for BMS Network DIP switches B0 B3 can be used to set the field baud rate of the ProtoNode to match the baud rate required by the BMS for BA...

Страница 15: ...DE TO DEVICES 4 1 Connection from DynaFlame Dynaforce Advantus Avenger to ProtoNode The DynaFlame Dynaforce terminals J3 MB2 are connected to the Protonode as shown Boiler 1 MB1 Modbus Address MB2 Mod...

Страница 16: ...de Start up Guide Page 16 of 87 Activating Comm Port 2 on Sola Display Select Gateway tab 1 Select Gateway tab 2 Check Enable Modbus gateway 3 Select Gateway on COM2 port 1 Select COM2 tab 2 Check Ena...

Страница 17: ...Camus ProtoNode Start up Guide Page 17 of 87 Verify activity on COM2 port COM1 Modbus data between Diana and SOLA COM2 Modbus data between Diana and front end Modbus or ProtoNode...

Страница 18: ...ng DynaMaxHS Place Local Modbus toggle switch in LOCAL Press and select Login enter sola Select Advanced Setup Select System Select System ID Access Verify MB1 Modbus address 1 To be in sequential ord...

Страница 19: ...Setup password 3232 Modbus Assign a network ID or slave address to DynaFLO s controller by pressing Network ID and inserting a number Make sure the Modbus ON is switched to Modbus ON When Modbus ON O...

Страница 20: ...s PLC Pin Number Function 1 A signal TX RX 6 B signal TX RX Having access to pins 1 and 6 of Port2 on DynaFLO by using the RJ11 6POS2C cable make connections to the Protonode according to the above t...

Страница 21: ...n from Valiant to ProtoNode The RS 485 connection is made by connecting wires from the Protonode to the terminal block located under the Valiant s control panel The designated BMS terminals are labell...

Страница 22: ...address can be changed from the Valiant s pushbutton screen To change the slave address go to Menu Settings General Settings Other Settings Modbus Address Note Do not change Modbus Stopbits Please re...

Страница 23: ...Camus ProtoNode Start up Guide Page 23 of 87 4 5 ProtoNode FPC N34 and FPC N35 Showing Connection Ports Figure 9 ProtoNode FPC N34 Top and ProtoNode FPC N35 Bottom...

Страница 24: ...PC N35 LonWorks Pins 1 through 3 are for RS 485 devices o Use standard grounding principles for RS 485 GND Pins 4 through 6 are for power Do not connect power until Section 4 5 Device Pins ProtoNode P...

Страница 25: ...biasing jumpers are OFF The OFF position is when the 2 red biasing jumpers straddle the 4 pins closest to the outside of the board of the ProtoNode Figure 11 Only turn biasing ON o IF the BMS cannot...

Страница 26: ...the pins closest to the inside of the board of the ProtoNode o On short cabling runs the EOL switch does not to need to be turned ON If the ProtoNode is placed at one of the ends of the trunk set the...

Страница 27: ...o enable the EOL termination turn the EOL switch ON switch position left side If more than one RS 485 device is connected to the network then the field bias resistor switch needs to be enabled to ensu...

Страница 28: ...LonWorks FPC N35 Wiring LonWorks Devices to the LonWorks Terminal Wire the LonWorks device network to the ProtoNode LonWorks Terminal o Use approved cable per the FT 10 installation guidelines o LonW...

Страница 29: ...se values are nominal and a safety margin should be added to the power supply of the host system A safety margin of 25 is recommended Figure 16 Required Current Draw for the ProtoNode Apply power to t...

Страница 30: ...on the 192 168 1 xxx network For Windows 10 Find the search field in the local computer s taskbar usually to the right of the windows icon and type in Control Panel Click Control Panel click Network a...

Страница 31: ...vered using the FS Toolbox utility See Appendix A 1 for instructions 5 3 Selecting Profiles for Devices Connected to ProtoNode NOTE If Modbus TCP IP was selected in Section 3 4 for the Field BMS proto...

Страница 32: ...Camus ProtoNode Start up Guide Page 32 of 87 Figure 19 Web Configurator Showing no Active Profiles...

Страница 33: ...lected from the drop down list enter the value of the device s Node ID which was assigned in Section 3 3 2 Then press the Submit button to add the Profile to the list of devices to be configured Repea...

Страница 34: ...IP Address for the Field Network Follow the steps outlined in Section 5 1 to access the ProtoNode Web Configurator To access the FS GUI click on the Diagnostics Debugging button in the bottom right c...

Страница 35: ...IP Address of that managed switch router Click the System Restart button at the bottom of the page to apply changes and restart the ProtoNode Unplug Ethernet cable from PC and connect it to the networ...

Страница 36: ...d Node_Offset Node_ID For example if the desired Device Instance for the device 1 is 50 001 and the following is true Device 1 has a Node ID of 1 Device 2 has a Node ID of 22 Device 3 has a Node ID of...

Страница 37: ...ofiles Follow the steps outlined in Section 5 1 to access the ProtoNode Web Configurator At the bottom left of the page click the Clear Profiles and Restart button Once restart is complete all past pr...

Страница 38: ...Browser Connect a Cat 5 Ethernet cable straight through or cross over between the PC and ProtoNode The default IP Address for the ProtoNode is 192 168 1 24 Subnet Mask is 255 255 255 0 If the PC and P...

Страница 39: ...rties window Open a web browser and go to the following address IP Address of ProtoNode fserver xif o Example 192 168 1 24 fserver xif If the web browser prompts to save the file save the file onto th...

Страница 40: ...ng on BACnet without having to ask the BMS integrator to test the unit To access the embedded BACnet Explorer go to the FS GUI page and click the Explorer button Then login to the BACnet Explorer page...

Страница 41: ...the BACnet Explorer landing page click on the BACnet Explorer button on the left side of the screen to go to the BACnet Explorer page To discover the devices connected to the same subnet as the BACne...

Страница 42: ...or optimal performance Any discovery or explore process will cause a green message to appear in the upper right corner of the browser to confirm that the action is complete 7 2 View Device Details and...

Страница 43: ...1 and click the Explore button that appears to the right of the highlighted device as a magnifying glass icon or double click the highlighted device o Now additional device details are viewable howeve...

Страница 44: ...indow If changes are expected since the last explore simply press the Refresh button that appears to right of individual properties to refresh the value NOTE The Explorer Search Bar will find devices...

Страница 45: ...s are editable such as object name object description etc however this is not recommended because the BACnet Explorer is a discovery tool not a Building Management System BMS To edit the present value...

Страница 46: ...t up Guide Page 46 of 87 Enter the appropriate change and click the Write button The window will close When the BACnet Explorer page appears the present value will be changed as specified Figure 39 Up...

Страница 47: ...able file and complete the installation Connect a standard Cat 5 Ethernet cable between the user s PC and ProtoNode Double click on the FS Toolbox Utility and click Discover Now on the splash page Che...

Страница 48: ...into the web browser or use the FieldServer Toolbox to connect to the ProtoNode Click on Diagnostics and Debugging Button then click on view and then on connections If there are any errors showing on...

Страница 49: ...d rate parity data bits stop bits o Check device address o Verify wiring o Verify the Modbus device s were listed in the Web Configurator Section 5 3 Field COM problems o If Ethernet protocols are use...

Страница 50: ...ormal operation ERR A steady red light will indicate there is a system error on the unit If this occurs immediately report the related system error shown in the error screen of the FS GUI interface to...

Страница 51: ...en the Diagnostic Capture is performed via the gateway s on board system Access the FieldServer Diagnostics page via one of the following methods o Open the FieldServer FS GUI page and click on Diagno...

Страница 52: ...i Fi cannot be captured if a network diagnostic is needed take a Wire Shark capture Once the Diagnostic Capture is complete email it to technical support The Diagnostic Capture will accelerate diagnos...

Страница 53: ...o Click on the Start Diagnostic button o Wait for the capture period to finish and the Diagnostic Test Complete window will appear Step 2 Send Log o Once the diagnostic test is complete a zip file is...

Страница 54: ...ft hand side do the following a Click on Setup b Click on File Transfer c Click on the General tab 5 In the General tab click on Choose Files and select the web img file extracted in step 1 6 Click on...

Страница 55: ...restart the ProtoNode The password needs to be a minimum of eight characters and is case sensitive If the password is lost click cancel on the password authentication popup window and email the passwo...

Страница 56: ...sers are supported Chrome Rev 57 and higher Firefox Rev 35 and higher Microsoft Edge Rev 41 and higher Safari Rev 3 and higher NOTE Internet Explorer is no longer supported as recommended by Microsoft...

Страница 57: ...frost protection 8 No demand due to burner switch turned off 9 DHW storage 10 Reserved 11 Warm weather shutdown Outlet sensor R 0007 0007 AI 3 AI nvoXOutletSensor SNVT_temp_p 40 130o C 0 1o C precisio...

Страница 58: ...outCode SNVT_count_f 0 No lockout 1 4096 See Appendix D 1 Alarm reason R 0023 0035 AI 18 AI nvoXAlarmReason SNVT_count_f 0 None 1 Lockout see register hex 0015 for lockout code 2 Alert Refer to Append...

Страница 59: ...21 0545 AV 64 AO nvoXLdLgMstrEnbl SNVT_count_f 0 Not a Lead Lag master 1 Lead Lag master Lead Lag setpoint R W 0222 0546 AV 65 AO nvi nvoXLdLgSetpoint SNVT_temp_p 40 200o F1 Burner cycle count R 0080...

Страница 60: ...its type the parameter has 0 RPM 1 If modulation output parameter doesn t match with the setting of this bit then the parameter setting is invalid 4 For binary fraction format commanded rate is a bina...

Страница 61: ...ite SNVT_temp_p Only Possible when the control is set to Remote Setpoint Actuator Position Write W 0061 0097 AV 5 Ana_Output nviX Actuator Position Write SNVT_count_f Only Possible when the control is...

Страница 62: ...M_Boiler_1_Active R AI 16 AI 20133 nvoBM1Act_XXX SNVT_count_f In Cascade mode only BM_Boiler_2_Active R AI 17 AI 20134 nvoBM2Act_XXX SNVT_count_f In Cascade mode only BM_Boiler_3_Active R AI 18 AI 201...

Страница 63: ...5 AI 30101 nvoBMUn11Avl_XXX SNVT_count_f In Cascade mode only BM_Unit_12_available R AI 56 AI 30102 nvoBMUn12Avl_XXX SNVT_count_f In Cascade mode only BM_Unit_13_available R AI 57 AI 30103 nvoBMUn13Av...

Страница 64: ...ID R AI 99 AI 34025 nvoError2ID_XXX SNVT_count_f Error_2_DoW R AI 100 AI 34026 nvoError2DoW_XXX SNVT_count_f Error_2_DoM R AI 101 AI 34027 nvoError2DoM_XXX SNVT_count_f Error_2_M R AI 102 AI 34028 nvo...

Страница 65: ...ToBnHr_XXX SNVT_time_hour BM_Unit_12_CurrentState R AI 133 AI 40101 nvoU12CrSt_XXX SNVT_count_f In Cascade mode only BM_Unit_12_Error R AI 134 AI 40102 nvoU12Err_XXX SNVT_count_f In Cascade mode only...

Страница 66: ...U15ClSP_XXX SNVT_temp_p In Cascade mode only BM_Unit_15_PowerLevel R AI 169 AI 40404 nvoU15PwLv_XXX SNVT_count_f In Cascade mode only BM_Unit_15_GenPumpStatus R AI 170 AI 40407 nvoU15GnPmSt_XXX SNVT_c...

Страница 67: ...voU18CrSt_XXX SNVT_count_f In Cascade mode only BM_Unit_18_Error R AI 200 AI 40702 nvoU18Err_XXX SNVT_count_f In Cascade mode only BM_Unit_18_CalcSetpoint R AI 201 AI 40703 nvoU18ClSP_XXX SNVT_temp_p...

Страница 68: ...due to safety relay OFF Lockout 17 Internal fault Safety relay test failed due to safety relay not OFF Lockout 18 Internal fault Safety relay test failed due to feedback not ON Lockout 19 Internal fau...

Страница 69: ...to IAS Lockout 59 Internal fault Mux pin shorted Lockout 60 Internal fault HFS shorted to LFS Lockout 61 Anti short cycle Hold 62 Fan speed not proved Hold 63 LCI off Hold 67 ILK off Hold 68 ILK on H...

Страница 70: ...out 145 Internal fault Flame bias out of range 3 Lockout 146 Internal fault Flame bias out of range 4 Lockout 147 Internal fault Flame bias out of range 5 Lockout 148 Internal fault Flame bias out of...

Страница 71: ...er up with lockout setting Lockout 212 Invalid preignition time setting Lockout 213 Invalid prepurge rate setting Lockout 214 Invalid prepurge time setting Lockout 215 Invalid purge rate proving setti...

Страница 72: ...could not be determined 21 Invalid safety group verification table was not accepted 22 CRC errors were found in application configuration data blocks 23 Backup Alert PCB was restored from active one 2...

Страница 73: ...75 Absolute max fan speed was out of range 76 Absolute min fan speed was out of range 77 Fan gain down was invalid 78 Fan gain up was invalid 79 Fan minimum duty cycle was invalid 80 Fan pulses per r...

Страница 74: ...nge in RUN 128 Modulation rate was limited due to IAS was open 129 Slow start ramp setting of zero will result in no modulation rate change 130 No forced rate was configured for slow start ramp 131 CH...

Страница 75: ...d Lag ON hysteresis was invalid 188 Lead Lag slave enable was invalid 189 Lead Lag hysteresis step time was invalid 190 No Lead Lag Modbus port was assigned 191 Lead Lag base load common setting was i...

Страница 76: ...ture was invalid 239 Lead Lag ODR outdoor temperature range was too small minimum 12 C 22 240 Lead Lag ODR water temperature range was too small minimum 12 C 22 F 241 Lead Lag DHW setpoint was invalid...

Страница 77: ...ormal Recycle Interrupted air flow switch was off during Measured Purge 298 Abnormal Recycle Interrupted air flow switch was off during Drive to Lightoff 299 Abnormal Recycle Interrupted air flow swit...

Страница 78: ...cle Invalid zero crossing 352 Abnormal Recycle fault stack sensor 353 Abnormal Recycle stack limit 354 Abnormal Recycle delta T limit 355 Abnormal Recycle fault outlet sensor 356 Abnormal Recycle outl...

Страница 79: ...473 Internal error PM parameter address was invalid 474 Internal error PM safety parameter address was invalid 475 Internal error Invalid record in lockout history was removed 476 Internal error EEPRO...

Страница 80: ...alid 529 Mix temperature was invalid 530 Mix sensor was invalid 531 Mix PID setpoint was invalid 532 STAT may not be a Mix demand source when Remote Stat is enabled 533 539 RESERVED 540 Delta T inlet...

Страница 81: ...ap detect ON hysteresis was invalid 595 Inlet DHW tap stop degrees was out of range 596 Outlet Inlet tap stop degrees was out of range 597 DHW tap detect on threshold was invalid 598 DHW plate preheat...

Страница 82: ...st protection is active 103 On due to Lead Lag CH frost protection is active 104 On due to local DHW frost protection is active 105 On due to Lead Lag DHW frost protection is active 106 On from local...

Страница 83: ...On Off Off 39 On On On Off Off On Off Off 40 Off Off Off On Off On Off Off 41 On Off Off On Off On Off Off 42 Off On Off On Off On Off Off 43 On On Off On Off On Off Off 44 Off Off On On Off On Off O...

Страница 84: ...136 Off Off Off On Off Off Off On 137 On Off Off On Off Off Off On 138 Off On Off On Off Off Off On 139 On On Off On Off Off Off On 140 Off Off On On Off Off Off On 141 On Off On On Off Off Off On Ad...

Страница 85: ...17 On Off Off On On Off On On 218 Off On Off On On Off On On 219 On On Off On On Off On On 220 Off Off On On On Off On On 221 On Off On On On Off On On 222 Off On On On On Off On On 223 On On On On On...

Страница 86: ...3 2 x 1 6 in Weight 0 2 kg 0 4 lbs Operating Temperature 40 C to 75 C 40 F to167 F Surge Suppression EN61000 4 2 ESD EN61000 4 3 EMC EN61000 4 4 EFT Humidity 5 90 RH non condensing Specifications subj...

Страница 87: ...ected to accident improper maintenance installation or application or on which original identification marks have been removed or altered This Limited Warranty also will not apply to interconnecting c...

Отзывы: