DynaFLO Modbus RTU Mappings to BACnet, Metasys N2, Modbus TCP/IP & LonWorks
Point Name
R/W
Modbus
Address
(hex)
Modbus
Register
(dec)
BACnet
Object
Type
BACnet
Object
ID / N2
Point
Address
N2
Data
Type
Lon Name
Lon SNVT
Note
DHW Outlet Temp
R
000A
0010
AI
1
Ana_Input
nvoX DHW Outlet
Temp
SNVT_temp_p
Setpoint Read
R
0062
0098
AI
2
Ana_Input
nvoX Setpoint Read SNVT_temp_p
Actuator Position Read
R
0060
0096
AI
3
Ana_Input
nvoX Actuator
Position Read
SNVT_count_f
Setpoint Write
W
0058
0088
AV
4
Ana_Output
nviX Setpoint Write SNVT_temp_p
Only Possible when the control is set to Remote
Setpoint
Actuator Position Write
W
0061
0097
AV
5
Ana_Output
nviX Actuator
Position Write
SNVT_count_f
Only Possible when the control is set to Remote
Direct.
Clear Alarms
W
0014
0020
BV
1/2
Dig_Output
nviX Clear Alarms
Write
SNVT_switch
If all conditions for all alarms have been
satisfied, this can ACK any pending alarm that is
not active anymore. However, this also clears
such alarms from alarm history.
General Alarm
R
0015
0021
BI
1/2
Dig_Input
nvoX General
Alarm
SNVT_switch
Low Temp Alarm
R
0018
0024
BI
2/3
Dig_Input
nvoX Low Temp
Alarm
SNVT_switch
High Temp Alarm
R
001B
0027
BI
3/4
Dig_Input
nvoX High Temp
Alarm
SNVT_switch
RTD1 Failure Alarm
R
001E
0030
BI
4/5
Dig_Input
nvoX RTD1 Failure
Alarm
SNVT_switch
AI1 Failure Alarm
R
0024
0036
BI
5/6
Dig_Input
nvoX AI1 Failure
Alarm
SNVT_switch
Low Battery
R
0027
0039
BI
6/7
Dig_Input
nvoX Low Battery SNVT_switch