Use the RJ11 cable connector shown below (provided with your DynaFLO) or a similar RJ11
(6POS2C) cable to connect to Port 2 of your DynaFLO’s PLC.
Pin Number
Function
1
A signal (+) TX+/RX+
6
B signal (-) TX-/RX-
Having access to pins 1 and 6 of Port2 on DynaFLO by using the RJ11 (6POS2C) cable, make
connections to the Protonode according to the above table:
Please refer to appendix C.2 for DynaFLO’s Modbus mapping table.
Note that DynaFLO
needs to be put into <Remote_SP> from the “Control” menu before setpoint can be
changed remotely.