Camus ProtoNode Start-up Guide
Page 19 of 87
4.3 Connection from DynaFLO to ProtoNode
Start-up screen > Setup (password:3232) > Modbus:
Assign a network ID or slave address to DynaFLO’s controller by pressing <Network ID #> and
inserting a number. Make sure the <Modbus ON> is switched to “Modbus ON”.
\
When <Modbus ON/OFF> switch turns ON, it opens Port 2 on DynaFLO’s controller and sets
the controller as a Modbus Slave.