24
* To eliminate the hard lockout error,
1) Press the
button to clear the error on screen
5.4.2
Automatic Reset Codes
Table 17: Automatic Reset Codes
#
Description
0
None
29
Burner switch turned OFF
30
Burner switch turned ON
47
Flame rod to ground leakage
49
Abnormal 24Vac voltage
50
Modulation Fault
61
Anti-short Cycle
62
Fan speed not proved
67
Interlock Off, safety circuit is open
69
Pilot test hold
78
Demand lost in run
79
Outlet high limit tripped (internal limit)
81
Delta-T limit exceeded (30
o
F)
91
Inlet sensor fault
92
Outlet sensor fault
93
DHW sensor fault
95
Stack sensor fault
96
Outdoor sensor fault
97-
99
Internal Fault
128
Fan speed failed during prepurge
129
Fan speed failed during preignition
130
Fan speed failed during ignition
131
Fan movement detected during standby
132
Fan speed failed during run
137
Interlock failed to close, safety circuit is open
110
Ignition failure occurred
111
Flame current below threshold (0.8Vdc)
149
Flame detected
150,
291
Flame not detected
301
-
310
Interlock Off, safety circuit is open
353
Stack limit (PVC: 149
o
F, CPVC: 194
o
F, PPE:
230
o
F, SS, AL29-4C: 250
o
F)
460
LCI lost in run, safety circuit is open
614
Lead boiler was rotated based on measured run
time
PART 6
CONTROL PANEL
6.1
DYNAMAX HS CONTROLLER
The appliance is provided with an operator interface panel at
the front. On a DynaMax HS Wall Hung boiler the DynaMax
HS Controller can be accessed by removing the upper
stainless steel jacket and the lower black sheetmetal jacket
which are each held on by two (2) screws. On a DynaMax HS
Floor Mount boiler the DynaMax HS Controller can be
accessed by carefully lifting off the black-coloured top cover
which is held on by four (4) snap lock fasteners.
6.2
SETTING THE DYNAMAX HS
CONTROLLER
Button
Description
Back button to return to
previous menu
Information button
Home Button returns screen
to home screen
Navigation buttons
Confirm selection
The 5-way control pad allows for easy access to various
functions on the DynaMax HS controller. A
button allows
for immediate information concerning boiler operation
including temperatures, boiler status and any errors that are
occurring.
The Boiler Temperature Controller for this appliance is the
Honeywell SOLA. It initiates the local call for heat and sets the
target return (appliance inlet) water temperature. This
controller offers a range of operation modes which provides
set point as well as modulating control. It provides the
following:
•
Readings of inlet and outlet water temperatures as well
as flame signal.
•
Operation as an auto reset limit.
•
Operation as a control for inlet water temperature, outlet
temperature, system temperature.
•
Available tank mounted sensor used in conjunction with
inlet sensor.
•
Adjustable; target temp, inter-stage differential, on delay
between stages, minimum on time per stage, minimum
off time per stage.
•
Flame failure signal.
•
Error message display in text
•
Manual override of boiler input rate for combustion
•
Pump exercising feature runs pump 10 seconds every
three days in the event of no pump operation.
Содержание DynaMax DMH201
Страница 2: ......
Страница 11: ...7 Figure 5 DynaMax HS Wall Hung Service Clearances Figure 6 DynaMax HS Floor Mount Service Clearances...
Страница 70: ...62 PART 14 EXPLODED VIEW PARTS LIST DYNAMAX HS WALL HUNG 10 May be located outside cabinet...
Страница 71: ...63 DYNAMAX HS FLOOR MOUNT 10 May be located outside cabinet...
Страница 77: ...69 11 6 Front Strut 14 8037 X X Not shown in Exploded View Part Recommended spare parts...
Страница 78: ...70 PART 15 ELECTRICAL DIAGRAMS 15 1 DM 200 299 INTERNAL WIRING DIAGRAM...
Страница 79: ...71 15 2 DM 399 800 INTERNAL WIRING DIAGRAM...
Страница 80: ...72...