6
Figure 4: DynaMax HS Floor Mount Model Dimensions
Table 5: Appliance Dimensions and Specifications
Model
Dim.
"A" [in.]
Dim.
"B" [in.]
Dim.
"C" [in.]
Dim.
"D"
[in.]
Dim.
"E" [in.]
Dim.
"F" [in.]
Dim. "J"
[in.]
Equivalent Length of Vent & Air Intake
Pipes at Recommended Diameter, [in.]
Water
Conn.
at
Heater
[in.]
NPT
Gas
Conn.
at
Boiler
[in.]
NPT
Category IV
CAT.II
Comb.
Vents
Over 25'
and up to
100'
Over 15'
and up to
25'
Up to
15'
210
42 1/2
25 3/4
14 1/4
23
24 1/4
34 1/4
32
3
3
2
4
1
1/2
260
42 1/2
25 3/4
14 1/4
23
24 1/4
34 1/4
32
3
3
2
4
1 1/4
1/2
299
47 1/8
34 7/8
14
23
29 7/8
33 7/8
32
4
3
3
5
1 1/4
3/4
399
47 1/8
34 7/8
14
23
29 7/8
33 7/8
32
4
3
3
5
1 1/2
1
500
47 1/8
34 7/8
14
23
29 7/8
33 7/8
32
4
3
3
6
1 1/2
1
600
47 1/8
36 1/4
14
23
30 3/4
38
40 1/2
4
3
3
6
2
1
700
47 1/8
36 1/4
14
23
30 3/4
38
40 1/2
4 (Air), 6
(Vent)
4
4
7
2
1
800
47 1/8
36 1/4
14
23
30 3/4
38
40 1/2
5 (Air), 6
(Vent)
5
5
7
2
1
Maintain minimum specified clearances for adequate operation. All installations must allow sufficient space for servicing the vent
connections, water pipe connections, circulating pump, bypass piping and other auxiliary equipment, as well as the appliance
Содержание DynaMax DMH201
Страница 2: ......
Страница 11: ...7 Figure 5 DynaMax HS Wall Hung Service Clearances Figure 6 DynaMax HS Floor Mount Service Clearances...
Страница 70: ...62 PART 14 EXPLODED VIEW PARTS LIST DYNAMAX HS WALL HUNG 10 May be located outside cabinet...
Страница 71: ...63 DYNAMAX HS FLOOR MOUNT 10 May be located outside cabinet...
Страница 77: ...69 11 6 Front Strut 14 8037 X X Not shown in Exploded View Part Recommended spare parts...
Страница 78: ...70 PART 15 ELECTRICAL DIAGRAMS 15 1 DM 200 299 INTERNAL WIRING DIAGRAM...
Страница 79: ...71 15 2 DM 399 800 INTERNAL WIRING DIAGRAM...
Страница 80: ...72...