background image

 

 

 

1.5.2 

End of Sequence 

1)  Setpoint temperature is satisfied.  
2)  Power to the gas valve is turned off.  
3)  Combustion air fan ramps to a stop over the factory 

preprogrammed time period.   

4)  Thermostat is now in standby mode waiting for the next 

“Call for Heat”.  

WARNING

 

To minimize the possibility of serious personal injury, fire 
or damage to your appliance, never violate the following 
safety rules.

 

 

DO NOT

 

Do  not  use  this  appliance  if  any  part  has  been 

under 

water

. The possible damage to a flooded appliance can 

be  extensive  and  present  numerous  safety  hazards. 
Immediately call a qualified service technician to inspect 
the  boiler  and  to  replace  any  part  of  the  control  system 
and any gas control which has been under water. 

 

WHAT TO DO IF YOU SMELL GAS

 

Do not try to light any appliance. • Do not touch any 
electric switch: do not use any phone in your building.  
• Immediately call your gas supplier from a neighbor’s 
phone. Follow the gas supplier’s instructions. • If you 
cannot reach your gas supplier, call the fire department. 

 

IMPORTANT

 

Consult and follow local Building and Fire Regulations and 
other Safety Codes that apply to this installation. Contact 
the local gas utility company to inspect  and authorize all 
gas and flue connections. 

Installation  and  service  must  be  performed  by  a 
qualified technician/installer, and trained by Camus® 
Hydronics.

 

 

WARNING 

Should overheating occur or the gas supply fails to shut 
off, 

DO NOT

 turn off or disconnect the electrical supply to 

the pump. Shut off the gas supply at a location external to 
the appliance. 

 

Boilers  and  water  heaters  are  heat  producing 
appliances.  To  avoid  damage  or  injury,  do  not  store 
materials  against  the  appliance  or  the  vent-air  inlet 
system. Use proper care to avoid unnecessary contact 
(especially children) with the appliance and vent-air inlet 
components.  

 

Never  cover  appliance,  lean  anything  against  it,  store 
trash or debris near it, stand on it or in any way block the 
flow of fresh air to appliance.  

 

UNDER  NO  CIRCUMSTANCES

  may  flammable 

materials such as gasoline or paint thinner be used or 
stored  in  the  vicinity  of  this  appliance,  vent-air  inlet 
system  or  any  location  from  which  fumes  could  reach 
the appliance or vent-air inlet system.  

 

A  gas  appliance  that  draws  combustion  air  from  the 
equipment room where it is installed must have a supply 
of fresh air circulating around it during burner operation 
for proper gas combustion and proper venting.  

 

1.6 

INSTALLATION CODES 

The  equipment  shall  be  installed  in  accordance  with 
those installation regulations enforced in the local area 
where  the  installation  is  to  be  made.

  These  shall  be 

carefully followed in all cases. Authorities having jurisdiction 
shall  be  consulted  before  installations  are  made.  In  the 
absence of such requirements, the installation shall conform 
to  the  latest  edition  or  current  as  amended  of  the  National 
Fuel  Gas  Code,  ANSI  Z223.1  and/or  CAN/CGAB149 
Installation  Code.  All  electrical  wiring  must  be  done  in 
accordance  with  the  requirements  of  the  authority  having 
jurisdiction  or,  in  the  absence  of  such  requirements,  with 
national electrical code, ANSI/NFPA70 and/or the Canadian 
electrical  code  part  1  CSA  C22.1.  Where  required  by  the 
authority having jurisdiction, the installation must conform to 
American Society of Mechanical Engineers Safety Code for 
Controls and Safety Devices for Automatically Fired Boilers, 
ASME CSD-1.  All boilers must conform to the latest edition 
of  the  ASME  Boiler and  Pressure  Vessel  Code,  Section  II.  
Where  required  by  the  authority  having  jurisdiction,  the 
installation  must  comply  with  the  CSA  International, 
CAN/CGA-B149  and/or  local  codes.  This  appliance  meets 
the safe lighting performance criteria with the gas manifold 
and  control  assembly  provided,  as  specified  in  the  ANSI 
standards for gas-fired units, ANSI Z21.13.  

1.7 

WARRANTY 

 

Factory warranty (shipped with unit) does not apply 
to units improperly installed or improperly operated.  

 

Factory  warranty  shall  apply  only  when  the 
appliance  is  installed  in  accordance  with  local 
plumbing  and  building  codes,  ordinances  and 
regulations, the printed instructions provided with it 
and good industry practices. 

 

Excessive 

water hardness

 causing a lime build-up 

in the stainless steel coils or tubes is not a fault of 
the  appliance  and  is  not  covered  by  warranty. 
Consult the factory for recommendations for use in 
hard water areas.

 (See Water Treatment and Water 

Chemistry)  

 

Using or storing 

corrosive chemicals

 in the vicinity 

of  this  appliance  can  rapidly  attack  the  stainless 
steel  venting  and  heat  exchanger  coils  and  voids 
warranty.

 

 

Damage  caused  by 

freezing  or  dry  firing

  voids 

warranty.

 

 

This  appliance  is  not  to  be  used  for 

temporary 

heating

 of buildings under construction.

 

 

The manufacturer shall 

NOT 

be held liable for any 

personal  injury  or  property  damage  due  to  ice 
formation  or  the  dislodging  of  ice  from  the  vent 
system or the vent termination

 

1.8 

REMOVAL OF EXISTING APPLIANCE 

When  an  existing  appliance  is  removed  from  a  common 
venting system, the common venting system is likely  to  be 
too  large  for  proper  venting  of  the  appliances  remaining 
connected  to  it.  At  the  time  of  removal  of  an  existing 
appliance,  the  following  steps  must  be  followed  with  each 
appliance  remaining  connected  to  the  common  venting 
system  placed  in  operation,  while  the  other  appliances 
remaining connected to the common venting system are not 
in operation. 

Содержание DynaMax DMH201

Страница 1: ...to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If yo...

Страница 2: ......

Страница 3: ...CHECKING GAS SUPPLY PRESSURE 16 3 5 HIGH and LOW GAS PRESSURE SWITCHES Optional 17 3 6 AIR GAS RATIO VALVE 17 3 7 BURNER 17 PART 4 WATER CONNECTION 18 4 1 FREEZE PROTECTION OUTDOOR INSTALLATION 18 4...

Страница 4: ...OLTAGE 52 9 11 COMBUSTIBLE MATERIALS 52 9 12 FREEZE PROTECTION FOR INDOOR OUTDOOR INSTALLATIONS 52 9 13 FREEZE PROTECTION FOR A HEATING BOILER SYSTEM Optional 52 PART 10 INSTALLATIONS 52 10 1 CHECKING...

Страница 5: ...e appliance 1 5 SEQUENCE OF OPERATION 1 Power switch is placed in the ON position 2 Minimum 120 VAC 60Hz single phase 15A circuit is supplied to the DynaMax HS field connection board 3 24Vac power is...

Страница 6: ...ade These shall be carefully followed in all cases Authorities having jurisdiction shall be consulted before installations are made In the absence of such requirements the installation shall conform t...

Страница 7: ...Never use a pressure washer or compressed air to clean the burner 4 Reinstall parts removed in steps 2 and 3 Be sure that vent pipe has proper pitch and is properly sealed Replace any damaged gasket o...

Страница 8: ...tection afforded by the shelter will help to minimize nuisance problems with electrical connections and will allow easier servicing of the appliance under severe weather conditions 1 11 CLEARANCE FROM...

Страница 9: ...23 1 2 19 3 3 2 1 1 4 1 2 Maintain minimum specified clearances for adequate operation All installations must allow sufficient space for servicing the vent connections water pipe connections circulat...

Страница 10: ...14 1 4 23 24 1 4 34 1 4 32 3 3 2 4 1 1 4 1 2 299 47 1 8 34 7 8 14 23 29 7 8 33 7 8 32 4 3 3 5 1 1 4 3 4 399 47 1 8 34 7 8 14 23 29 7 8 33 7 8 32 4 3 3 5 1 1 2 1 500 47 1 8 34 7 8 14 23 29 7 8 33 7 8...

Страница 11: ...7 Figure 5 DynaMax HS Wall Hung Service Clearances Figure 6 DynaMax HS Floor Mount Service Clearances...

Страница 12: ...ces vented by natural draft shall not be connected into any portion of a mechanical draft system operating under positive pressure A UL listed concentric vent air intake kit may be used with the DynaM...

Страница 13: ...minimize external sweating The following air intake options shall be utilized Outside air sealed direct vertical or horizontal Outside air ducted to jacket flange Indoor Air NOTE For wall hung units t...

Страница 14: ...ilding to minimize external sweating The following air intake options shall be utilized Outside air sealed direct vertical or horizontal Outside air ducted to jacket flange Indoor Air NOTE Sealed comb...

Страница 15: ...be located a minimum of 12 inches 0 30m away from the flue gas termination but never above 3 Air piping must terminate in a down turned elbow to avoid recirculation of flue products into the inlet ai...

Страница 16: ...other equipment In all cases local codes take precedence 6 Position the air inlet and vent terminations so they are not likely to be damaged by foreign objects or exposed to build up of debris 7 Perfo...

Страница 17: ...ing system Under these circumstances an engineered air supply is necessary If the appliance is to be installed near a corrosive or potentially corrosive air supply the appliance must be isolated from...

Страница 18: ...ssembly 3 ft 91 cm within a height of 15 ft 4 6 m above the meter regulator assembly I Clearance to service regulator vent outlet 3 ft 91 cm J Clearance to non mechanical air supply inlet to building...

Страница 19: ...1 cm within a height of 15 ft 4 6 m above the meter regulator assembly I Clearance to service regulator vent outlet 3 ft 91 cm J Clearance to non mechanical air supply inlet to building or the combust...

Страница 20: ...op and must never be smaller than the size of the connection on the appliance Sizing based on Table 8 is recommended depending on model Before operating the appliance the complete gas train and all co...

Страница 21: ...for the gas combustion process The valve is a 1 1 negative pressure gas valve The valve performs the functions of a pressure regulator safety shutoff and air gas ratio control Full closing of the val...

Страница 22: ...ty codes before proceeding If the appliance is installed above radiation level it must be provided with a low water cut off device at the time of appliance installation available from Camus Some local...

Страница 23: ...r damage Table 10 Minimal System Pipe Size Input BTU hr Water Size NPT in 199 000 1 1 4 250 000 1 1 4 299 000 1 1 2 399 000 2 500 000 2 600 000 2 700 000 2 800 000 2 4 5 HEAT EXCHANGER This appliance...

Страница 24: ...7 299 000 18 9 9 3 16 2 7 0 399 000 25 2 8 4 21 6 6 3 500 000 31 5 9 2 27 0 6 9 600 000 38 8 17 5 32 0 11 8 700 000 45 3 18 2 40 0 14 4 800 000 51 8 23 5 43 0 16 0 Table 12 Flow and Pressure Drop at...

Страница 25: ...t When testing the operation of the flow proving device always ensure that 115Vac is being supplied to the pump 4 9 WATER FLOW SWITCH Floor mount hydronic and DHW models only A paddle style water flow...

Страница 26: ...he end user the DHW tuning valve is designed to act as a maximum flow controller The tuning valve is designed to provide the correct amount of hot water for each particular DynaMax HS model and applic...

Страница 27: ...Valve Interlock J6 Safety Annunciation Alarm LCI J8 24VAC Power Inlet Outlet Sensor J9 DHW Stack Sensor 5 3 1 SERVICE PARTS The DynaMax HS Controller is not repairable Any modification or repairs will...

Страница 28: ...e upper stainless steel jacket and the lower black sheetmetal jacket which are each held on by two 2 screws On a DynaMax HS Floor Mount boiler the DynaMax HS Controller can be accessed by carefully li...

Страница 29: ...configurable parameters Delta T Outlet and Inlet water temperature differential o F LL Operating Temp Indicates temperature at modulation sensor if equipped Default S5 system sensor LL system setpoint...

Страница 30: ...tion Figure 26 Temperature screen Intermittent Pump Electrical Connection Terminals 7 and 8 115Vac relay coil Terminals 4 and 6 Normally open contacts Pump Delay Relay Constant Pump Operation Electric...

Страница 31: ...int Modulates on boiler inlet sensor default Heat demand is generated when Remote Operator is closed 1 Place both toggle switches to LOCAL 2 Press and select Login 3 Select Quick Start 4 Select CH Set...

Страница 32: ...switches to LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select CH Config 5 Select Outdoor Reset Config 6 Select Outdoor Reset and Press and select Enable 7 Set Max outdoor temp Warm weath...

Страница 33: ...nsor to J3 ECOM connector 4 Place both toggle switches in LOCAL 5 Press and select Login 6 Select Advanced Setup 7 Select CH Config 8 Select Outdoor Reset Config 9 Select Outdoor Reset and Press and s...

Страница 34: ...present 1 Place both toggle switches in LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select CH Config 5 Select Modulation rate source 4 20mA and burner on off 6 Place right hand toggle swi...

Страница 35: ...ration 5 Select Demand switch DHW switch and Press 6 Select Mod sensor Inlet and Press go to step 7 DHW Sensor operation 5 Select Demand switch Sensor only and Press 6 Select Mod sensor DHW and Press...

Страница 36: ...t Heat demand is generated when Remote Operator is closed DHW Sensor if required 1 Place both toggle switches in LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select DHW Config 5 Select Dem...

Страница 37: ...s address 1 8 Select CH Config twice 9 Select Modulation Sensor S5 10 Select Lead Lag Config 11 Select Lead Lag Master Config 12 Select Master enable Enable Fixed Setpoint operation 13 Select Setpoint...

Страница 38: ...ches in LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select System 5 Select System ID Access 6 Select MB1 Modbus address 2 To be in sequential order 7 Select MB2 Modbus address 2 To be in...

Страница 39: ...ess 6 Select S5 and Press Master Boiler 7 Place both toggle switches in LOCAL 8 Press and select Login 9 Select Advanced Setup 10 Select Lead Lag Config 11 Select Lead Lag Outdoor Reset 12 Select Outd...

Страница 40: ...stage delay 2 minutes a lag boiler will be brought online and will also fire at the base load rate specified Modulation of boilers will only occur after all boilers in the Lead Lag system are firing a...

Страница 41: ...3oC Add stage inter stage delay 722 0 64800 seconds Default 120 seconds Drop stage threshold 727 0 130oC Default 5oF 3oC Drop stage inter stage delay 731 0 64800 seconds Default 120 seconds Lead rotat...

Страница 42: ...800 Auxiliary Pump Options 2 754 16385 Ignition Parameters Preferred Lightoff Rate 666 3000 Fahrenheit o F Celcius o C Enter Into Display 20 28 9 289 10 23 3 233 0 17 8 178 10 12 2 122 20 6 7 67 30 1...

Страница 43: ...tches in LOCAL 2 Press and select Login 3 Select Quick Start 4 Select Adjustable Stack limit and enter desired stack limit rate using 5 way control and press Adjust outlet high limit Description Progr...

Страница 44: ...AL 2 Press and select Display Setup 3 Select Line that needs to be changed and press View burner run time pump cycles Description Programming Instructions To view burner run time pump cycles for maint...

Страница 45: ...out For proper operation minimum 0 8Vdc must be fed back to the module Oxide deposit on the sensor rod must be removed with steel wool DO NOT use sand paper or grit cloth since this will contaminate t...

Страница 46: ...from the system Verify that wiring is correct Flame Failure Pressing the manual OK button on the DynaMax HS Control Panel to restart the ignition sequence The boiler has failed to ignite the burner af...

Страница 47: ...rocedure Clean or replace the burner if required Air in the piping system Purge all air from the piping system Incorrect igniter gap Check that spark gap is 9 64 Auto Reset High Limit Trips The outlet...

Страница 48: ...e wired correctly Measure the resistance of the sensors 10k sensors Replace the sensor if necessary Fan Not Turning Fan refuses to rotate Alert 122 123 128 129 130 131 132 Check fan power wires Fan si...

Страница 49: ...urner switch turned OFF 30 Burner switch turned ON 47 Flame rod to ground leakage 49 Abnormal 24Vac voltage 50 Modulation Fault 61 Anti short Cycle 62 Fan speed not proved 67 Interlock Off safety circ...

Страница 50: ...turn at a time NO Verify gas valve is being powered by ignition control Check ignition speed is between 2500 to 3000 RPM using System Monitor NO Adjust ignition speed to 3000 RPM YES YES Burner light...

Страница 51: ...ressure switch tripped optional To identify the safety that is open set the multimeter to Vac and measure the voltage from one contact to ground The contacts produce a 24Vac when the circuit is closed...

Страница 52: ...he circuit is closed Is pump powered NO Check pump wiring and pump delay relay YES Is there a current transformer NO Check operation of paddle style flow switch installed on outlet of DynaMax HS YES U...

Страница 53: ...an 150o F is selected and PVC venting is used the setpoint must be reduced to below 150o F to avoid nuisance flame failures If a setpoint greater than 150o F is required venting with CPVC AL29 4C 316L...

Страница 54: ...rod Is Flame sensor plug secure NO Fasten flame sensor plug securely to flame sensor wire and check for corrosion deposits at wire terminals YES Check continuity of flame sensor wire from flame sensor...

Страница 55: ...HS must be firing before proceeding DM 0200 250 260 Figure 56 Venturi Gas Valve Assembly To adjust the high fire setting 1 Press the button 2 Select Test and press 3 Select Forced Rate and press 4 Se...

Страница 56: ...r 5 minutes DM 500 800 Figure 58 DM 500 800 Gas Valve To adjust the high fire setting 1 Press the button 2 Select Test and press 3 Select Forced Rate and press 4 Select Set High Fire Locate the input...

Страница 57: ...Profile short dense and blue Normal Flame A normal flame at 100 of burner input is blue with a well defined flame and no flame lifting Yellow Tip Yellow tipping can be caused by blockage or partial ob...

Страница 58: ...ine across the floor Check neutralized pH level regularly or as required by local jurisdiction Replace neutralizer medium as required Neutralizer medium is expected to last approximately three to six...

Страница 59: ...t it was removed NOTE When the combustion air fan is removed for any reason the inlet to the burner must be covered to prevent foreign objects from falling into the burner Always look inside the burne...

Страница 60: ...BOILER SYSTEM Optional Use only properly diluted inhibited glycol antifreeze designed for hydronic systems Camus recommends using a 30 70 mixture of glycol antifreeze to water DO NOT exceed a mixture...

Страница 61: ...s to accumulate a line scale build up Lime scale buildup This will be a NON WARRANTABLE FAILURE 2 If boiler pumps are not operated when treated water is introduced a corrosion cell may be created in t...

Страница 62: ...piping between the tank and heater and the control of water velocity as explained below are important for correct operation of your hot water heater 10 9 DOMESTIC HOT WATER WITH PLATE HEAT EXCHANGER T...

Страница 63: ...following components are needed for a Lead Lag setup 1 10k System Sensor Turn off all the boilers before beginning the setup process To setup the DynaMax HS lead lag system follow the instructions Sys...

Страница 64: ...ve NOTE Recycle power on all boilers after programming is complete if lag boilers are not discovered automatically NOTE CH Setpoint or DHW Setpoint must match Setpoint located in Lead Lag Master Confi...

Страница 65: ...eader to minimize induced flow through zones 2 Separate boiler loop as shown is recommended for system piping greater than 50 equivalent feet Pressure Reducing Valve Pressure Gauge Ball Valve Air Sepa...

Страница 66: ...Valve Air Separator Expansion Tank Zone Circulator Flow Check Valve DynaMax HS Boiler Temperature Pressure Gauge Drain Union Anti scald Mixing Valve Note 1 Size main header to minimize induced flow th...

Страница 67: ...Separator Expansion Tank Zone Circulator Flow Check Valve DynaMax HS Boiler Temperature Pressure Gauge Drain Union Anti scald Mixing Valve Note 1 Size main header to minimize induced flow through zone...

Страница 68: ...60 Figure 34 Single Boiler Hydronic Heating Direct Storage Tank Zoned Piping Arrangement Cold Water In DHW Sensor Union Direct DHW Tank Anti Scald Mixing Valve Cold Water In Hot Water Out...

Страница 69: ...Flow Check Valve DynaMax HS Boiler Master M1 Temperature Pressure Gauge Drain Union DynaMax HS Boiler Slave S2 System Sensor Note 1 Size main header to minimize induced flow through zones 2 Location...

Страница 70: ...62 PART 14 EXPLODED VIEW PARTS LIST DYNAMAX HS WALL HUNG 10 May be located outside cabinet...

Страница 71: ...63 DYNAMAX HS FLOOR MOUNT 10 May be located outside cabinet...

Страница 72: ...GM20 40 154 00 X X X 4 Heat Exchanger Flange Nuts GM10 05 012 X 5 Igniter GM10 35 108 03 X X X X X X X GM10 35 161 01 X X X 6 Flame Sensor GM10 35 109 03 X X X X X X X GM10 35 162 00 X X X 7 Igniter F...

Страница 73: ...MR6100 E X X X X VCZND6100 U X VBN3EM3POX X X VBN3FP3POX X X X 18 High Limit TCL085A X TCL110A X 19 Turn Lock Wall Hung X Floor Mount X 20 Wall Mount Back Panel 14 5402 14 5402 250 X X 21 Wall Mount F...

Страница 74: ...5506 60 75 X X X 44 Side Panel Left 14 5507 20 25 X X 14 5507 X X X 14 5507 60 75 X X X 45 Front Panel Bottom 14 5508 X X X X X X X X 46 Side Panel Left Front 14 5509 20 25 X X 14 5509 X X X X X X 48...

Страница 75: ...74 Igniter Gasket GM10 25 018 X 75 Flame Sensor Gasket GM10 25 004 X 76 Burner Refractory GM10 25 098 01 X X GM10 25 107 02 X X X X X GM10 25 128 03 X X X 77 Automatic Air Vent FV 4M1 X 78 Terminal Bo...

Страница 76: ...0566 X X X X 300611 X X X Stainless to Plastic Vent Adapter FS0604PVCR X 300537 X X 10 3 Rubber Air Sleeve 1056 22 X X X X X X 1056 33 X 1056 44 X X 1056 55 X 10 4 Burner Gasket GM10 25 074 09 X X X X...

Страница 77: ...69 11 6 Front Strut 14 8037 X X Not shown in Exploded View Part Recommended spare parts...

Страница 78: ...70 PART 15 ELECTRICAL DIAGRAMS 15 1 DM 200 299 INTERNAL WIRING DIAGRAM...

Страница 79: ...71 15 2 DM 399 800 INTERNAL WIRING DIAGRAM...

Страница 80: ...72...

Страница 81: ...ough sequential Modbus addresses Connect the system sensor to the master boiler The master boiler will use the water temperature in the primary loop to control the operation of the lead lag setup If o...

Страница 82: ...lay J4 2 3 DHW Pump 1 6hp 4 24Vac or 115Vac for pump contact 5 6 3 way diverter valve 7 Boiler pump contact 10 24Vac return 12 Ground J5 1 Interlock 2 Gas Valve contact J6 1 Blocked Flue 2 Flow switch...

Страница 83: ...excluded however if caused by appliance operation at large changes exceeding 150 F between the water temperature at inlet and appliance temperature or operating at temperatures exceeding 210o F BURNE...

Страница 84: ...ing boilers as well as a supplier of specialty HVAC products Our service line is open 24 hours 7 days a week The CAMUS CERTIFIED seal assures you that Reliability Efficiency Serviceability are built i...

Отзывы: