Transparent mode is entered while the computer is communicating with the data logger through
a terminal emulator program. It is accessed through Campbell Scientific data logger support
software or other terminal emulator programs. Data logger keyboards and displays cannot be
used.
In
Device Configuration Utility
connect to your data logger. Click the Terminal tab.
Watch
videos/sdi12-sensors-transparent-mode
from our website.
Data loggers from other manufacturers will also have a transparent mode. Refer to those
manuals on how to use their transparent mode.
The following examples show how to enter transparent mode and change the SDI-12 address of
an SDI-12 sensor. The steps shown in
(p. 35) are used with most
Campbell Scientific data loggers.
B.2.1 Changing an SDI-12 address
This example was done with a CR1000X, but the steps are only slightly different for CR6, CR3000,
CR800-series, CR350-series, CR300-series, CR1000 data loggers.
1. Connect an SDI-12 sensor to the CR1000X.
2. Open
Device Configuration
utility.
3. Under Device Type, type the data logger model and double-click on the model type. This
example uses a CR1000X directly connected to the computer USB port.
Wintersense SDI-12
35