l
Click the Send button and select the WINTERSENSE_nnn.xobj file from the
C:\Campbellsci\Lib\OperatingSystems directory. File type needs to be changed to All
Files (*.*) for the .xobj file to show up on the list.
l
Verify that the .xobj file is now on the data logger CPU drive.
3. Connect the sensor to the data logger digital and power terminals. Note the terminal the
sensor is connected to. See
(p. 8) for more information.
4. Open a terminal interface to the data logger. Press Enter twice within the terminal window
to get a command prompt.
5. Within the terminal, run the following commands:
l
Type
SDI12
at the prompt and then enter the corresponding number assigned to
the digital terminal the sensor is connected to.
l
Identify the SDI12 address of the sensor by typing
?!
at the prompt.
l
Verify that the responding sensor is the Wintersense SDI-12 that you want to update
by using the SDI12 verify command
aI!
.
6. Send the OS to the sensor with the
XLOADOS
extended command in the following format:
l
<address>XLOADOS <baud rate> <OS name>!
l
For example, this update command would be entered as:
0XLOADOS 9600 CPU:WINTERSENSE_nnn.XOBJ!
NOTE:
The CR300-series data loggers are case sensitive, and the file name must match the
name used in the command. The All Caps checkbox on the bottom will need to be
unchecked to allow lower cases.
Wintersense SDI-12
23