7.1 Wiring
The Wintersense SDI-12 cable has an M12 connector on one end and terminates in individual
wires at the other. See
(p. 8). Connect the wires in the order shown in the following
table.
Table
7-1:
Wire
colo
ur
,
function,
and
data
logger
connection
Wire
colo
ur
Wire function
Data logger connection
Pin
White
SDI-12 signal
C or U configured for SDI-12
1
6
Clear
Shield
G
None
Brown
Power
12V
5
Black
Power ground
G
8
1
C and U terminals are automatically configured by
SDI12Recorder()
.
If multiple SDI-12 sensors are connected to a data logger, Campbell Scientific recommends using
separate terminals when possible. However, multiple SDI-12 sensors can connect to the same
data logger control or U terminal. Each must have a unique SDI-12 address. Valid addresses are 0
through 9, a through z, and A through Z.
For the CR6 and CR1000X data loggers, triggering conflicts may occur when a companion
terminal is used for a triggering instruction such as
TimerInput()
,
PulseCount()
, or
WaitDigTrig()
. For example, if the Wintersense SDI-12 is connected to C3 on a CR1000X, C4
cannot be used in the
TimerInput()
,
PulseCount()
, or
WaitDigTrig()
instructions.
Figure 7-1. M12 connector pinout
7.2 Programming
Short Cut
is the best source for up-to-date programming code for Campbell Scientific data
loggers. If your data acquisition requirements are simple, you can probably create and maintain a
Wintersense SDI-12
8