SECTION 11. OUTPUT PROCESSING INSTRUCTIONS
11-5
The year is output as 19xx if xx is greater than
85, otherwise it will be output as 20xx. The
CR7 will require a PROM update in the year
2085. If year is output along with a 2 option in
day or hour-minute, the previous year will be
output during the first minute of the new year.
CODE RESULTS
xxx1
SECONDS (with a resolution of 0.1 sec.)
xx1x
HOUR-MINUTE
xx2x
HOUR-MINUTE, 2400 instead of 0000
x1xx
DAY OF YEAR
x2xx
DAY OF YEAR, previous day during
first minute of new day
1xxx
YEAR
Any combination of Year, Day, HR-MIN, and
seconds is possible (e.g., 1011: YEAR, HR-
MIN, SEC).
PAR.
DATA
NO.
TYPE
DESCRIPTION
01:
4
Enter appropriate TIME
option code
Outputs generated: 1 for each time parameter
selected
*** 78 SET HIGH OR LOW RESOLUTION ***
FINAL STORAGE FORMAT
FUNCTION
This instruction sets the Final Storage Format to
high resolution (5 character) or low resolution
(4 character, Section 2.2). Instruction 78 should
be entered ahead of the output instructions for
which the specified resolution is desired. The
default format is low resolution. At the
beginning of each program table execution, the
low resolution format is automatically enabled.
PAR.
DATA
NO.
TYPE
DESCRIPTION
01:
2
0 = low resolution;
1 = high resolution
Outputs generated: 0
*** 79 SAMPLE ON MAXIMUM ***
OR MINIMUM
FUNCTION
Instruction 79 samples specified input location
values at the time a new maximum or minimum
value is detected by a previous Maximize (73)
or Minimize (74) Instruction. When the Output
Flag is set, the values are transferred to Final
Storage.
Instruction 79 must directly follow the maximum
or minimum Instruction to which it refers. If the
previous Instruction 73 or 74 has more than 1
repetition, Instruction 79 will sample whenever a
new maximum or minimum is detected in any of
the locations. If sampling is to occur only when
a specific input location shows a new maximum
or minimum, the previous Maximize or Minimize
Instruction should have 1 repetition referring to
that input location.
PAR.
DATA
NO.
TYPE
DESCRIPTION
01:
2
Repetitions (number of
sequential locations to sample)
02:
4
Starting input location number
Outputs generated: 1 per repetition
*** 80 SET ACTIVE OUTPUT AREA ***
Instruction 80 is used to direct Output data to
Final Storage or to Input Storage. At the
beginning of each table the Active Output area
is set to Final Storage. When directed to Final
Storage, the second parameter can be used to
set the output array ID. If 80 is used to direct
output to Final Storage, and Parameter 2 is 0,
the array ID is determined by the instruction
location number of Instruction 80 or by the
Instruction that set the Output Flag, whichever
came last. When data is sent to Input Storage,
no array ID is sent.
Содержание CR7
Страница 2: ...This is a blank page ...
Страница 4: ...This is a blank page ...
Страница 28: ...CR7 MEASUREMENT AND CONTROL SYSTEM OVERVIEW OV 18 This is a blank page ...
Страница 38: ...SECTION 1 FUNCTIONAL MODES 1 10 This is a blank page ...
Страница 42: ...SECTION 2 INTERNAL DATA STORAGE 2 4 This is a blank page ...
Страница 52: ...SECTION 3 INSTRUCTION SET BASICS 3 10 This is a blank page ...
Страница 57: ...SECTION 4 EXTERNAL STORAGE PERIPHERALS 4 5 FIGURE 4 4 1 Example of CR7 Printable ASCII Output Format ...
Страница 58: ...SECTION 4 EXTERNAL STORAGE PERIPHERALS 4 6 This is a blank page ...
Страница 68: ...SECTION 6 9 PIN SERIAL INPUT OUTPUT 6 6 This is a blank page ...
Страница 140: ...SECTION 13 CR7 MEASUREMENTS 13 16 FIGURE 13 5 1 Circuits Used with Instructions 4 9 ...
Страница 162: ...APPENDIX A GLOSSARY A 4 This is a blank page ...
Страница 164: ...B 2 This is a blank page ...
Страница 170: ...APPENDIX C BINARY TELECOMMUNICATIONS C 6 This is a blank page ...
Страница 173: ...APPENDIX D CALIBRATION PROCEDURES D 3 FIGURE D 2 1 Calibration Points for the Analog Interface Card ...
Страница 174: ...APPENDIX D CALIBRATION PROCEDURES D 4 FIGURE D 2 2 CR7X CPU Card ...
Страница 186: ...CR7 INDEX I 8 This is a blank page ...