SECTION 11. OUTPUT PROCESSING INSTRUCTIONS
Instructions 73 – Maximum and 74 – Minimum have only one time option. (Time is output as a quoted
string.) Instruction 80 – Set Active Storage Area, is not in the TD operating system. Its functions are
included in Instruction 84 – Data Table. Instruction 84 is only in the TD operating system.
*** 73 MAXIMUM ***
FUNCTION
This instruction stores the MAXIMUM value
taken (for each input location specified) over
a given output interval. An internal FLAG is
set whenever a new maximum value is seen.
This FLAG may be tested by Instruction 79.
Time of occurrence maximum value(s) is
OPTIONAL output information, which is
formatted and activated by entering one of
the following CODES for Parameter no. 2.
CODE
OPTIONS
00
Output value ONLY
01
Output value with TIME
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
01:
2
Repetitions
02:
2
Time of maximum
(optional)
03:
4
Starting input location no.
Outputs Generated: 1 for each input location
(plus 1 with time of max. option)
*** 74 MINIMUM ***
FUNCTION
Operating in the same manner as Program 73,
this instruction is used for storing the MINIMUM
value (for each input location specified) over a
given output interval.
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
01:
2
Repetitions
02:
2
Time of minimum
(optional)
03:
4
Starting input location no.
Outputs Generated: 1 for each input location
(plus 1 with time of min. option)
*** 84 DATA TABLE ***
FUNCTION
Instruction 84 is used to define a table of final
storage data. New records of data are stored in
the table based on time (interval data) or when
a user flag (CR10X flags 1-8) is set (event
data). Time based output intervals are
specified in seconds. Fractional values may be
used following the same rules that apply for the
table scan rate.
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
01:
FP
Time into interval (Seconds)
02:
FP
Time interval (Seconds)
0 = Store new record
each time.
-a = Store if user flag
"a" is set (a=1..8)
03:
FP
Number of records in table
0 = automatically allocates
number of records.
If 0 and parameter 2 = -a
(event driven) or if 0 and
parameter 2 = 0 then
allocates size as if a 1
second output table
-x = redirect to input loc x
Parameter 1 specifies how many seconds into
the interval, specified in parameter 2, data will
be output to final storage. If the output is event
driven, enter a 0 for parameter 1.
Parameter 2 specifies the output interval
(seconds) for the table. If output is determined
by a flag, -a should be used, ('a' is the flag to
be tested). If Parameter 2 = 0, data will be
output unconditionally each time Instruction 84
is executed.
Parameter 3 specifies how many records will be
stored in the table. When the table is full,
subsequent new records will overwrite the oldest
Содержание CR23X
Страница 8: ...CR23X TABLE OF CONTENTS vi This is a blank page ...
Страница 12: ...CR23X MICROLOGGER OVERVIEW OV 2 1 2 3 A 4 5 6 B 7 8 9 C 0 D FIGURE OV1 1 CR23X Micrologger ...
Страница 34: ...CR23X MICROLOGGER OVERVIEW OV 24 This is a blank page ...
Страница 50: ...SECTION 1 FUNCTIONAL MODES 1 16 This is a blank page ...
Страница 72: ...SECTION 4 EXTERNAL STORAGE PERIPHERALS 4 8 This is a blank page ...
Страница 88: ...SECTION 6 9 PIN SERIAL INPUT OUTPUT 6 10 This is a blank page ...
Страница 103: ...SECTION 7 MEASUREMENT PROGRAMMING EXAMPLES 7 15 CR23X AVW1 FIGURE 7 15 2 Well Monitoring Example ...
Страница 110: ...SECTION 7 MEASUREMENT PROGRAMMING EXAMPLES 7 22 This is a blank page ...
Страница 134: ...SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES 8 24 This is a blank page ...
Страница 164: ...SECTION 9 INPUT OUTPUT INSTRUCTIONS 9 30 This is a blankpage ...
Страница 188: ...SECTION 11 OUTPUT PROCESSING INSTRUCTIONS 11 8 This is a blankp age ...
Страница 221: ...SECTION 13 CR23X MEASUREMENTS 13 21 FIGURE 13 5 1 Circuits Used with Instructions 4 9 ...
Страница 229: ...14 3 1 2 3 A 4 5 6 B 7 8 9 C 0 D FIGURE 14 3 1 CR23X Battery Pack and Panel ...
Страница 239: ...SECTION 14 INSTALLATION AND MAINTENANCE 14 13 S A N Y O FIGURE 14 11 6 Removal of band clamp and battery ...
Страница 240: ...SECTION 14 INSTALLATION AND MAINTENANCE 14 14 This is a blank page ...
Страница 244: ...APPENDIX A GLOSSARY A 4 This is a blank page ...
Страница 268: ...APPENDIX B CONTROL PORT SERIAL I O INSTRUCTION 15 B 24 This is a blank page ...
Страница 276: ...APPENDIX C BINARY TELECOMMUNICATIONS C 8 This is a blank page ...
Страница 278: ...This is a blank page ...
Страница 282: ...APPENDIX F DYNAGAGE SAP FLOW P67 F 4 This is a blank page ...
Страница 299: ...APPENDIX I TD OPERATING SYSTEM ADDENDUM FOR CR510 CR10X AND CR23X MANUALS ...
Страница 300: ...This is a blank page ...
Страница 302: ...This is a blank page ...
Страница 308: ...TABLE DATA ADDENDUM AD 6 This is a blank page ...
Страница 324: ...TD ADDENDUM SECTION 1 FUNCTIONAL MODES AD 1 8 This is a blank page ...
Страница 340: ...TD ADDENDUM SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES AD 8 10 This is a blank page ...
Страница 342: ...This is a blank page ...
Страница 373: ...This is a blank page ...